VUTR 200 V(E) EC
Page 2/6. Setting up temperature setpoints.
Press
to select a temperature setpoint. Then use
and
to
defi ne the temperature setpoint value.
After that press the
button to save the settings.
T1
is the setpoint for the supply air temperature at which the unit will
switch to a lower speed in case of failure to attain the set temperature
conditions.
T4
is the temperature increase relative to
T1
for switching to the pre-
programmed speed.
The «Sensing» parameter allows changing the temperature measuring
location for determining the value and for further processing in the
program.
If the unit serves a number of spaces the parameter value should be set
to «Exhaust air».
When selecting the parameter: «in the th-Tune» the control panel must
be installed in spaces where the air is supplied by the unit.
Page 3/6. Temperature regulator operation setup.
For «Winter» and «Summer» modes it is possible to choose the type of
the temperature regulator.
If the temperature regulator type value is «1» temperature is controlled
by room temperature.
If the temperature regulator type value is «1» the temperature is
controlled by room temperature
Page 4/6. Sensor operation setup.
You may enable/disable the humidity sensor in the exhaust air duct via
software in the CF7 parameter.
CF8 - enable/disable outdoor sensor 0-10 V:
CF9 - change the input type of the outdoor relay humidity sensor.
(WARNING! When an exhaust kitchen hood is connected you must select
the «DIRECT» sensor type).
Page 5/6. Sensor operation setup.
F7 - setpoint for controlling humidity based on the exhaust duct sensor
readings.
F8 - setpoint for controlling fan operation based on the outdoor sensor
readings (0-10 V).
Page 6/6. Hour meter operation.
To switch the reminder about fi lter replacement off select one of the
menu items:
To reset the fi lter replacement alerts once the fi lter has been replaced
press the following buttons to make the following menu selection:
•
To reset the timer select «YES» in the «Reset of operating hours
counter:» parameter.
•
To change the fi lter replacement interval select the desired time and