VENCO VCFI Series Скачать руководство пользователя страница 21

DANGER

Disconnect and secure to the ‘OFF’ position all 
electrical power to the fan prior to inspection or 
servicing. Failure to comply with this safety precaution 
could result in serious injury or death.

DANGER

Pour écarter les risques de blessure grave ou de mort, 
débrancher et verrouiller l’alimentation électrique en 
position « Arrêt » avant tout contrôle ou entretien.

Inspection of the fan should be conducted at the first  
30 minute and 24 hour intervals of satisfactory 
operation. 
  •  30 Minute Interval - Check all fasteners for 

tightness. Adjust and tighten as necessary. 

  •  24 Hour Interval - Inspect all fan components. 

Check all fasteners, airfoil retaining ring, the safety 
cable, and guy wires (if applicable). Adjust and 
tighten as necessary.

Inspection

IMPORTANT: 

If unusual vibration or oscillating 

movement is observed during fan operation, 
immediately discontinue use of the fan and contact the 
manufacturer or a suitably qualified maintenance/repair 
technician.
  1.  When the fan is started, observe the operation 

and check for any unusual noise, vibration or 
overheating. Refer to the Troubleshooting section 

of this manual if a problem develops. 

  2.  With the system in full operation, measure current 

input to the VFD and compare with the FLA ratings 
in the table above to determine if the motor/VFD 
system is operating under safe load conditions. 

  3.  Keep approaches to fan clean and free from 

obstruction.

Operation

NOTE: 

Installation and maintenance are to be 

performed only by qualified personnel who are familiar 
with local codes and regulations and have experience 
with this type of equipment. 
Once the fan has been put into operation, a periodic 
maintenance program should be set up to ensure 
reliable fan performance. A proper maintenance 
program will help deliver years of dependable service. 
Items to be included in this program are as follows:
  1.  Verify that all fasteners are tight and properly 

torqued.

  2.  Verify that all of the fan’s safety systems – safety 

cable, airfoil retaining ring, and guy wires (if 
applicable) are properly installed. Inspect for signs 
of damage or failure. Safety cable and guy wire 
tension should also be checked. Safety cable 
should be wrapped around the building structure 
leaving as little slack as possible. Guy wires 
should be under enough tension to prevent any 
lateral movement of the motor and downtube (if 
applicable).

  3.  Inspect the fan for signs of fatigue, corrosion, or 

wear.

 4.  Impellers require little attention when moving clean 

air. Occasionally, oil and dust may accumulate 
causing imbalance. When this occurs, clean 
the impeller and other fan components to 
ensure smooth and safe operation. Remove any 
accumulated dust and dirt using hot water or mild 
cleaning solutions. Harsh chemicals should not 
be used to clean the fan as they may damage the 
fan’s finish or motor.

IMPORTANT:

 Do not allow water or solvents to enter 

the motor. Under no circumstances should motors be 
sprayed with steam, water or solvents.
  5.  Motor maintenance is generally limited to cleaning. 

Limit cleaning to exterior surfaces only. Removing 
dust buildup on motor housing ensures proper 
motor cooling.

  6.  Prior to restarting unit, check all fasteners for 

tightness each time maintenance checks are 
performed. 

Maintenance

High Volume, Low Speed Ceiling Fans

21

Содержание VCFI Series

Страница 1: ...tandards including fire rated construction 2 When cutting or drilling into wall or ceiling do not damage electrical wiring and other hidden utilities WARNING This appliance can be used by children age...

Страница 2: ...e Protection Agency NFPA where applicable Follow the Canadian Electric Code CEC in Canada 2 The rotation of the impeller is critical It must be free to rotate without striking or rubbing any stationar...

Страница 3: ...nal use consider using Tectyl 511M Rust Preventive WD 40 or the equivalent Removing from Storage As fans are removed from storage to be installed in their final location they should be protected and m...

Страница 4: ...d location of the fan s 10 Before installation it is important to verify that the mounting surface will bear the operating weight and maximum torque twisting force of the unit The Structural Engineer...

Страница 5: ...INGLET POWER CABLE PLUG OPTIONAL LIGHT POWER CABLE OPTIONAL SAFETY CABLE WITH NO 4 GRIPPLE FACTORY INSTALLED VFD FIRE ALARM LANDING POINT COMMUNICATION CABLE WITH RJ45 SPLITTER LIGHT POWER PLUG OPTION...

