AC70 VC CONTROL FREQUENCY INVERTER MANUAL
APPENDIX
134
H-65
Motor magnetic saturation
coefficient 3
0-9999
※
●
116 341H
H-66
Linkage main station setting
0: Local machine configure as
linkage slave station
1: Main station control mode 1.
2: Main station control mode 2.
0
●
117 342H
H-67
Local inverter address
1-247
1
●
117 343H
H-68
Data format
0: No check (N,8,1)
1: E
ven parity check
(E,8,1)
2: Odd parity check
(O,8,1)
3:
No check
(N,8,2)
3
〇
117 344H
H-69
Baud rate
0: 1200bps
1: 2400bps
2: 4800bps
3: 9600bps
4: 19200bps
5: 38400bps
3
〇
117 345H
H-70
Communication setting
frequency ratio
0.00-20.00 1.00
●
117 346H
H-71
Time of communication time
out
0.0-6500.0s 10.0s
●
117 347H
H-72
RS485 communication
broken responding mode
LED“0” digit: RS485
communication
broken responding mode
0.Give alarm and free stop
1.No alarm and continue running
2.No alarm but stop
LED “00” digit: Communication
write operation mode.
0: Reply for write operation
1: No reply for write operation
LED “000” digit:: reserved
LED “0000” digit: reserved
0001
●
117 348H
H-73
Respond relay
0.000-1.000s 0.005s
●
118 349H
H-74
Instantaneous stop decel.
respond voltage lower limit
0%-200% 20%
●
118 34AH
H-75
Instantaneous stop decel.
respond voltage upper limit
0%-200%
90%
●
118 34BH
H-76
Instantaneous stop decel.
gain
0.01-10.00 2.00
●
118 34CH
H-77
Voltage recover stability
time
0.0-100.0s 2.0s
●
118 34DH
H-78
Torque compensation upper
limit
0.00-60.00% 50.00%
118
34EH
H-79
Output terminal external
control status
0-9999 0
●
118 34FH
H-80 Reserved
118 350H