GWNP Series Installation Guide

Installation

Observe precautions for handling static sensitive

devices to avoid damage to the circuitry that

is not covered under the factory warranty.

1.  Disconnect and lock out all power supplies before beginning the installation.

2.  Choose a location on a wall in the area to be monitored. Install the unit on a standard electrical box centrally, near main traffic 

paths but away from outside air vents and excessive drafts.

3.  Remove the front cover of the GWNP unit, and set it aside.

4.  Wiring terminals are located on the back of the unit. Determine whether these terminals fit into the electrical box chosen for 

the installation. In the case of some electrical boxes, such as weatherproof style boxes, the GWNP may not make a snug fit 
against the box. If this happens, use the Veris AA66 Foam Gasket Kit accessory to improve the fit (sold separately).

5.  Run wires through the back of the electrical box and wire the GWNP as shown. Properly shielded wire must be used for all 

connections. For the RS-485, use shielded, twisted-pair wire. Connect the shield at one end only. The GND terminal can be 

used.

Relay

Power Supply

+

Common

High Threshold (HT)

Low Threshold (LT)

RS485(-)

RS485(+)

GND 

Power

Modbus

BACnet

6.  Mount the GWNP on the box. Use the two mounting holes on the unit and the included #6 screws. The wiring terminals must 

face into the electrical box, with the board facing outward.

7.  Install the AGxx Series gas sensor according to the directions included with the sensor. 

8.  Adjust the DIP switches as needed.

9.  If desired, replace the LED light pipes with the black plastic light blocking insert (included with the GWNP). The light pipes are 

located inside of the front cover.

10.  Replace the front cover. Reconnect power.

Содержание GWNP Series

Страница 1: ...s free of dust and debris The GWNP is warranted for a period of five years GWNP Series BACnet and Modbus Protocol Communication Wall Mounted Platform for Gas Sensors Specifications Input Power 15 to 3...

Страница 2: ...of this material LOSS OF CONTROL Assure that the system will reach a safe state during and after a control path failure Separate or redundant control paths must be provided for critical control funct...

Страница 3: ...ED Blink Codes Relay Contacts LED Description Red OFF during normal conditions ON solid when the high setpoint is reached Flashes once when the device is initially powered Flashes while the platform i...

Страница 4: ...these terminals fit into the electrical box chosen for the installation In the case of some electrical boxes such as weatherproof style boxes the GWNP may not make a snug fit against the box If this h...

Страница 5: ...BACnet Positions 1 through 7 of the ADDRESS DIP switch designate the address Position 8 toggles between the Modbus and BACnet communication protocols as shown in the diagram below LSB MSB 1 2 4 8 16...

Страница 6: ...will not be executed even if writing to read write locations were also requested Exception code 2 is given in this case Preserved means the values is maintained through power outages HoldingRegisters...

Страница 7: ...egister 2 Valid values to set are 1 to low set point 1 A value of zero resets to sensor default 78 DIP switch values Changing to a non zero value will cause the current DIP switch settings to be locke...

Страница 8: ...igh_Set_point_Exceeded BI 1 Becomes ACTIVE when AI 1 AV 3 becomes INACTIVE when AI 1 AV 3 AV 4 Low_Set_point_Exceeded BI 2 Becomes ACTIVE when AI 1 AV 5 becomes INACTIVE when AI 1 AV 5 AV 6 Device_Obj...

Страница 9: ...rmware Revision 0 8 2 BACnet Protocol Version 1 BACnet Protocol Revision 12 Product Description Environmental Sensor BACnet Standardized Device Profile Annex L BACnet Application Specific Controller B...

Страница 10: ......

Отзывы: