Vents VUTR 200 V2 EC A17 Скачать руководство пользователя страница 12

www.ventilation-system.com

12

VUTR 200 V(E) EC

DISCONNECT THE UNIT FROM POWER MAINS PRIOR TO ANY OPERATIONS. THE UNIT MUST 

BE CONNECTED TO POWER SUPPLY BY A QUALIFIED ELECTRICIAN. THE RATED ELECTRICAL 

PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTURER’S LABEL.

 

ANY INTERNAL CONNECTION MODIFICATIONS ARE NOT ALLOWED AND RESULT IN 

WARRANTY LOSS.

CONNECTION TO POWER MAINS

The air-handling unit is rated for connection to single-phase AC mains 230 V / 50(60) Hz. The EC unit has a power cord with a plug to connect to a 

standard grounded outlet. The power cord is pre-wired to the terminal block.

The external power input must be equipped with an automatic circuit breaker built into the stationary wiring to open the circuit in the event of 

overload or short-circuit.

The external switch location must ensure free access for quick shutdown of the unit.
The trip current of the automatic circuit breaker must correspond to the current consumption (see the table on page 5).
Supply and exhaust air damper actuators, a kitchen hood, external sensors with 0-10 V analogue output and relay sensors can be connected to the 

unit. Connection to a fi re alarm panel and an enable signal of compressor-condenser unit (CCU) operation are foreseen.

For accessing the terminal block and the controller undo the screws securing the control unit and remove it. Then undo 2 screws of the control unit 

cover and remove it.

ACCESS TO THE CONTROL UNIT

2

1

L

SM1*

N

Connection of sensors 

with 0-10 V 

analogue output

Normally opened contact 

from relay sensor or switch

Cooler deactivation signal 

(no-contact, 16 A)

Power input

230 VAC

2

1

PK1*

1

X1

Control unit

X4

gnd

2

R+

3

R-

4

GND~

5

~24V

6

0-10V

7

GND

8

~24V

9

NO

10

NO

11

NO

12

NO

13

2

14

1

15

2

16

1

17

PE

18

N

19

L1

GND

Green

Yellow

Brown

Grey

White

P1**    th-Tune

Rx+/Tx+

Rx-/Tx-

GND~

~24V

1

TS1

2

TS1

3

PE

4

N

5

L

Grey

Black

Yellow/green

Blue

Brown

P2*

    Kitchen hood

TS1

1

2

1

2

L1

PE

Design. Name

Model

Wire**

SM1*

Exhaust or supply air damper electric actuator

LF230

2x0.75 mm

2

PK1*

Contact from fi re alarm panel

NC

2x0.75 mm

2

P1*

Control panel

th-Tune

P2

Kitchen hood

* - the appliances are not supplied with the unit, are available on separate order.
** - wire cross-section at a cable length of maximum 100 m.

Maximum cable length from controller to control panel

Cable type

Distance to power source

Phone cable 

up to 50 m

AWG24 shielded cable

up to 200 m

EXTERNAL CONNECTIONS DIAGRAM

 —

 Electric shock hazard!

Содержание VUTR 200 V2 EC A17

Страница 1: ...USER S MANUAL Heat recovery air handling unit VUTR 200 V2 EC A17 VUTR 200 V2 EC A18 VUTR 200 V2 E EC A17 VUTR 200 V2 E EC A18...

Страница 2: ...ion electrical and technical norms and standards The warnings contained in the user s manual must be considered most seriously since they contain vital personal safety information Failure to follow th...

Страница 3: ...t Disconnect the unit from power mains prior to any technical maintenance Do not store any explosive or highly ammable substances in close proximity to the unit When the unit generates unusual sounds...

Страница 4: ...MUST PREVENT UNAUTHORIZED ACCESS BY UNATTENDED CHILDREN The unit is designed for wall and oor mounting The unit is rated for continuous operation Transported air must not contain any ammable or explos...

Страница 5: ...Top view 135 347 510 600 598 125 95 139 113 95 144 124 141 TECHNICAL DATA Parameters VUTR 200 V2 A17 VUTR 200 V2 A18 VUTR 200 V2E EC A17 VUTR 200 V2E EC A18 Unit voltage V 50 60 Hz 1 230 Maximal unit...

Страница 6: ...hood The kitchen hood must be equipped with an air damper to shut o the exhaust duct when the kitchen hood is not in use UNIT DESIGN AND OPERATION PRINCIPLE SERVICE SIDE VIEW Intake filter Extract air...

Страница 7: ...short or not connected protect the unit parts from ingress of foreign objects To prevent uncontrollable access to the fans the spigots may be covered with a protecting grille or other protecting devi...

Страница 8: ...and install a humidity sensor into the mount on the extract air duct panel and then connect the humidity sensor contact socket to the respective contact socket on the control unit 1 2 3 Contact socke...

Страница 9: ...undo the four self tapping screws and remove the plug in the bottom panel Lead the kitchen hood cable into the unit and connect it according to the external connections wiring diagram page 12 Fix the...

Страница 10: ...ntrol panel 3 Complete the electrical connections according to the external wiring diagram Page 12 4 Secure the rear part of the control panel in the mounting box using the screws supplied 5 Connect t...

Страница 11: ...a wall route the phone cable to the selected location 1 Secure the rear part of the casing in the standard box by means of the round head screws supplied 2 Connect the phone cable to the front part of...

Страница 12: ...to the unit Connection to a re alarm panel and an enable signal of compressor condenser unit CCU operation are foreseen For accessing the terminal block and the controller undo the screws securing th...

Страница 13: ...t an outdoor air temperature sensor a supply air temperature sensor a temperature sensor of an exhaust duct a room temperature sensor when using the th Tune with the temperature sensor A17 a humidity...

Страница 14: ...s the knob to set the start time and the corresponding temperature setpoint for each time range individually you may create up to six time ranges The pictogram shows the current time of a day status i...

Страница 15: ...the display screen Simultaneously press the Up Down and Enter buttons and hold them for 3 5 seconds After this time the message Display address setting 32 appears on the display screen 3 Move the cur...

Страница 16: ...on for cancelling the parameter edits and exiting the submenu Parameters Prg Access to the additional options menu Alarms Access to the alarm view and reset menu THE SERVICE SETTINGS ARE PROGRAMMED AT...

Страница 17: ...t exchanger and the electric heater 3 Outside air temperature Readings are taken from the temperature sensor built into the supply duct upstream of the heat exchanger UNIT OPERATION MODE SELECTION The...

Страница 18: ...ty of each fan via the unit parameter setup menu UNIT PARAMETERS To enter the user parameter menu press the button Use and to select the desired menu item and press to enter 1 System information To vi...

Страница 19: ...t time scheduler The Set time scheduler menu consists of four pages To navigate between the pages use the and buttons Attention With the th Tune control panel connected the scheduled operation is set...

Страница 20: ...the week as follows 1 Use the button to set the cursor at Copy to 2 Use and to select a day of the week or all days 3 Press and select Yes using and 4 To con rm the copying operation press the button...

Страница 21: ...setting the next special day 5 Setting up other special days Other special days are set up similarly Setting up setpoints Page 4 4 The setpoints for schedule entries are programmed on page 4 4 Setting...

Страница 22: ...of the temperature regulator If the temperature regulator type value is 1 temperature is controlled by room temperature If the temperature regulator type value is 1 the temperature is controlled by r...

Страница 23: ...active alarms can be reset manually To reset an alarm manually press in the active alarms menu and enter the alarm control menu The alarm management menu enables the following actions viewing the curr...

Страница 24: ...aning is required To clean the heat exchanger remove it from the unit and clean the heat exchanger by using compressed air or a vacuum cleaner After cleaning re install the heat exchanger into the uni...

Страница 25: ...duct pipe anges Install anti vibration connectors SYSTEM ALARMS Fire alarm Emergency system shutdown on command from the re alarm board This alarm interrupts the fan operation In case of such alarm f...

Страница 26: ...he user Mismatch of the unit model and the brand name with the information stated on the unit packing and in the user s manual User s failure to ensure timely technical maintenance of the unit Externa...

Страница 27: ...umber E mail Purchase Date Seller s Stamp Seller s Stamp Installation Company Stamp This is to certify acceptance of the complete unit delivery with the user s manual The warranty terms are acknowledg...

Страница 28: ...V140 1EN 01...

Отзывы: