5 Operation
83 SD780 Series Servo Technical Manual
This signal is not configured in the factory default digital output configuration. Please confirm
before use.
The signal is not configured in the factory default digital output configuration. Therefore, the pin
number configuration (0x03) needs to be performed by parameters Pn613
~
Pn615.
The output condition is that the signal is output when the current feedback speed (absolute value)
of the motor is higher than the setting value of Pn317 (rotation determination threshold).
2.
Wiring of rotation detection signals
The rotation detection signal is a universally configurable digital output signal. See “Sequence
Output Circuit” for wiring details.
5.3.6 Consistent Speed
The speed coincidence signal (/V-CMP) is a signal that is output when the difference between the
speed of the servo motor and the command speed is equal to or lowers than the set value of the
speed coincidence range Pn320. Used when interlocking with the upper device. This signal is the
output signal during speed control.
1.
Configuration of Speed-consistent Signals
Function
code
Parameter
Range Default
Unit
Communication
address
When
enabled
Pn320
Speed consistent
range
0
~
100
10
rpm
0x0320
Immediately
When the difference between the motor speed and the command speed is lower
than the set value, the switch-speed match signal (/V-CMP) is output.
In the factory default digital output configuration, the signal is configured as CN129 and 30 pin
numbers (Pn614=0x02) by default. Please confirm before use.
OCZ
GND
Twisted pair
Servo driver
Controller
5V~30V
SEN
OCZ
GND
5V~30V
SEN
Example of optocoupler circuit
Example of relay circuit
Servo driver
Twisted pair
Controller