Installation Guide

Air Quality

Objects Table

Object Name

Type and  

Instance

Description of  

Present_Value Property

SENSOR

AI 1

Gas concentration of sensor.

LIFETIME

AI 2

Remaining hours until sensor replacement.

RUNTIME

AI 3

Hours of runtime for sensor.

Device_Instance

AV 1

Alternative way to change object_identifier property of device. Fractional 

values are truncated.

Identifier_Value_Prefix

AV 2

Initially 133, this is the value is prepended to the MAC address in the device 

object identifier value.

High_Set-point

AV 3

High set-point value. Originally sensor high set-point.

High_Hysteresis

AV 4

High hysteresis value. Originally sensor high set-point hysteresis.

Low_Set-point

AV 5

Low set-point value. Originally sensor low set-point.

Low_Hysteresis

AV 6

Low hysteresis value. Originally sensor low set-point hysteresis.

High_Set_point_Exceeded

BI 1

Becomes ACTIVE when AI 1 ≥ AV 3; becomes INACTIVE when  

AI 1 ≤  (AV 3 - AV 4).

Low_Set_point_Exceeded

BI 2

Becomes ACTIVE when AI 1 ≥ AV 5; becomes INACTIVE when  

AI 1 ≤  (AV 5 - AV 6).

Device_Object_Reset

BV 1

Always reads INACTIVE. Write ACTIVE to reset the Device Objects Object_

Name and Object_Identifier to their defaults.

High_Relay_Override

BV 2

ACTIVE means BV 3 controls relay, otherwise BI 1 controls the relay.

High_Relay_Level

BV 3

When BV 2 is ACTIVE, an ACTIVE BV 3 behaves like the set-point has been 

exceeded.

Low_Relay_Override

BV 4

ACTIVE means BV 5 controls relay, otherwise BI 2 controls the relay.

Low_Relay_Level

BV 5

When BV 4 is ACTIVE, an ACTIVE BV 5 behaves like the set-point has been 

exceeded.

Lock_Settings

BV 6

When BV 6 is ACTIVE, DIP switches are disabled, and register values control 

the settings.  When BV 6 is INACTIVE, the DIP switches control.

Device Objects Table

Object Name

Object Identifier

Object Property

Description

GWNxxxx

Device 133nnn

Object_Identifier (R/W)

Unique value where nnn initially is MS/TP 

address. GWN is the product name.

Object_Name (R/W)

Unique name, initially a combination of model 

and serial number. Maximum length is 64 

characters.

APDU_Timeout

Default is 3000, maximum value is 60000.

Max_Master

Default is 127

Description

Maximum length is 64 characters

Location

Maximum length is 31 characters

BACnet Descriptions (cont.)

Содержание GWNP Series

Страница 1: ...s free of dust and debris The GWNP is warranted for a period of five years GWNP Series BACnet and Modbus Protocol Communication Wall Mounted Platform for Gas Sensors Specifications Input Power 15 to 3...

Страница 2: ...of this material LOSS OF CONTROL Assure that the system will reach a safe state during and after a control path failure Separate or redundant control paths must be provided for critical control funct...

Страница 3: ...ED Blink Codes Relay Contacts LED Description Red OFF during normal conditions ON solid when the high setpoint is reached Flashes once when the device is initially powered Flashes while the platform i...

Страница 4: ...these terminals fit into the electrical box chosen for the installation In the case of some electrical boxes such as weatherproof style boxes the GWNP may not make a snug fit against the box If this h...

Страница 5: ...BACnet Positions 1 through 7 of the ADDRESS DIP switch designate the address Position 8 toggles between the Modbus and BACnet communication protocols as shown in the diagram below LSB MSB 1 2 4 8 16...

Страница 6: ...will not be executed even if writing to read write locations were also requested Exception code 2 is given in this case Preserved means the values is maintained through power outages HoldingRegisters...

Страница 7: ...egister 2 Valid values to set are 1 to low set point 1 A value of zero resets to sensor default 78 DIP switch values Changing to a non zero value will cause the current DIP switch settings to be locke...

Страница 8: ...igh_Set_point_Exceeded BI 1 Becomes ACTIVE when AI 1 AV 3 becomes INACTIVE when AI 1 AV 3 AV 4 Low_Set_point_Exceeded BI 2 Becomes ACTIVE when AI 1 AV 5 becomes INACTIVE when AI 1 AV 5 AV 6 Device_Obj...

Страница 9: ...rmware Revision 0 8 2 BACnet Protocol Version 1 BACnet Protocol Revision 12 Product Description Environmental Sensor BACnet Standardized Device Profile Annex L BACnet Application Specific Controller B...

Страница 10: ......

Отзывы: