Intrepid 1640 Woodburning Stove

30000830

Connection Above the Fireplace

In this installation, the chimney connector enters the 
fireplace flue though a thimble located above the fire-
place.  The liner of the fireplace chimney should extend 
at least to the point at which the chimney connector 
enters the chimney.  Follow all the guidelines for install-
ing a chimney connector into a freestanding masonry 
chimney, and pay special attention to these additional 
points:

• 

Check the stove and chimney connector clearances 
to combustible mantel and trim materials.  If neces-
sary, use a combination of mantel, trim, and connec-
tor heat shields to provide the required clearances. 
Refer to Page 12.

• 

Double-check connector clearance to the ceiling.

• 

The fireplace damper must be closed and sealed to 
prevent room air from being drawn up the flue which 
could reduce performance.  However, it must be 
possible to reopen the damper to inspect or clean 
the chimney.

• 

Floor protection requirements also apply to fireplace 
installations. Refer to Page 8.

ST244a
Intrepid
fplc over mantel
12/00

Fig. 7 

  If the clearance between the chimney connector and 

either the ceiling or the mantel is inadequate, a  protective 
heat shield is required.

Mantel

With Chimney Con-
nector Heat Shields 

10” 

(250 mm)

10”  

(250 mm)

ST244a

Wall Pass-throughs

Whenever possible, design the installation so that the 
connector does not pass through a combustible wall.  
If you must include a wall pass-through in your instal-
lation, check with your building inspector before you 
begin.  Also check with the chimney connector manu-
facturer for any specific requirements.
Consult with your dealer regarding special connection 
components available for use as wall pass-throughs.  
Use only parts that have been tested and listed for 
use as a wall pass-through. Refer to Figures 9 - 12 for 
further details.

U.S. Requirements:

The National Fire Protection Association (NFPA) has 
established guidelines for use in the United States for 
passing chimney connectors through combustible walls.  
Many building code inspectors follow these guidelines.  
Figure 9 shows one NFPA-approved method.  All com-
bustible material in the wall is cut away to provide 12” 
(305mm) clearance to the connector.  Brick and mortar 
are used to enclose the clearance area.

ST272
masonry wall pass through
w/ single wall
connector
12/99

Min. 2” (51mm) Chimney clear-
ance to brick and combustibles

A

 = Minimum 12” (305 mm) brick con-

struction between liner and combustible 
framing materials

Min. 12” 

(305 mm) 

Fire clay 
liner

A

A

Chimney Flue

Fire clay liner 

Masonry 
Chimney 
constructed 
to NFPA 211

Fig. 9

   Masonry Wall Pass-through with single wall 

chimney connector.

Chimney con-
nector

Alternate Methods Approved by the NFPA: 

• 

Using a section of double-wall chimney with a 9” 
(229mm) clearance to combustibles. (Fig. 10)

• 

Placing a chimney connector pipe inside a steel 
double-wall ventilated thimble, which is then sepa-
rated from combustibles by 6” (152mm) of fiberglass 
insulating material. (Fig. 11)

• 

Placing a chimney connector pipe inside a section 
of 9” (229mm) diameter, solid-insulated, factory-built 
chimney, with two inches of air space between the 
chimney section and combustibles. (Fig. 12)

f i r e - p a r t s . c o m

Содержание Intrepid 1640

Страница 1: ...LURE TO FOLLOW INSTRUCTIONS MAY RESULT IN PROPERTY DAMAGE BODILY INJURY OR EVEN DEATH CONTACT LOCAL BUILDING OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION INSPECTION REQUIREMENTS IN YOUR AREA Do Not D...

Страница 2: ...hat you hire a professional solid fuel stove technician to install your Intrepid or to advise you on the installation should you attempt to install it yourself Consult the authority having local juris...

Страница 3: ...e content of the fuel used as well as the design construction and climatic location of your home Figures shown are based on maximum fuel consumption obtained under laboratory conditions and on average...

Страница 4: ...re the bases for many national codes They are nationally recognized and are accepted by most local authorities Your local dealer or your local building of cial may have a copy of these regulations IMP...

Страница 5: ...the ue Chimney connectors are used only to make the connection from the stove to the chimney They are for interior use only Double wall connectors must be tested and listed for use with solid fuel bur...

Страница 6: ...ns Securing the Single wall Connector to a Prefabricated Chimney Follow the installation instructions of the chimney manufacturer exactly Special adaptors are available from your local dealer to make...

Страница 7: ...lding inspector before you begin Also check with the chimney connector manu facturer for any speci c requirements Consult with your dealer regarding special connection components available for use as...

Страница 8: ...ired 18 457mm clearance around the connector The resulting space must remain empty A ush mounted sheet metal cover may be used on one side only If covers must be used on both sides each cover must be...

Страница 9: ...um oor protector requirement from the front of the stove 16 416 mm from the front in the United States and 18 457 mm from the front in Canada The optional 3 75 mm legs may be used only on hearths that...

Страница 10: ...or chimney connector and nearby walls oors the ceiling and any other xed combustible surface Keep furnishings and other combustible materials away from the stove as well In general a distance of 48 12...

Страница 11: ...D C E A D ST509a Wall shield BB 11 00 ST509a Fig 19 Corner installation vertical chimney connector two wall shields B B A D A C C A D A ST510 Wall shield cc 11 00 A 1 25mm B 34 864mm C 48 1219mm D 35...

Страница 12: ...om the stove s top plate With a ventilated shield this clearance may be reduced safely to 14 357mm Unprotected top trim B protruding 2 51mm or less from the face of the replace must be a minimum of 24...

Страница 13: ...Alcove side view 11 10 00 djt Metal stud A This area from 62 to 65 must be covered with a non combustible material 7 16 Durock or equivalent Fig 23 Alcove side section Joist shield supplied by chimne...

Страница 14: ...Chimney Connector Clearance Stove Clearance I 12 305 mm 48 1219 mm Front Clearance to Combustibles Side Rear Corners NA NA Q 9 229 mm P 12 305 mm J 12 305 mm K 9 229 mm L 10 254 mm I 12 305 mm H 16 4...

Страница 15: ...s 11 00 P Q M N C N A N A Top Exit No Chimney Connector Shields Rear Exit Top Exit with Chimney Connector Shields or Double wall Chimney Connector Stove Installed Par allel to Wall Stove in Corner Unp...

Страница 16: ...Have an assistant tilt the stove while you install rst the back and then the front legs using the four 3 8 16 x 1 hex head bolts with 3 8 washers from the parts bag The shoulder of the legs should se...

Страница 17: ...s provided in the kit to attach the adaptor to the center mounting ange at the bottom of the Rear Shroud Install Smokeshelf Firebricks Look inside the rebox and locate the position for the Smokeshelf...

Страница 18: ...insulated and weather tight poor draft may result from insuf cient air in the house In such cases a slightly opened window near the stove on the windward side of the house will pro vide the fresh air...

Страница 19: ...t can be broken with a sharp blow from a hammer or from the thermal shock of rapid and extreme temperature change The cast plates expand and contract with changes in tempera ture When you rst begin us...

Страница 20: ...and ULC S627 for Canada Your stove may be used as a replace with the front doors open or removed only when the spark screen is placed correctly in the opening to protect against the possibility of spa...

Страница 21: ...rd from the rebricks to the grate where it will fall into the ashpan for easy removal Remove ash before it reaches the top of the ash pan Check the level at least once a day and before each re fueling...

Страница 22: ...st clean the areas to be painted with a wire brush Then touch up the stove with Vermont Castings high tem perature stove paint Apply the paint sparingly and keep in mind that two light coats of paint...

Страница 23: ...f necessary Failure to keep the chimney and connector system clean can result in a serious chimney re When wood is burned slowly it produces tar organic vapors and moisture that combine to form creoso...

Страница 24: ...on this Close and lock the door or damper on a slip of paper and then try to pull the paper out If the paper pulls out with little or no resistance the gasket isn t snug enough at that spot If adjusti...

Страница 25: ...temperatures Because the insulation is less dense than masonry the inner steel liner warms up more quickly than a masonry chimney Although steel chimneys are not as attractive as their masonry counter...

Страница 26: ...wood is Purchase your fuel from a reputable dealer Creosote Creosote is a by product of low temperature stove operations weak draft or both It is a tar that results when unburned gases condense insid...

Страница 27: ...eed to be attentive in timing the use of the other appliances If you need to crack a nearby window or door to enable the chimney to pull well you should install an outside air intake to bring combusti...

Страница 28: ...de See Chart Pg 29 4 Secondary Air Manifold Right 30000819 5 Left Side See Chart Pg 29 6 Secondary Air Manifold Left 30000820 7 1 4 20 x 2 1 4 CS Hex Hd Screw 2 1201403 8 Secondary Air Tube A 30000825...

Страница 29: ...Flue Collar Heat Shield 30000863 69 Rear Convection Shroud 30000826 70 10 x 1 2 Blk Phillips Sheetmetal Screw 2 1202058 72 Faucet Stub Chrome w Shaft 5004245 73 Ashpan Front 1306493 74 Ashpan Handle...

Страница 30: ...30 Intrepid 1640 Woodburning Stove 30000830 fire parts com...

Страница 31: ...y relevant information or circumstances regarding determi nation of failure 5 In addition the owner must return the failed catalyst Exclusions Limitations 1 This warranty is transferable however proof...

Страница 32: ...CFM Specialty Home Products 410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 905 670 7777 www majesticproducts com www vermontcastings com CFM Specialty Home Products fire parts com...

Отзывы: