Installation Guide
Air Quality
Objects Table
Object Name
Type and
Instance
Description of
Present_Value Property
SENSOR
AI 1
Gas concentration of sensor.
LIFETIME
AI 2
Remaining hours until sensor replacement.
RUNTIME
AI 3
Hours of runtime for sensor.
Device_Instance
AV 1
Alternative way to change object_identifier property of device. Fractional
values are truncated.
Identifier_Value_Prefix
AV 2
Initially 133, this is the value is prepended to the MAC address in the device
object identifier value.
High_Set-point
AV 3
High set-point value. Originally sensor high set-point.
High_Hysteresis
AV 4
High hysteresis value. Originally sensor high set-point hysteresis.
Low_Set-point
AV 5
Low set-point value. Originally sensor low set-point.
Low_Hysteresis
AV 6
Low hysteresis value. Originally sensor low set-point hysteresis.
High_Set_point_Exceeded
BI 1
Becomes ACTIVE when AI 1 ≥ AV 3; becomes INACTIVE when
AI 1 ≤ (AV 3 - AV 4).
Low_Set_point_Exceeded
BI 2
Becomes ACTIVE when AI 1 ≥ AV 5; becomes INACTIVE when
AI 1 ≤ (AV 5 - AV 6).
Device_Object_Reset
BV 1
Always reads INACTIVE. Write ACTIVE to reset the Device Objects Object_
Name and Object_Identifier to their defaults.
High_Relay_Override
BV 2
ACTIVE means BV 3 controls relay, otherwise BI 1 controls the relay.
High_Relay_Level
BV 3
When BV 2 is ACTIVE, an ACTIVE BV 3 behaves like the set-point has been
exceeded.
Low_Relay_Override
BV 4
ACTIVE means BV 5 controls relay, otherwise BI 2 controls the relay.
Low_Relay_Level
BV 5
When BV 4 is ACTIVE, an ACTIVE BV 5 behaves like the set-point has been
exceeded.
Lock_Settings
BV 6
When BV 6 is ACTIVE, DIP switches are disabled, and register values control
the settings. When BV 6 is INACTIVE, the DIP switches control.
Device Objects Table
Object Name
Object Identifier
Object Property
Description
GWNxxxx
Device 133nnn
Object_Identifier (R/W)
Unique value where nnn initially is MS/TP
address. GWN is the product name.
Object_Name (R/W)
Unique name, initially a combination of model
and serial number. Maximum length is 64
characters.
APDU_Timeout
Default is 3000, maximum value is 60000.
Max_Master
Default is 127
Description
Maximum length is 64 characters
Location
Maximum length is 31 characters
BACnet Descriptions (cont.)