VUTR 200 V(E) EC
DISCONNECT THE UNIT FROM POWER MAINS PRIOR TO ANY OPERATIONS. THE UNIT MUST
BE CONNECTED TO POWER SUPPLY BY A QUALIFIED ELECTRICIAN. THE RATED ELECTRICAL
PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTURER’S LABEL.
ANY INTERNAL CONNECTION MODIFICATIONS ARE NOT ALLOWED AND RESULT IN
WARRANTY LOSS.
CONNECTION TO POWER MAINS
The air-handling unit is rated for connection to single-phase AC mains 230 V / 50(60) Hz. The EC unit has a power cord with a plug to connect to a
standard grounded outlet. The power cord is pre-wired to the terminal block.
The external power input must be equipped with an automatic circuit breaker built into the stationary wiring to open the circuit in the event of
overload or short-circuit.
The external switch location must ensure free access for quick shutdown of the unit.
The trip current of the automatic circuit breaker must correspond to the current consumption (see the table on page 5).
Supply and exhaust air damper actuators, a kitchen hood, external sensors with 0-10 V analogue output and relay sensors can be connected to the
unit. Connection to a fi re alarm panel and an enable signal of compressor-condenser unit (CCU) operation are foreseen.
For accessing the terminal block and the controller undo the screws securing the control unit and remove it. Then undo 2 screws of the control unit
cover and remove it.
ACCESS TO THE CONTROL UNIT
2
1
L
SM1*
N
Connection of sensors
with 0-10 V
analogue output
Normally opened contact
from relay sensor or switch
Cooler deactivation signal
(no-contact, 16 A)
Power input
230 VAC
2
1
PK1*
1
X1
Control unit
X4
gnd
2
R+
3
R-
4
GND~
5
~24V
6
0-10V
7
GND
8
~24V
9
NO
10
NO
11
NO
12
NO
13
2
14
1
15
2
16
1
17
PE
18
N
19
L1
GND
Green
Yellow
Brown
Grey
White
P1** th-Tune
Rx+/Tx+
Rx-/Tx-
GND~
~24V
1
TS1
2
TS1
3
PE
4
N
5
L
Grey
Black
Yellow/green
Blue
Brown
P2*
Kitchen hood
TS1
1
2
1
2
L1
PE
Design. Name
Model
Wire**
SM1*
Exhaust or supply air damper electric actuator
LF230
2x0.75 mm
2
PK1*
Contact from fi re alarm panel
NC
2x0.75 mm
2
P1*
Control panel
th-Tune
P2
Kitchen hood
* - the appliances are not supplied with the unit, are available on separate order.
** - wire cross-section at a cable length of maximum 100 m.
Maximum cable length from controller to control panel
Cable type
Distance to power source
Phone cable
up to 50 m
AWG24 shielded cable
up to 200 m
EXTERNAL CONNECTIONS DIAGRAM
—