AC70 VC CONTROL FREQUENCY INVERTER MANUAL
APPENDIX
126
F-07
Input signal respond mode
selection
LED unit digit: Free stop
terminal recover mode
0: Recover to original command
with speed search function.
1:Don’t recover to original
command after free stop terminal
disconnecting.
2: Recover to original command
without speed search function.
LED ten digit: UP and DW
terminal control starting
frequency setting
0: Runs with UP/DW terminal
adjusting without save the
frequency record after power loss.
1: Run to last stop moment
frequency and then perform
UP/DW adjusting.
2: Runs to preset frequency[F-70]
first, and then execute UP/DW
adjusting.
LED hundred digit: STOP/RESE
of keypad effective range
selection.
0: STOP/RESE key valid only
when under keypad control
1: STOP/RESE key valid under
any run command source
LED thousand digit: Terminal
running mode selection after
fault reset
0: Start inverter running directly
after power on in terminal control
mode
1: Stop first and then start in
terminal control mode.
0001
〇
94 207H