Vertiv
|
+24 VDC Power System User Manual (Section 6013)
|
Rev. G
70
To Display Remote Access Password
NOTE!
The default MCA Remote Access Password is VORTEX, in all capital letters.
Local Procedure
1.
With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET
ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the
FUNCTION SET ENTER pushbutton. Repeatedly press and release the FUNCTION SELECT DOWN
arrow pushbutton until "FUNCTION MENU" is displayed. Press and release the FUNCTION SET ENTER
pushbutton.
2.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "CONFIGURE
MENU" is displayed.
3.
Press and release the FUNCTION SET ENTER pushbutton.
4.
"VERIFY INVENTORY" is displayed. Press and release the FUNCTION SET ENTER pushbutton.
5.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "REMOTE
INSTALLED" or "REMOTE ACTIVE" is displayed.
6.
With "REMOTE INSTALLED" or "REMOTE ACTIVE" being displayed, press and release the ALARM
CUTOFF, FUNCTION SELECT UP, and FUNCTION SELECT DOWN pushbuttons simultaneously.
The Remote Access Password is displayed.
The display automatically times out, or press the FUNCTION SELECT UP or FUNCTION SELECT DOWN
arrow pushbutton to return to the previous display.
Remote Procedure
None
To Move Back to the Beginning of the MCA Logic Tree
Procedure
1.
Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously.
To View Active Alarms
Procedure
1.
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the
FUNCTION SET ENTER pushbutton. Refer to the ALARM MENUS in "Navigating the MCA" for
additional information.