Installation Guide

Air Quality

The GWNP includes two sets of DIP switches, as shown in the Product Diagram section. The DIP switch labeled 
“ADDRESS” is for addressing. The DIP switch labeled “CONFIG” is for communications configuration.

Address Configuration

Each device on a single network must have a unique address. Set the DIP switch labeled “ADDRESS” to assign a 
unique address before the device is connected to the network. If an address is selected that conflicts with another 
device, neither device will be able to communicate.

Address the GWNP as any whole number between and including 1 to 127. Note that zero is not a valid address 
for Modbus; zero is a valid address for BACnet. Positions 1 through 7 of the “ADDRESS” DIP switch designate the 
address. Position 8 toggles between the Modbus and BACnet communication protocols, as shown in the diagram 
below. 

LSB

MSB

1

2

4

8

16

32

64

Decimal Values

Binary Address

Modbus/BACnet

Toggle

On = Modbus

Off = BACnet

To set an address using the DIP switch, simply add the values of any switches that are in the ON position.

For example, an address of 73 is set as shown in the diagram below.

73

=

LSB

MSB

1

2

4

8

16

32

64

Position number 1 has an ON value of 1, position number 4 has an ON value of 8 and position number 7 has an ON 
value of 64 (1 + 8 + 64 = 73).

Communications Configuration

See the Product Diagram section for the location of the DIP switch labeled “CONFIG”. The following parameters are 
configurable:

•  Parity (Modbus only): None, Odd, None1 (one stop bit), Even

•  Baud rate: 8600, 19200, 38400, 57600 (Modbus),  76800 (BACnet)

•  Autobaud: On, Off

Note: Autobaud may not be able to automatically determine the baud rate in some situations.  In this case, set 
Autobaud to OFF and use the manual baud setting.

off

off

on

off

off

on

on

on

None
Odd
None1
Even

9600
19200
38400
57600 (Modbus)
76800 (BACnet)

off

off

on

off

off

on

on

on

Parity

(Modbus Only)

Baud

Autobaud

Yes
No

On
Off

Configuration

Содержание GWNP Series

Страница 1: ...s free of dust and debris The GWNP is warranted for a period of five years GWNP Series BACnet and Modbus Protocol Communication Wall Mounted Platform for Gas Sensors Specifications Input Power 15 to 3...

Страница 2: ...of this material LOSS OF CONTROL Assure that the system will reach a safe state during and after a control path failure Separate or redundant control paths must be provided for critical control funct...

Страница 3: ...ED Blink Codes Relay Contacts LED Description Red OFF during normal conditions ON solid when the high setpoint is reached Flashes once when the device is initially powered Flashes while the platform i...

Страница 4: ...these terminals fit into the electrical box chosen for the installation In the case of some electrical boxes such as weatherproof style boxes the GWNP may not make a snug fit against the box If this h...

Страница 5: ...BACnet Positions 1 through 7 of the ADDRESS DIP switch designate the address Position 8 toggles between the Modbus and BACnet communication protocols as shown in the diagram below LSB MSB 1 2 4 8 16...

Страница 6: ...will not be executed even if writing to read write locations were also requested Exception code 2 is given in this case Preserved means the values is maintained through power outages HoldingRegisters...

Страница 7: ...egister 2 Valid values to set are 1 to low set point 1 A value of zero resets to sensor default 78 DIP switch values Changing to a non zero value will cause the current DIP switch settings to be locke...

Страница 8: ...igh_Set_point_Exceeded BI 1 Becomes ACTIVE when AI 1 AV 3 becomes INACTIVE when AI 1 AV 3 AV 4 Low_Set_point_Exceeded BI 2 Becomes ACTIVE when AI 1 AV 5 becomes INACTIVE when AI 1 AV 5 AV 6 Device_Obj...

Страница 9: ...rmware Revision 0 8 2 BACnet Protocol Version 1 BACnet Protocol Revision 12 Product Description Environmental Sensor BACnet Standardized Device Profile Annex L BACnet Application Specific Controller B...

Страница 10: ......

Отзывы: