  c.  Repeat step 5b. for subsequent fans until all 

fans in the chain are connected in series.

  d.  Follow the “Fan Networking” instructions on 

page 11 to complete network setup for the fans.

With Optional 1,000 ft. Bulk Spool of CAT-5e Cable

Included Component:
  •  1,000 ft. Bulk Spool of CAT-5e Control Cable (1)
  •  Shielded, Pass-Through RJ45 Connectors (25)
Hardware/Tools Needed (Not Included):
  •  Fan Control (1, optional)
  •  CAT-5e Termination Tool

  1.  Determine required length of CAT-5e cable run. 

Unspool appropriate amount of cable and cut to 
length.

IMPORTANT:

 Individual CAT-5e cable lengths must 

not exceed 200 ft. in order to prevent network 
communication issues.
  2.  Strip and remove 2 in. of CAT-5e cable jacket 

leaving the foil shield intact. 

  3.  Fold foil shield back over cable jacket and trim foil 

so that 1/4 in. remains. 

  4.  Untwist conductor pairs, straighten and align wires 

according to EIA/TIA T568B wiring pinout. 

1 2 3 4 5 6 7 8

1. White/Orange
2. Orange
3. White/Green
4. Blue
5. White/Blue
6. Green
7. White/Brown
8. Brown

Foil Shield

  5.  Trim conductor ends flush leaving 1 in. exposed. 
  6.  Fully insert cable into shielded, pass-through RJ45 

connectors until foil enters back end of connector. 
Use only the provided RJ45 connectors. 

  7.  Verify that conductors are in the correct wiring 

scheme order. 

  8.  Crimp RJ45 connector with CAT-5e termination tool 

(not included).

  9.  Repeat on opposite end of CAT-5e cable to 

complete cable construction.

 10.  Follow the “With Pre-Built CAT-5e Cable” 

instructions on page 18 to complete 
communication wiring and fan control installation.

Power Wiring Installation

DANGER

Always disconnect, lock and tag power source before 
installing or servicing. Failure to disconnect power 
source can result in fire, shock or serious injury.

DANGER

Pour écarter les risques d’incendie, de choc électrique 
ou de blessure grave, veiller à toujours débrancher, 
verrouiller et étiqueter la source de courant avant 
l’installation ou l’entretien.

IMPORTANT: 

Do not connect power until mechanical 

installation, fire alarm relay installation, communication 
wiring and fan control installation are complete.

IMPORTANT: 

Do not apply power to the fan above 

the rated voltage of the variable frequency drive (VFD). 
Failure to comply with this warning will result in voiding 
of the product warranty and may result in permanent 
damage to the VFD and motor.

IMPORTANT: 

To prevent electrical failures, source 

power must comply with the following power quality 
requirements. If source power falls outside of these 
specified tolerances, an external power line filter will be 
required (by others). If other power quality issues are 
present, contact the factory for support.

Allowable Voltage 

Fluctuation

+/- 10% of nominal

Allowable Frequency 

Fluctuation

+/- 5% of nominal (47-63 Hz)

Area of Use

Do not install fans in electrical environments 
with Pollution higher than Degree 2 in 
accordance with UL 61800-5-1

Surge Immunity

Do not install fans in electrical environments 
above Installation Class 3 in accordance 
with IEC 61000-4-5

Hardware/Tools Needed (Not Included):
  •  Phillips Screwdriver

With Optional Electrical Plug 

  1.   If the fan is supplied with the optional electrical 

plug for power wiring, refer to the chart below for 
the corresponding receptacle that will be needed 
(provided by others). 

Electrical Plug Reference (Locking)

Voltage

Phase

Plug*

Receptacle

208-230

1

L6-30P

L6-30R

277

1

L7-30P

L7-30R

208-230

3

L15-30P

L15-30R

460

3

L16-30P

L16-30R

*

NOTE: 

Plugs are available from manufacturer. Receptacles must be 

provided by others.

  2.  Install the receptacle according to all national and 

local codes for electrical wiring.

High Volume, Low Speed Ceiling Fans

19

Содержание VCFI Series

Страница 1: ...tandards including fire rated construction 2 When cutting or drilling into wall or ceiling do not damage electrical wiring and other hidden utilities WARNING This appliance can be used by children age...

Страница 2: ...e Protection Agency NFPA where applicable Follow the Canadian Electric Code CEC in Canada 2 The rotation of the impeller is critical It must be free to rotate without striking or rubbing any stationar...

Страница 3: ...nal use consider using Tectyl 511M Rust Preventive WD 40 or the equivalent Removing from Storage As fans are removed from storage to be installed in their final location they should be protected and m...

Страница 4: ...d location of the fan s 10 Before installation it is important to verify that the mounting surface will bear the operating weight and maximum torque twisting force of the unit The Structural Engineer...

Страница 5: ...INGLET POWER CABLE PLUG OPTIONAL LIGHT POWER CABLE OPTIONAL SAFETY CABLE WITH NO 4 GRIPPLE FACTORY INSTALLED VFD FIRE ALARM LANDING POINT COMMUNICATION CABLE WITH RJ45 SPLITTER LIGHT POWER PLUG OPTION...

Страница 6: ...BE MOUNT ASSEMBLY HEX BOLT I Beam Clamping Plate 2 I Beam Clamping Plate Shim 2 I BEAM CLAMPING PLATE I BEAM CLAMPING PLATE SHIM UNIVERSAL MOUNTING PLATE 1 2 in WASHER 1 2 in 13 GRADE 8 NYLON LOCKNUT...

Страница 7: ...o one side of the I beam and tighten hardware until the universal mounting plate is snug against the beam but can still be moved approximately 1 4 in of the bolt threads exposed below the nylon locknu...

Страница 8: ...Kit For Beams 4 1 2 8 7 8 in Wide Components required from Bag 915429 Wood Beam Bracket 2 1 2 in 13 x 1 1 2 in Grade 8 Hex Bolt 4 1 2 in 13 Grade 8 Nylon Locknut 8 1 2 in Washer 16 Hardware Tools Nee...

Страница 9: ...STEEL ANGLES BY OTHERS 1 2 in 13 x 1 3 4 in GRADE 8 HEX BOLT Z PURLIN 1 2 in WASHER Z PURLIN BRACKET 1 2 in 13 GRADE 8 NYLON LOCKNUT TORQUE TO 80 FT LBF 108 5 N m TORQUE TO 80 FT LBF 108 5 N m 5 Using...

Страница 10: ...motor hub assembly to their corresponding female connectors in the downtube DOWNTUBE AND MOUNT ASSEMBLY MOTOR HUB ASSEMBLY LIGHT POWER PLUG OPTIONAL LIGHT COMMUNICATION PLUG OPTIONAL LIGHT POWER PLUG...

Страница 11: ...1 5 on dipswitch 3 to set the desired Modbus address A table with all possible Modbus addresses is shown to the right IMPORTANT Positions 6 8 are used to set parameters needed for fan operation and sh...

Страница 12: ...e mounting structure referred to as the live end 4 Attach the dead end of the safety cable to the live end using the supplied 0 188 in u bolt steel cable IMPORTANT The first steel cable clamp must be...

Страница 13: ...Insert the loose end of the safety cable into the No 4 Gripple connector Note that the cable will only feed through the Gripple connector in one direction marked on the Gripple connector with an arrow...

Страница 14: ...ing IMPORTANT Steel cable clamps consist of two parts the u bolt and the saddle Steel cable clamps must be installed with the u bolt over the dead end of the guy wire and the saddle over the live end...

Страница 15: ...e that the fan is level in all directions 5 Cut or organize excess guy wires to ensure that they do not interfere with fan rotation NOTE If necessary the guy wires can be loosened by inserting the lon...

Страница 16: ...on locknuts per blade as shown below Hand tighten hardware 5 16 in WASHER 2 PER BLADE 5 16 in 18 GRADE 8 NYLON LOCKNUT 2 PER BLADE MOTOR HUB ASSEMBLY 5 16 in 18 x 2 in GRADE 8 HEX BOLT 2 PER BLADE MOT...

Страница 17: ...b retention bracket Install 4 1 4 in 20 x 3 4 in grade 5 hex bolts into the u nuts Torque to 96 in lbf 10 8 N m LIGHT POWER PLUG HUB COVERING PLATE HUB RETENTION BRACKET U NUT LIGHT BRACKET LIGHT POWE...

Страница 18: ...Communication Wiring Fan Control Installation IMPORTANT VCFI fans must be installed with the supplied CAT 5e communication cable or shielded CAT 5e by others that complies with the following specifica...

Страница 19: ...shock or serious injury DANGER Pour carter les risques d incendie de choc lectrique ou de blessure grave veiller toujours d brancher verrouiller et tiqueter la source de courant avant l installation...

Страница 20: ...d will match the models shown Install fuses per the manufacturer s recommendation Be sure to follow all national and local codes for electrical installation Fuse Sizing Chart VCFI 3 8 to 24 ft VCFI 6...

Страница 21: ...egulations and have experience with this type of equipment Once the fan has been put into operation a periodic maintenance program should be set up to ensure reliable fan performance A proper maintena...

Страница 22: ...nd fasteners for tightness Check guy wire tension if applicable Defective motor Replace motor Defective variable frequency drive VFD Replace VFD Fan does not operate Electrical supply Check for switch...

Страница 23: ...xxx 0 1000 RMS Modulated Output Voltage Volts 1 units 16 Current Motor RMS R xx x 0 150 RMS Motor current Amps 0 1 units 17 Temperature Motor R S xxx x 300 1100 Motor Temp C 0 1 units 18 Temperature T...

Страница 24: ...____________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ _____...