Installation Guide

Air Quality

Modbus Point Map (cont.)

Register

Description

58-73   

Location (read/write) preserved. Must be null terminated, 31 characters max.

74

High set-point (read/write preserved). Scaled by value in register 2. Valid values to set are 2 to top of 

range. A value of zero resets to sensor default.

75

High hysteresis (read/write preserved). Scaled by value in register 2. Valid values to set are 1 to high set-

point - 1. A value of zero resets to sensor default.

76

Low set-point (read/write preserved). Scaled by value in register 2. Valid values set are 2 to top of range. A 

value of zero resets to sensor default.

77

Low hysteresis (read/write preserved). Scaled by value in register 2. Valid values to set are 1 to low set-

point - 1. A value of zero resets to sensor default.

78 

DIP switch values. Changing to a non-zero value will cause the current DIP switch settings to be locked in 

place. Changing to zero restores dip switch functionality.

79-125

Reserved (read only) returns 0x8000

Note: In the tables below, all properties are read-only unless otherwise noted. “Preserved” means the value is 
maintained through power outages.

Present_Value Range Restrictions

Object Name

Minimum Value

Maximum Value

Device_Instance

4,194,302

Identifier_Value_Prefix

0

4194

High_Set-point  

Low_Set-point

2

Maximum range of installed sensor.

High_Hysteresis  

Low_Hysteresis

1

High_Set-point-1 

Low_Set-point-1

Standard Object Types Supported 

Object Type

Supported Optional Properties

Writable Properties

Analog Input – AI

Description 
Reliability

None

Analog Value – AV

Description

Present_Value

Binary Input (supports change of value) Description 

Reliability

None

Binary Value – BV

Description

Present_Value

Device – DEV

Description
Location
Max_Master
Max_Info_Frames
Active_COV_Subscriptions

APDU_Timeout
Description
Location,
Max_Master
Object_Identifier
Object_Name

Note: Reliability is “No Sensor” if no sensor is installed.

BACnet Descriptions

Содержание GWNP Series

Страница 1: ...s free of dust and debris The GWNP is warranted for a period of five years GWNP Series BACnet and Modbus Protocol Communication Wall Mounted Platform for Gas Sensors Specifications Input Power 15 to 3...

Страница 2: ...of this material LOSS OF CONTROL Assure that the system will reach a safe state during and after a control path failure Separate or redundant control paths must be provided for critical control funct...

Страница 3: ...ED Blink Codes Relay Contacts LED Description Red OFF during normal conditions ON solid when the high setpoint is reached Flashes once when the device is initially powered Flashes while the platform i...

Страница 4: ...these terminals fit into the electrical box chosen for the installation In the case of some electrical boxes such as weatherproof style boxes the GWNP may not make a snug fit against the box If this h...

Страница 5: ...BACnet Positions 1 through 7 of the ADDRESS DIP switch designate the address Position 8 toggles between the Modbus and BACnet communication protocols as shown in the diagram below LSB MSB 1 2 4 8 16...

Страница 6: ...will not be executed even if writing to read write locations were also requested Exception code 2 is given in this case Preserved means the values is maintained through power outages HoldingRegisters...

Страница 7: ...egister 2 Valid values to set are 1 to low set point 1 A value of zero resets to sensor default 78 DIP switch values Changing to a non zero value will cause the current DIP switch settings to be locke...

Страница 8: ...igh_Set_point_Exceeded BI 1 Becomes ACTIVE when AI 1 AV 3 becomes INACTIVE when AI 1 AV 3 AV 4 Low_Set_point_Exceeded BI 2 Becomes ACTIVE when AI 1 AV 5 becomes INACTIVE when AI 1 AV 5 AV 6 Device_Obj...

Страница 9: ...rmware Revision 0 8 2 BACnet Protocol Version 1 BACnet Protocol Revision 12 Product Description Environmental Sensor BACnet Standardized Device Profile Annex L BACnet Application Specific Controller B...

Страница 10: ......

Отзывы: