background image

MA-SE-DCT3-01-02 Manual Doge CT3 eng rev2 

 

   Rev.4 Pagina 7 di 17 

 

PROGRAMMING OF DIP SWITCH 

(chart 6) Alarm timer  
DIP1 

Alarm Timer  

OFF (default) 

3 minutes 

ON 

8 minutes 

 
(chart 7) Setting of zone 1  
DIP2 

Behaviour of zone 1 

OFF (default) 

Zone 1 delayed for the time set by DIP3 

ON  

Zone 1 immediate 

 
(chart 8) Delay on zone 1 
DIP3 

Delay on input time and output Z1 

OFF (default) 

Input 30seconds, output 1 minute  

ON  

input 1minute,  output  2 minutes 

 

(chart 9) Setting of termination type zones 1, 2 and 3 
DIP4 

Behaviour of inputs Z1, Z2, Z3 

OFF (default) 

Lines of NC input  

ON  

Lines of single-balancing input with 5600 ohm resistance  

 

 (chart 10) Max number of alarms for any arming of the system  
DIP6 

Alarms which can be sent  

OFF

(default)

 

Infinitive alarms  

ON 

The control panel triggers off max 4 alarms for any zone and for any arming e.g. zone 1 can 
trigger off alarm 4 times, zone 2 can trigger off alarm 4 times and so can zone 3. 
The counting of the alarms resets at any arming or 24 hours after last alarm.  
24 hours zone has no limit for the number of alarms. 

 

(char t11) Alarm memory, cancellation  
DIP7 

Behaviour  

OFF 

(default)

 

Visualization of first zone in alarm resets when the system is disarmed 

ON 

Visualization of first zone in alarm remains active until next arming of the system. 

 

(chart12) Selection of the sounds  
DIP8 

Sound 

Frequency Limits (Hz) 

dB (A) MAX at 3meters 

OFF 

(default)

 

Sirena Standard 

1.250 - 2.645 

103 

ON 

NFC48265 

1430 - 1585 

107 

 

INSTALLATION, SERVICE AND TEST (WALK TEST) 

The  anti-tamper  circuit  is  blocked  right  after  supplying  of  the  board  and  for  about  60  seconds  after  any  system  disarming;  if  the 
housing is open during this period the block becomes permanent and both opening of 24 hours line and short-circuit on balanced 
lines do not trigger off any alarm. In order to restore the operating of the 24 hours line and the short-circuit control of the balanced 
lines, it is enough to close cover and arm the system.  
 

Walk test: Attenuation of the siren sound to check detectors and sirens  

The walk test allows to check the efficiency of the peripheral devices connected to the zones with an attenuation of the horn sound 
but keeping completely operative all inputs and outputs.  
During the anti-tamper block the sound is attenuate. In this way, it can occur that the connected detectors trigger off correctly the 
alarm and that the siren outputs command the telephone dialer and other indication devices if any.   
Doge CT3 will behave normally at both arming and disarming , but the alarm will be attenuated to about 60 dB, the 24 hours line will 
be deactivated and the short-circuit – in case of balanced termination of the zone (DIP 4 on)  – will not be detected.  
In order to restore the high-intensity sound, it is necessary to close the cover and arm and disarm the system, furthermore if the 
panel remains on continuously for 1 hour, the horn automatically restores to high-intensity sound.   
 

Содержание DOGE CT3

Страница 1: ...er charged against UV Protection against wall tampering and cover opening Protection against polarity inversion Discharged battery causes block of the horn and quick flashing further to block of the i...

Страница 2: ...e central Led with 1 pulse and then pause ON PARTIAL The central Led flash 3 times and then flash of the central Led with 2 pulses and then pause ON DISARMED All Led switch on for 5 seconds and then s...

Страница 3: ...ND ANOMALIES RED LED LD1 1 Speaker interruption 1 FLASH 2 Mains missing with immediate indication tension of the supply unit less than 11 9V 2 FLASHES 3 Battery not connected 3 FLASHES 4 Battery spoil...

Страница 4: ...of partially armed system 0V in case of disarmed system Can be connected to the Led of system status of Minidoge or Minimurano 12V Output with 13 V tension always available protected by auto restorabl...

Страница 5: ...line and FARO DT detector tamper STANDARD DETEC DOGE CT Pict 7 Connection balanced line and STANDARD AM detector tamper STANDARD DETECTOR DOGE CT Pict 5 Connection with NC line and tamper STANDARD de...

Страница 6: ...on the picture 10 Memorize the first pushbutton of the remote control on OUT3 and the second on OUT4 the open collector outputs of the Vela receiver Program the two outputs as mono stable Two pushbutt...

Страница 7: ...3meters OFF default Sirena Standard 1 250 2 645 103 ON NFC48265 1430 1585 107 INSTALLATION SERVICE AND TEST WALK TEST The anti tamper circuit is blocked right after supplying of the board and for abo...

Страница 8: ...time switches on The output STI system status activates fix at 0V in case of total arming or intermitting in case of partial arming INPUT OUTPUT TIME After arming the control panel the output time st...

Страница 9: ...e of anomaly during arming and disarming operations it will flash quickly As soon as the anomaly disappear flash returns to normal speed about 1 flash per second LED Anomalies on board it shows anomal...

Страница 10: ...minutes can be set to 8 minutes Frequency limits See chart 12 Sounds Acoustic power See chart 12 Sounds Duration of the Led flash 1 000 000 flash minimum Conditions of humidity from 20 to 100 of humi...

Страница 11: ...nt LEDs flash for 1 minute Does the tamper LED make 5 flashes Put zone 2 in alarm status Do the front LEDs make 2 flashes and then a pause AND does the loudspeaker sound at low volume Push A button of...

Страница 12: ...ck if the sounder is correctly powered through the power supply connector Open the sounder cover and count the number of flashes as indicated in chart 3 Solve the anomaly then turn the sounder off and...

Страница 13: ...ceiver to DOGE CT3 using the dedicated cable Picture 7 Give power supply to DOGE CT3 using a battery or a power supply unit Do the 2 LEDs of the receiver make a GREEN flash Push the button of the rece...

Страница 14: ...6 relay 1 contact common 7 relay 2 contact n o Led 1 red when activated 8 relay 2 contact common 9 output 3 Open Collector Led 2 green when activated 10 output 4 Open Collector Led 2 red when activate...

Страница 15: ...uency 433 92 MHz APPLICATION NOTES RELAY OUTPUT CHANGE To modify relay outputs from normally open N O to normally closed N C Cut the route relevant to desired output as in below figure N B After cutti...

Страница 16: ...rn to operating mode is signaled by LED switching off Exemple 3 removal of transmitter from memory Push the button 5 times at first pressure LED 1 switches on green at second pressure LED 1 switches o...

Страница 17: ...pressure push the button of transmitter that you want remove NOTE Maximum number of acquirable transmitters 50 Activation of output Activation of outputs is signalled by switching on of relevant LED L...