CDVSC7 & CDV7 Series Gas Fireplace
69D3011
17
3"
1"
1"
1"
FP2288
TV rear vent
VenTInG InSTallaTIon
Figure 14 -
Combustible Clearances for Vent Pipe
A Minimum of 3" Clearance
to the Top Is Required
Along Horizontal Length
until Flue Pipe Penetrates
Outside Wall.
A Minimum 1"
Clearance to
Combustibles
Permitted All
Around Flue at
Outside Wall
VenT pIpe CleaRanCeS
Rear Vent: horizontal sections of this vent
system require a minimum of 3" clearances
to combustibles at the top of the flue and 1"
clearance at the sides and bottom
until the
flue penetrates the outside wall.
a minimum
1" clearance all around the flue is acceptable
at this point of penetration.
Vertical sections of this vent system require
a minimum of 1" clearance to combustibles
on all sides of the pipe.
w
a
R
n
In
G
Top Vent: horizontal sections of this vent
system require a minimum of 3" clearances
to combustibles at the top of the flue and 1"
clearance at the sides and bottom
until the
flue penetrates the outside wall.
a minimum
1" clearance all around the flue is acceptable
at this point of penetration. If vertical rise
is 7
1
/
2
feet or higher when top venting, the
clearance to combustibles is 1" on all sides
of the horizontal run.
Vertical sections of this vent system require
a minimum of 1" clearance to combustibles
on all sides of the pipe.
w
a
R
n
In
G
1"
3"
1"1"
FP2289
RV rear vent
A Minimum of 3" Clearance
to the Top Is Required Along
Horizontal Length until Flue
Pipe Penetrates Outside
Wall.
A Minimum 1" Clearance
to Combustibles Permitted
All Around Flue at Outside
Wall
FP88
FP89
CDVR Series
CDVT Series