Страница 6: ...BE MOUNT ASSEMBLY HEX BOLT I Beam Clamping Plate 2 I Beam Clamping Plate Shim 2 I BEAM CLAMPING PLATE I BEAM CLAMPING PLATE SHIM UNIVERSAL MOUNTING PLATE 1 2 in WASHER 1 2 in 13 GRADE 8 NYLON LOCKNUT...

Страница 7: ...o one side of the I beam and tighten hardware until the universal mounting plate is snug against the beam but can still be moved approximately 1 4 in of the bolt threads exposed below the nylon locknu...

Страница 8: ...Kit For Beams 4 1 2 8 7 8 in Wide Components required from Bag 915429 Wood Beam Bracket 2 1 2 in 13 x 1 1 2 in Grade 8 Hex Bolt 4 1 2 in 13 Grade 8 Nylon Locknut 8 1 2 in Washer 16 Hardware Tools Nee...

Страница 9: ...STEEL ANGLES BY OTHERS 1 2 in 13 x 1 3 4 in GRADE 8 HEX BOLT Z PURLIN 1 2 in WASHER Z PURLIN BRACKET 1 2 in 13 GRADE 8 NYLON LOCKNUT TORQUE TO 80 FT LBF 108 5 N m TORQUE TO 80 FT LBF 108 5 N m 5 Using...

Страница 10: ...motor hub assembly to their corresponding female connectors in the downtube DOWNTUBE AND MOUNT ASSEMBLY MOTOR HUB ASSEMBLY LIGHT POWER PLUG OPTIONAL LIGHT COMMUNICATION PLUG OPTIONAL LIGHT POWER PLUG...

Страница 11: ...1 5 on dipswitch 3 to set the desired Modbus address A table with all possible Modbus addresses is shown to the right IMPORTANT Positions 6 8 are used to set parameters needed for fan operation and sh...

Страница 12: ...e mounting structure referred to as the live end 4 Attach the dead end of the safety cable to the live end using the supplied 0 188 in u bolt steel cable IMPORTANT The first steel cable clamp must be...

Страница 13: ...Insert the loose end of the safety cable into the No 4 Gripple connector Note that the cable will only feed through the Gripple connector in one direction marked on the Gripple connector with an arrow...

Страница 14: ...ing IMPORTANT Steel cable clamps consist of two parts the u bolt and the saddle Steel cable clamps must be installed with the u bolt over the dead end of the guy wire and the saddle over the live end...

Страница 15: ...e that the fan is level in all directions 5 Cut or organize excess guy wires to ensure that they do not interfere with fan rotation NOTE If necessary the guy wires can be loosened by inserting the lon...

Страница 16: ...on locknuts per blade as shown below Hand tighten hardware 5 16 in WASHER 2 PER BLADE 5 16 in 18 GRADE 8 NYLON LOCKNUT 2 PER BLADE MOTOR HUB ASSEMBLY 5 16 in 18 x 2 in GRADE 8 HEX BOLT 2 PER BLADE MOT...

Страница 17: ...b retention bracket Install 4 1 4 in 20 x 3 4 in grade 5 hex bolts into the u nuts Torque to 96 in lbf 10 8 N m LIGHT POWER PLUG HUB COVERING PLATE HUB RETENTION BRACKET U NUT LIGHT BRACKET LIGHT POWE...

Страница 18: ...Communication Wiring Fan Control Installation IMPORTANT VCFI fans must be installed with the supplied CAT 5e communication cable or shielded CAT 5e by others that complies with the following specifica...

Страница 19: ...shock or serious injury DANGER Pour carter les risques d incendie de choc lectrique ou de blessure grave veiller toujours d brancher verrouiller et tiqueter la source de courant avant l installation...

Страница 20: ...d will match the models shown Install fuses per the manufacturer s recommendation Be sure to follow all national and local codes for electrical installation Fuse Sizing Chart VCFI 3 8 to 24 ft VCFI 6...

Страница 21: ...egulations and have experience with this type of equipment Once the fan has been put into operation a periodic maintenance program should be set up to ensure reliable fan performance A proper maintena...

Страница 22: ...nd fasteners for tightness Check guy wire tension if applicable Defective motor Replace motor Defective variable frequency drive VFD Replace VFD Fan does not operate Electrical supply Check for switch...

Страница 23: ...xxx 0 1000 RMS Modulated Output Voltage Volts 1 units 16 Current Motor RMS R xx x 0 150 RMS Motor current Amps 0 1 units 17 Temperature Motor R S xxx x 300 1100 Motor Temp C 0 1 units 18 Temperature T...

Страница 24: ...____________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ _____...

Отзывы: