www.ventilation-system.com
15
Connect the pGD1 control panel to the controller connector
(see fi gure on page 16) using the 6P6C (PLUG-6P6C-P-C2) phone
plug.
The maximum length of the phone cable is 50 m.
The pGD1 off ers extended functionality and has identical
settings entered via the controller screen (see «Controller functions
and menu»).
• The main page of the control panel menu displays the following information:
• date and current time
• indoor temperature (use the «Up» button and the «Down» button to see readings of the following sensors: outdoor and supply air temperature,
temperature and humidity in an exhaust air duct)
• unit operation mode
• set-point
temperature
• selected
speed
• fan speed mode
• scheduled operation status (on/off )
The main page enables access to the user or engineering menu containing extended information specifi c to the unit operation and detailed
parameters for adjustment.
PLAN NETWORK CONFIGURATION WHILE USING AN EXTERNAL CONTROL PANEL (pGD1).
To enable interaction with the control panel boot up the controller in the pLan mode and assign the following pLan addresses to the controller and the
control panel:
Controller
– 1;
Control panel (pGD1)
– 30, 31 or 32 (factory default value).
SETTING PLAN ADDRESS FOR A CONTROL PANEL (pGD1).
11. Connect the control panel to the controller and power up the controller.
2. Ignore any information which might show on the display screen. Simultaneously press the «Up», «Down» and «Enter» buttons and hold them for
3-5 seconds. After this time the message
«Display address setting…..32»
appears on the display screen.
3. Move the cursor to the address setting fi eld using the «Enter» button. Use the «Up» and «Down» buttons to set the desired address value and press
«Enter».
SETTING CONTROLLER PLAN ADDRESS VIA THE BUILT-IN CONTROL PANEL.
1. Power off the controller.
2. Power up the controller and immediately press the «Up» and «Alarm» buttons simultaneously.
Hold the buttons pressed until the controller page appears on the screen (wait for about 15 seconds).
3. Use the «Up» and «Down» buttons to set the device address to 1.
4. Press the «Enter» button within 10 seconds to confi rm. Failure to press the button within 10 seconds will cause the controller to close the address
setting page automatically while keeping the original address value.
5. Upon confi rmation the controller will restart with a new pLan address automatically.
SETTING CONTROLLER PLAN ADDRESS VIA THE pGD1 CONTROL PANEL.
To set the controller address use the pGD1 panel to set the control panel (dGD1) address to 0. To do this follow the steps described in the
«SETTING
PLAN ADDRESS FOR A CONTROL PANEL (pGD1)»
paragraph above. Upon setting the control panel address to zero by using the respective buttons
on the external control panel follow the steps described in the
«SETTING CONTROLLER PLAN ADDRESS VIA THE BUILT-IN CONTROL PANEL»
paragraph.
After setting the controller address set the pLan address of the control panel (pGD1) to 30, 31 or 32.