  8.  Plug in the motor power, motor ground, and hall 

cables as shown. Note that the connectors on the 
Hall and motor power cables only fit in one specific 
orientation.

HALL CONNECTION

3

NOTE:

HALL CABLE PLUG HAS BUILT-IN
ALIGNMENT TAB. DO NOT FORCE
THIS PLUG.  

MOTOR POWER

MOTOR GROUND

MOTOR POWER

MOTOR GROUND

HALL CONNECTION

  9.  Install rear VFD cover to the back of the VFD using 

(4) M4-0.7 x 10mm machine screws.

DOWNTUBE & MOUNT ASSEMBLY

MOTOR & HUB ASSEMBLY

FRONT VFD COVER

REAR VFD COVER

M4 - 0.7 x 10 MACHINE SCREW

If networking multiple fans to run using a single control 
source, the dipswitch settings on each fan’s VFD circuit 
board will need to be adjusted using the following 
instructions.

DIPSWITCH 3

DIPSWITCH 2

First Fan

  1.  Determine the first fan in the network daisy-chain 

by identifying the fan that is connected directly to 
the control source. 

  2.  Remove the front VFD cover from the first fan in the 

network using a phillips screwdriver.

  3.  Dipswitch 2 is used to set parameters that improve 

network function. Verify that each of the switches 
on dipswitch 2 are set as follows: 

      Position 1 – Off
      Position 2 – On
      Position 3 – On 
  4.  Dipswitch 3 is used to set unique Modbus 

addresses for each fan in the daisy-chain. Adjust 
positions 1-5 on dipswitch 3 to set the desired 
Modbus address. A table with all possible Modbus 
addresses is shown to the right.

IMPORTANT:

 Positions 6 – 8 are used to set parameters 

needed for fan operation and should not be adjusted.

  5.  Refer to instruction manual provided with HVLS 

control to determine if additional networking 
modifications are required. Follow instructions to 
complete necessary modifications. 

  6.  Reinstall the front VFD cover.

All Remaining Fans

  1.  Remove the front VFD cover using a phillips 

screwdriver.

  2.  Set dipswitch 2 as shown below. Dipswitch 2 is 

used to set parameters that improve network 
function and will need to be adjusted for all fans in 
the network except for the first fan.

      Position 1 – Off 
      Position 2 – Off
      Position 3 – Off 
  3.  Adjust positions 1 – 5 on dipswitch 3 so that each 

successive fan has a unique Modbus address. A 
table with all possible Modbus addresses is shown 
on the following page. 

IMPORTANT:

 Positions 6 – 8 are used to set parameters 

needed for fan operation and should not be adjusted.

NOTE: 

It is good practice to use successive Modbus 

addresses for networked fans, but this is not necessary 
for proper functioning of the network. 
  4.  Refer to instruction manual provided with HVLS 

control to determine if additional networking 
modifications are required. Follow instructions to 
complete necessary modifications. 

  5.  Reinstall the front VFD cover.

Fan Networking

High Volume, Low Speed Ceiling Fans

11

Содержание VCFI Series

Страница 1: ...tandards including fire rated construction 2 When cutting or drilling into wall or ceiling do not damage electrical wiring and other hidden utilities WARNING This appliance can be used by children age...

Страница 2: ...e Protection Agency NFPA where applicable Follow the Canadian Electric Code CEC in Canada 2 The rotation of the impeller is critical It must be free to rotate without striking or rubbing any stationar...

Страница 3: ...nal use consider using Tectyl 511M Rust Preventive WD 40 or the equivalent Removing from Storage As fans are removed from storage to be installed in their final location they should be protected and m...

Страница 4: ...d location of the fan s 10 Before installation it is important to verify that the mounting surface will bear the operating weight and maximum torque twisting force of the unit The Structural Engineer...

Страница 5: ...INGLET POWER CABLE PLUG OPTIONAL LIGHT POWER CABLE OPTIONAL SAFETY CABLE WITH NO 4 GRIPPLE FACTORY INSTALLED VFD FIRE ALARM LANDING POINT COMMUNICATION CABLE WITH RJ45 SPLITTER LIGHT POWER PLUG OPTION...

Страница 6: ...BE MOUNT ASSEMBLY HEX BOLT I Beam Clamping Plate 2 I Beam Clamping Plate Shim 2 I BEAM CLAMPING PLATE I BEAM CLAMPING PLATE SHIM UNIVERSAL MOUNTING PLATE 1 2 in WASHER 1 2 in 13 GRADE 8 NYLON LOCKNUT...

Страница 7: ...o one side of the I beam and tighten hardware until the universal mounting plate is snug against the beam but can still be moved approximately 1 4 in of the bolt threads exposed below the nylon locknu...

Страница 8: ...Kit For Beams 4 1 2 8 7 8 in Wide Components required from Bag 915429 Wood Beam Bracket 2 1 2 in 13 x 1 1 2 in Grade 8 Hex Bolt 4 1 2 in 13 Grade 8 Nylon Locknut 8 1 2 in Washer 16 Hardware Tools Nee...

Страница 9: ...STEEL ANGLES BY OTHERS 1 2 in 13 x 1 3 4 in GRADE 8 HEX BOLT Z PURLIN 1 2 in WASHER Z PURLIN BRACKET 1 2 in 13 GRADE 8 NYLON LOCKNUT TORQUE TO 80 FT LBF 108 5 N m TORQUE TO 80 FT LBF 108 5 N m 5 Using...

Страница 10: ...motor hub assembly to their corresponding female connectors in the downtube DOWNTUBE AND MOUNT ASSEMBLY MOTOR HUB ASSEMBLY LIGHT POWER PLUG OPTIONAL LIGHT COMMUNICATION PLUG OPTIONAL LIGHT POWER PLUG...

Страница 11: ...1 5 on dipswitch 3 to set the desired Modbus address A table with all possible Modbus addresses is shown to the right IMPORTANT Positions 6 8 are used to set parameters needed for fan operation and sh...

Страница 12: ...e mounting structure referred to as the live end 4 Attach the dead end of the safety cable to the live end using the supplied 0 188 in u bolt steel cable IMPORTANT The first steel cable clamp must be...

Страница 13: ...Insert the loose end of the safety cable into the No 4 Gripple connector Note that the cable will only feed through the Gripple connector in one direction marked on the Gripple connector with an arrow...

Страница 14: ...ing IMPORTANT Steel cable clamps consist of two parts the u bolt and the saddle Steel cable clamps must be installed with the u bolt over the dead end of the guy wire and the saddle over the live end...

Страница 15: ...e that the fan is level in all directions 5 Cut or organize excess guy wires to ensure that they do not interfere with fan rotation NOTE If necessary the guy wires can be loosened by inserting the lon...

Страница 16: ...on locknuts per blade as shown below Hand tighten hardware 5 16 in WASHER 2 PER BLADE 5 16 in 18 GRADE 8 NYLON LOCKNUT 2 PER BLADE MOTOR HUB ASSEMBLY 5 16 in 18 x 2 in GRADE 8 HEX BOLT 2 PER BLADE MOT...

Страница 17: ...b retention bracket Install 4 1 4 in 20 x 3 4 in grade 5 hex bolts into the u nuts Torque to 96 in lbf 10 8 N m LIGHT POWER PLUG HUB COVERING PLATE HUB RETENTION BRACKET U NUT LIGHT BRACKET LIGHT POWE...

Страница 18: ...Communication Wiring Fan Control Installation IMPORTANT VCFI fans must be installed with the supplied CAT 5e communication cable or shielded CAT 5e by others that complies with the following specifica...

Страница 19: ...shock or serious injury DANGER Pour carter les risques d incendie de choc lectrique ou de blessure grave veiller toujours d brancher verrouiller et tiqueter la source de courant avant l installation...

Страница 20: ...d will match the models shown Install fuses per the manufacturer s recommendation Be sure to follow all national and local codes for electrical installation Fuse Sizing Chart VCFI 3 8 to 24 ft VCFI 6...

Страница 21: ...egulations and have experience with this type of equipment Once the fan has been put into operation a periodic maintenance program should be set up to ensure reliable fan performance A proper maintena...

Страница 22: ...nd fasteners for tightness Check guy wire tension if applicable Defective motor Replace motor Defective variable frequency drive VFD Replace VFD Fan does not operate Electrical supply Check for switch...

Страница 23: ...xxx 0 1000 RMS Modulated Output Voltage Volts 1 units 16 Current Motor RMS R xx x 0 150 RMS Motor current Amps 0 1 units 17 Temperature Motor R S xxx x 300 1100 Motor Temp C 0 1 units 18 Temperature T...

Страница 24: ...____________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ _____...

Отзывы: