AC300 Series Vector Control Inverter Manual
Function Parameter Specifications
104
Keyboard up and down keys quickly modify the parameter number setting:
LED “00” digit
: used to specify the parameter number 00~99
LED “000” digit
: used to specify parameter group number 00~15
F04.14
Keyboard display parameter 1
LED one digit ten: yy setting in monitoring
code Cxx.yy
LED hundred thousand digits: xx setting in
monitoring code Cxx.yy
For example: set "0000" to indicate that
the monitoring code C00.00
Factory default: 0000
F04.15
Keyboard display parameter 2
Same as above
Factory default: 0001
F04.16
Keyboard display parameter 3
Same as above
Factory default: 0002
F04.17
Keyboard display parameter 4
Same as above
Factory default: 0011
Keyboard display parameters: used to set the contents of the single-line keyboard and double-line keyboard display
parameters.
If F004.14 is set to 0000, the keyboard displays C00.00 given frequency.
Set to :0004 The display parameter is C00.04 (output voltage)
Set to :0011 and the display parameter is C00.11 (bus voltage)
Set to: 0200 The display parameter is C02.00 (PID feedback)
Set to: 0300 The display parameter is C02.00 (this power-on running time)
The single-line keyboard switches the keyboard display parameters 1-4 in sequence by long pressing the “SET”
button (the two-line keyboard can be pressed through the “
” button). Each time the button is pressed, one item is
skipped and cycles between display parameters 1-4.
After the display content is switched, there is no power-off and memory function. After power-on, the content of
“Display Parameter 1” is displayed by default.
Access ‘C’ parameter group by pressing ‘PRG’ for more than 2s; check the current state of VFD
C00-Basic Parameter Monitor Group
Function code
Function name
Unit and definition
Address
C00.00 Given
frequency
0.01Hz
0x2100
C00.01 Output
frequency
0.01Hz
0x2101
C00.02 Output
current
0.1A
0x2102
C00.03 Input
voltage
0.1V
0x2103
C00.04 Output
voltage
0.1V
0x2104
C00.05 Machine
speed
1RPM
0x2105
AC300 Series Vector Control Inverter Manual
Function Parameter Specifications
105
C00.06 Given
torque
0.1%
0x2106
C00.07 Output
torque
0.1%
0x2107
C00.08
PID given value
0.1%
0x2108
C00.09
PID feedback value
0.1%
0x2109
C00.10 Output
power
0.1%
0x210A
C00.11 Bus
voltage
0.1V
0x210B
C00.12
Module temperature 1
0.1
℃
0x210C
C00.13
Module temperature 2
0.1
℃
0x210D
C00.14
Input terminal X on state
See input terminal diagram
0x210E
C00.15
Output terminal Y on state
See output terminal diagram
0x210F
C00.16
Analog AI1 input value
0.001V/0.001mA
0x2110
C00.17
Analog AI2 input value
0.001V/0.001mA
0x2111
C00.18 Reserved
0x2112
C00.19
Pulse input value of PUL port
0.001kHz
0x2113
C00.20 Analog
output
AO1
0.01V/0.01mA/0.01kHz 0x2114
C00.21 Analog
output
AO2(extend) 0.01V/0.01mA/0.01kHz
0x2115
C00.22
Counting value of counter
0x2116
C00.23
Running time after power on
0.1 hour
0x2117
C00.24
Local accumulative running time
hour
0x2118
C00.25
VFD power level
kW
0x2119
C00.26
VFD rated voltage
V
0x211A
C00.27
VFD rated current
A
0x211B
C00.28 Software
version
0x211C
C00.29
PG feedback frequency
0.01Hz
0x211D
C00.30
Counted time of timer sec/min/hour
0x211E
C00.31
PID output value
0.00%
0x211F
C00.32 Software
sub-version
0x2120
C00.33 Encoder
angle
0.1°
0x2121
C00.34
Encoder deviation accumulative
1
0x2122
C00.35
Encoder Z signal pulse count
1
0x2123
C00.36
Fault pre alarm code
1
0x2124
C00.37
Total power consumption (low bit)
1°
0x2125
C00.38
Total power consumption (high bit)
10000°
0x2126
C00.39
Power factor angle
1°
0x2127