Intrepid 1640 Woodburning Stove

30000830

SAFETY NOTICE:  IF YOUR STOVE  IS NOT PROP-
ERLY INSTALLED, OPERATED AND MAINTAINED, A 
HOUSE FIRE MAY RESULT.  FOR SAFETY, FOLLOW 
ALL INSTALLATION, OPERATION AND MAINTE-
NANCE DIRECTIONS.  CONTACT LOCAL BUILDING 
OFFICIALS ABOUT RESTRICTIONS AND IN�.

Before you begin an installation, review your plans to 
be certain that:

• 

Your stove and chimney connector will be far 
enough from combustible material to meet all clear-
ance requirements.

• 

The floor protector is large enough and is construct-
ed properly to meet all requirements.

• 

You have all necessary permits from local authori-
ties.

Your local building official is the final authority for ap-
proving your installation as safe and determining that it 
meets local and state codes.
The metal label permanently attached to the back of  
the stove indicates that the Intrepid has been tested 
to current UL and ULC standards by CSA.  Clear-
ance and installation information is also printed on the 
label.  Local authorities generally will accept the label 
as evidence that, when the stove is installed according 
to the information on the label and in this manual, the 
installation meets codes and can be approved. Codes, 
however, vary in different areas.  Before starting the 
installation, review your plans with the local building 
authority.  Your local dealer can provide any additional 
information needed.
For any unresolved questions about installation, refer 
to the National Fire Protection Association’s publication 
ANSI/NFPA 211–1988 Standard for Chimneys, Fire-
places, Vents and Solid Fuel Burning Appliances.  In 
Canada, the equivalent publication is CSA CAN-B365, 
Installation Code for Solid Fuel Burning Appliances and 
Equipment.  These standards are the bases for many 
national codes.  They are nationally recognized and are 
accepted by most local authorities.  Your local dealer 
or your local building official may have a copy of these 
regulations.  

IMPORTANT:  FAILURE TO FOLLOW THESE IN-
STALLATION INSTRUCTIONS MAY RESULT IN A 
DANGEROUS SITUATION, INCLUDING A CHIMNEY 
OR HOUSE FIRE.  FOLLOW ALL INSTRUCTIONS 
EXACTLY AND DO NOT ALLOW MAKESHIFT COM-
PROMISES TO ENDANGER PROPERTY AND PER-
SONAL SAFETY.

Installation

2' Min.

2' Min.

3'

Min.

0 To 10'

3'

Min.

0 To 10'

AC617

RLTSKC8

2/11/98

Fig. 2

   The 2’-3’-10’ Chimney Rule.

Reference Point

AC617

Chimneys

Your stove must  be connected either to a sound 
masonry chimney that meets local codes, to a relined 
masonry chimney that meets local codes, or to an 
approved prefabricated metal chimney.  Whichever of 
those types you use, the chimney and chimney connec-
tor must be in good condition and kept clean.
If you use an existing masonry chimney, it must be 
inspected to ensure safe condition before the stove is 
installed.  Your local professional chimney sweep, build-
ing inspector, or fire department official will be able to 
make the inspection or direct you to someone who can.
The chimney should extend at least 3’ (914mm) above 
the highest point where it passes through a roof, and at 
least 2’ (610mm) higher than any portion of a building 
within 10’ (3m).
To assure proper draft and good performance, any 
chimney used with this stove should extend at least 16’ 
(5 m) above the flue collar of the stove.

Masonry Chimneys

An existing masonry chimney must be inspected to con-
firm that it has a lining.  Do not use an unlined chimney.  
The chimney also  should be examined for cracks, 
loose mortar, other signs of deterioration, and blockage.  
Repair any defects before the chimney is used with 
your stove.  

ST241

chimney types

12/13/99   djt

Fig. 3   

Standard Chimney Types

A prefabricated double-
wall insulated chimney

A tile-lined 
masonry 
chimney

ST241

f i r e - p a r t s . c o m

Содержание Intrepid 1640

Страница 1: ...LURE TO FOLLOW INSTRUCTIONS MAY RESULT IN PROPERTY DAMAGE BODILY INJURY OR EVEN DEATH CONTACT LOCAL BUILDING OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION INSPECTION REQUIREMENTS IN YOUR AREA Do Not D...

Страница 2: ...hat you hire a professional solid fuel stove technician to install your Intrepid or to advise you on the installation should you attempt to install it yourself Consult the authority having local juris...

Страница 3: ...e content of the fuel used as well as the design construction and climatic location of your home Figures shown are based on maximum fuel consumption obtained under laboratory conditions and on average...

Страница 4: ...re the bases for many national codes They are nationally recognized and are accepted by most local authorities Your local dealer or your local building of cial may have a copy of these regulations IMP...

Страница 5: ...the ue Chimney connectors are used only to make the connection from the stove to the chimney They are for interior use only Double wall connectors must be tested and listed for use with solid fuel bur...

Страница 6: ...ns Securing the Single wall Connector to a Prefabricated Chimney Follow the installation instructions of the chimney manufacturer exactly Special adaptors are available from your local dealer to make...

