36
MCA
Menu
Tree
Line No.
(Section
6022)
Message Displayed
Associated
with...
Definition
Can this value
be changed?
119
VACANT ****A = ##
or
****A PLACES = ##
Inventory
Menu
Displays number of Rectifier Module
(PCU) mounting positions available
for type of Rectifier Module (PCU)
(amperage)
***A = the designation of the
Rectifier Module (PCU) type.
## = number of positions available
for that type of Rectifier Module
(PCU).
Press the FUNCTION SELECT UP or
DOWN arrow pushbutton to display
an entry. Press the ALARM CUTOFF
and FUNCTION SET ENTER
pushbuttons simultaneously to
change the value of the displayed
entry. The display changes to "***A
PLACES = ##", where *** is the
Rectifier Module (PCU) amperage
and ## is the total (filled and empty)
number of available mounting
positions in the system for this
amperage Rectifier Module (PCU).
Use the FUNCTION SET YES (+) or
NO (-) pushbutton to increment or
decrement, respectively, the value.
Press the FUNCTION SET ENTER
pushbutton a second time to lock
the value being displayed. At the
"ARE YOU SURE? + -" prompt, press
either the FUNCTION SET YES (+)
pushbutton to accept the new
setting, or the FUNCTION SET NO
(-) pushbutton to cancel this
operation without changing the
existing setting.
Yes, see "Initially
Starting the
System" in the
separate
Installation
Instructions
(Section 6012)
.