GWNP Series Installation Guide

Product Diagram

Pin Connector for AGxx Gas Sensor

An AGxx sensor is required for GWNP 

operation. Sensors are sold separately.

Status LED Indicators

Left - red
Center - yellow
Right - green

RX and TX LED Indicators

RX - receiving data
TX - sending data

Settings LED Indicator

OFF during normal conditions

ON when settings have been overridden 

by communications

COMM

OVRD

Address

DIP Switch

Configuration

DIP Switch

The LED indicators allow determination of device status at a glance. The GWNP includes a light blocking insert that can be set in 
place of the light pipes if this visibility is not desired.

Status LED Blink Codes

Relay Contacts

LED

Description

Red

•  OFF during normal conditions.
•  ON solid when the high setpoint is reached.
•  Flashes once when the device is initially powered.
•  Flashes while the platform is auto-resetting, such as when a sensor is installed.
•  Flashes continuously when the sensor reading is over range.

Yellow •  OFF during normal conditions.

•  ON solid when the low setpoint is reached.
•  Flashes once when the device is initially powered.
•  Flashes while the platform is auto-resetting, such as when a sensor is installed.
•  1 flash every 10 seconds if possible sensor damage is detected.
•  2 flashes every 10 seconds if the sensor requires replacement.
•  4 or more flashes every 10 seconds if internal problems are detected, such as if the unit needs servicing or if the operating 

temperature is out of range.

Green

•  ON solid during normal operation.
•  Flashes once when the device is initially powered.
•  Flashes while the platform is auto-resetting, such as when a sensor is installed.

Unit Condition

Low Setpoint Relay

High Setpoint Relay

OFF

Closed

Open

ON (everything OK)

Open

Open

ON (inoperative)

Closed

Closed

ON (low setpoint reached)

Closed

Open

ON (high setpoint reached)

Closed

Closed

Содержание GWNP Series

Страница 1: ...s free of dust and debris The GWNP is warranted for a period of five years GWNP Series BACnet and Modbus Protocol Communication Wall Mounted Platform for Gas Sensors Specifications Input Power 15 to 3...

Страница 2: ...of this material LOSS OF CONTROL Assure that the system will reach a safe state during and after a control path failure Separate or redundant control paths must be provided for critical control funct...

Страница 3: ...ED Blink Codes Relay Contacts LED Description Red OFF during normal conditions ON solid when the high setpoint is reached Flashes once when the device is initially powered Flashes while the platform i...

Страница 4: ...these terminals fit into the electrical box chosen for the installation In the case of some electrical boxes such as weatherproof style boxes the GWNP may not make a snug fit against the box If this h...

Страница 5: ...BACnet Positions 1 through 7 of the ADDRESS DIP switch designate the address Position 8 toggles between the Modbus and BACnet communication protocols as shown in the diagram below LSB MSB 1 2 4 8 16...

Страница 6: ...will not be executed even if writing to read write locations were also requested Exception code 2 is given in this case Preserved means the values is maintained through power outages HoldingRegisters...

Страница 7: ...egister 2 Valid values to set are 1 to low set point 1 A value of zero resets to sensor default 78 DIP switch values Changing to a non zero value will cause the current DIP switch settings to be locke...

Страница 8: ...igh_Set_point_Exceeded BI 1 Becomes ACTIVE when AI 1 AV 3 becomes INACTIVE when AI 1 AV 3 AV 4 Low_Set_point_Exceeded BI 2 Becomes ACTIVE when AI 1 AV 5 becomes INACTIVE when AI 1 AV 5 AV 6 Device_Obj...

Страница 9: ...rmware Revision 0 8 2 BACnet Protocol Version 1 BACnet Protocol Revision 12 Product Description Environmental Sensor BACnet Standardized Device Profile Annex L BACnet Application Specific Controller B...

Страница 10: ......

Отзывы: