AC70 VC CONTROL FREQUENCY INVERTER MANUAL
FUNCTION PARAMETER DETAILED SPECIFICATION
107
F-62
Analog output signal
selection
Range: 0000-0023
Default: 0003
LED unit digit: A02 output signal mode selection
0: Frequency pulse train output default setting for 0.2KHz to 10.0KHz;
1:0-20mA
2:4-20mA
3:0-10V
LED ten digit: A01 output signal mode selection
0:0-10V
1:0-20mA
2:4-20mA
LED hundred digit: Reserve
LED thousand digit: Reserve
Tip: After output mode selected by software configured, it also need to select by J1, I2, J3, J4, J5 ,
terminals pin short connection. Refer to following for selecting in detail.
A02 selects for frequency pulse train output, need select J1 among J1, J2, J3 dial switching.
A02 selects for 0-20ma or 4-20mA output signal, need select J2 among J1, J2, J3 dial switching.
A02 selects for 0-10V output signal, need select J2 among J1, J2, J3 dial switching.
A01 selects for 0-20mA or 4-20mA output signal, need make J5 short connection, J4 disconnect.
A01 selects for 0-10V output signal, need make J4 short connection, J5 disconnect.
In the factory default setting of A01 and A02 output signal is 0-10V analog output. If need other output
mode, please configure the software and hardware according requirement.
F-63 AO1 output signal gain
Range: 25%-200%
Default: 100%
F-64 AO2 output signal gain
Range: 25%-200%
Default: 100%
Used to adjust AO1 terminal output analog value and AO2 output signal value.
F-65 AO1 output signal zero adjust
Range : -10%-10%
Default: 0.0
F-66 AO2 output signal zero adjust
Range : -10%-10%
Default: 0.0
Used to adjust the output signal zero point of (AO1) terminal and (AO2) terminal. It is invalid to adjust this value
when (AO2) is frequency pulse output.
F-67
Keypad potentiometer input
lower limit voltage
Range: 0.00V-[F-68]
Default: 0.20V
F-68
Keypad potentiometer input
upper limit voltage
Range:[F-67]-5.50V Default:
4.80V
F-69 Keypad potentiometer gain
Range: 0.00-5.00
Default: 1.00
Keypad potentiometer input voltage lower limit
This function defines the minimum signal received by the
keyboard potentiometer. Frequency inverter will automatically filters the signal whose value is lower than this value;
Keypad potentiometer input voltage upper limit
This function defines the maximum signal received by the
keyboard potentiometer. Frequency inverter will automatically filters the signal whose value is upper than this value.
Keypad potentiometer gain
This function is used to amplify or reduce keyboard potentiometer input analog
quantity.
Tips: Keypad potentiometer input voltage upper limit is corresponding to frequency upper limit [E-10] ,
Keyboard potentiometer input voltage upper limit is corresponding to 0.00 Hz.