AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING
10
Chart 3-1: treatment for inverter after longtime store
3.3 Inverter Stable Running Environment
Installation environment is very important to the best use of this product for long time. Pls install this product in the
environment as the following table requirement.
Environment
Requirement
Install place
Indoor without direct sunshine
Install temperature
-10
~
+40
℃
Store temperature
-20
~
+60
℃
Humidity
<95%RH, no condensation
Surrounding
Please install the inverter in place as follows:
●
Place without oil mist, corrosive gases, flammable gas, dust or etc.
●
Place without metal dust, oil, water or etc into inverter (please do not install inverter on
flammable material such as food and etc).
●
Place without radioactive material or flammable material.
●
Place without poisonous gases or liquid.
●
Place with very little salification erosion.
●
Place whihout direct sunshine.
Altitude <1000m
Vibration
<10
~
20Hz:9.8m/s
2
<20
~
55Hz:5.9m/s
2
Installation and
cooling
●
Inverter can not be installed horizontally must be installed vertically.
●
Please independently install high heating equipments such as braking resistor and etc which
can not be installed in the same cabinet with inverter, installed at the air-in port of the inverter
is strictly prohibited.
Table 3-1:AC70 series inverter running environment condition
●
In order to improve the product stability, pls do not use the inverter where temperature changes sharply. While
using in closed space such as control cabinet, please use cooling fan or air-condition to cool inverter to avoid
temperature over limit range. Please also prevent inverter from freeze, too low temperature may cause components
freeze fault.