Installation Guide
Air Quality
Example: No Parity, 19200 Baud, Autobaud Off
1
2
3
4
5
off
off
on
off
off
None
19200 Baud
Autobaud Off
Function Codes
Function Code
Function
03
Read holding registers
06
Write single register
08
Diagnostics (Sub-function 00 – Return query data)
16
Write multiple registers
17
Report slave ID – Returns manufacturer, model name, and serial number (standard Veris format)
All of these values correspond to BACnet objects with the same name. See the BACnet Conformance Statement for
their definitions.
Note that an attempt to write to “read only” holding registers will give an error and the entire write command will
not be executed even if writing to read/write locations were also requested. Exception code 2 is given in this case.
“Preserved” means the values is maintained through power outages.
Holding Registers
Register
Description
1
Sensor measurement (read only)
2
Sensor scale factor (n in 10
n
, value would be -2 for percent, -6 for ppm) (read only)
3,4
Sensor measurement in IEEE 32-bit floating point. Most significant word first. (read only)
5
Alarm bit map (read only)
Bit 0 (lsb) – High set-point exceeded
Bit 1 – Low set-point exceeded
Bits 2-15 – Zero
6
Alarm bit map override
Bit 0 – High set-point override
Bit 1 – Low set-point override
Bit 2 – High set-point level (1 – Above, 0 – Below)
Bit 3 – Low set-point level
Bits 4-15 – Zero
7
Time to sensor replacement (days remaining) (read only)
8
Run time (days) (read only)
9
Status (read only)
Bit 0 – Over range
Bit 1 – Warmup
Bit 2 – Damage detected
Bits 3-15 – Zero
10-17
Sensor gas type (read only). For example, CO.
All strings packed two characters, big endian, per word. Short strings null terminated.
18-25
Sensor serial number (read only) (always eight hexadecimal digits)
26-41
Manufacturer (read only) “Veris Industries”
42-57
Model (read only) “GWNPxx”