Страница 7: ...lding inspector before you begin Also check with the chimney connector manu facturer for any speci c requirements Consult with your dealer regarding special connection components available for use as...

Страница 8: ...ired 18 457mm clearance around the connector The resulting space must remain empty A ush mounted sheet metal cover may be used on one side only If covers must be used on both sides each cover must be...

Страница 9: ...um oor protector requirement from the front of the stove 16 416 mm from the front in the United States and 18 457 mm from the front in Canada The optional 3 75 mm legs may be used only on hearths that...

Страница 10: ...or chimney connector and nearby walls oors the ceiling and any other xed combustible surface Keep furnishings and other combustible materials away from the stove as well In general a distance of 48 12...

Страница 11: ...D C E A D ST509a Wall shield BB 11 00 ST509a Fig 19 Corner installation vertical chimney connector two wall shields B B A D A C C A D A ST510 Wall shield cc 11 00 A 1 25mm B 34 864mm C 48 1219mm D 35...

Страница 12: ...om the stove s top plate With a ventilated shield this clearance may be reduced safely to 14 357mm Unprotected top trim B protruding 2 51mm or less from the face of the replace must be a minimum of 24...

Страница 13: ...Alcove side view 11 10 00 djt Metal stud A This area from 62 to 65 must be covered with a non combustible material 7 16 Durock or equivalent Fig 23 Alcove side section Joist shield supplied by chimne...

Страница 14: ...Chimney Connector Clearance Stove Clearance I 12 305 mm 48 1219 mm Front Clearance to Combustibles Side Rear Corners NA NA Q 9 229 mm P 12 305 mm J 12 305 mm K 9 229 mm L 10 254 mm I 12 305 mm H 16 4...

Страница 15: ...s 11 00 P Q M N C N A N A Top Exit No Chimney Connector Shields Rear Exit Top Exit with Chimney Connector Shields or Double wall Chimney Connector Stove Installed Par allel to Wall Stove in Corner Unp...

Страница 16: ...Have an assistant tilt the stove while you install rst the back and then the front legs using the four 3 8 16 x 1 hex head bolts with 3 8 washers from the parts bag The shoulder of the legs should se...

Страница 17: ...s provided in the kit to attach the adaptor to the center mounting ange at the bottom of the Rear Shroud Install Smokeshelf Firebricks Look inside the rebox and locate the position for the Smokeshelf...

Страница 18: ...insulated and weather tight poor draft may result from insuf cient air in the house In such cases a slightly opened window near the stove on the windward side of the house will pro vide the fresh air...

Страница 19: ...t can be broken with a sharp blow from a hammer or from the thermal shock of rapid and extreme temperature change The cast plates expand and contract with changes in tempera ture When you rst begin us...

Страница 20: ...and ULC S627 for Canada Your stove may be used as a replace with the front doors open or removed only when the spark screen is placed correctly in the opening to protect against the possibility of spa...

Страница 21: ...rd from the rebricks to the grate where it will fall into the ashpan for easy removal Remove ash before it reaches the top of the ash pan Check the level at least once a day and before each re fueling...

Страница 22: ...st clean the areas to be painted with a wire brush Then touch up the stove with Vermont Castings high tem perature stove paint Apply the paint sparingly and keep in mind that two light coats of paint...

Страница 23: ...f necessary Failure to keep the chimney and connector system clean can result in a serious chimney re When wood is burned slowly it produces tar organic vapors and moisture that combine to form creoso...

Страница 24: ...on this Close and lock the door or damper on a slip of paper and then try to pull the paper out If the paper pulls out with little or no resistance the gasket isn t snug enough at that spot If adjusti...

Страница 25: ...temperatures Because the insulation is less dense than masonry the inner steel liner warms up more quickly than a masonry chimney Although steel chimneys are not as attractive as their masonry counter...

Страница 26: ...wood is Purchase your fuel from a reputable dealer Creosote Creosote is a by product of low temperature stove operations weak draft or both It is a tar that results when unburned gases condense insid...

Страница 27: ...eed to be attentive in timing the use of the other appliances If you need to crack a nearby window or door to enable the chimney to pull well you should install an outside air intake to bring combusti...

Страница 28: ...de See Chart Pg 29 4 Secondary Air Manifold Right 30000819 5 Left Side See Chart Pg 29 6 Secondary Air Manifold Left 30000820 7 1 4 20 x 2 1 4 CS Hex Hd Screw 2 1201403 8 Secondary Air Tube A 30000825...

Страница 29: ...Flue Collar Heat Shield 30000863 69 Rear Convection Shroud 30000826 70 10 x 1 2 Blk Phillips Sheetmetal Screw 2 1202058 72 Faucet Stub Chrome w Shaft 5004245 73 Ashpan Front 1306493 74 Ashpan Handle...

Страница 30: ...30 Intrepid 1640 Woodburning Stove 30000830 fire parts com...

Страница 31: ...y relevant information or circumstances regarding determi nation of failure 5 In addition the owner must return the failed catalyst Exclusions Limitations 1 This warranty is transferable however proof...

Страница 32: ...CFM Specialty Home Products 410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 905 670 7777 www majesticproducts com www vermontcastings com CFM Specialty Home Products fire parts com...

Отзывы: