AC300 Series Vector Control Inverter Manual
Function Parameter Specifications
98
5 Machine
speed
Corresponding to the
mechanical speed
corresponding to the
output frequency of the
The minimum output
corresponds to 0rpm
The maximum output
corresponds to the speed
corresponding to the
maximum frequency
6 Given
torque
Corresponding to the
output torque of the
current inverter
The minimum output
corresponds to a torque
of 0.00%
The maximum output
corresponds to 200% of the
torque
7 Output
torque
Corresponding to the
output torque of the
current inverter
The minimum output
corresponds to a torque
of 0.00%
The maximum output
corresponds to 200% of the
torque
8
PID given value
Corresponding to the PID
given by the current
inverter
The minimum output
corresponds to 0.00%
PID given
The maximum output
corresponds to 100% PID
given
9
PID feedback value
Corresponding to the PID
feedback amount of the
current inverter
The minimum output
corresponds to 0.00%
PID feedback
The maximum output
corresponds to 100% of the
PID feedback amount
10 Output
power
Corresponds to the
output power of the
current inverter
The minimum output
corresponds to 0 power
Maximum output
corresponds to rated output
power
11 Bus
voltage
Corresponds to the input
voltage of the current
inverter
The minimum output
corresponds to 0V
The maximum output
corresponds to twice the
rated DC voltage of the
12 AI1
Corresponds to the
current AI1 input value of
the inverter
The minimum output
corresponds to the AI1
input lower limit
The maximum output
corresponds to the upper
limit of the AI1 input.
13 AI2
Corresponds to the
current AI input value of
the inverter
The minimum output
corresponds to the AI
input lower limit
The maximum output
corresponds to the upper
limit of the AI input.
14 AS
input
Corresponds to the AS
input value of the current
inverter
The minimum output
corresponds to the AS
input lower limit
The maximum output
corresponds to the upper
limit of the AS input.
15 PULoutput
value
Corresponds to the PUL
input value of the current
inverter
The minimum output
corresponds to the PUL
input lower limit
The maximum output
corresponds to the upper
limit of the PUL input.
AC300 Series Vector Control Inverter Manual
Function Parameter Specifications
99
16
Module temperature 1
Corresponds to the
module temperature 1 of
the current inverter
The minimum output
corresponds to the
module temperature 1 is
0 degrees Celsius
The maximum output
corresponds to the module
temperature 1 is 100
degrees Celsius
17
Module temperature 2
Corresponds to the
module temperature 2 of
the current inverter
The minimum output
corresponds to the
module temperature 2 is
0 degrees Celsius
The maximum output
corresponds to module
temperature 2 of 100
degrees Celsius
18 RS485
given
AO address 0x3019
/0x2019
AO2 address 0x301A
/0x201A
Minimum output
corresponds to 0
The maximum output
corresponds to 1000
AO output gain:
The value used to adjust the analog output of the (AO) terminal.
A0 output signal offset:
Used to adjust the zero point of the (AO) terminal output signal.
AO analog output and gain, offset schematic
A0 output filtering:
This parameter is defined as the size of the AO1 output analog signal filtered to eliminate the interference signal. The
F03.40
A01 output gain
Setting range : 0.0
~
200.0%
Default : 100.0%
F03.41
A01 analog output signal bias
Setting range : -10.0
~
10.0%
Default : 0.0%
F03.42
A01 output filter
Setting range : 0.000
~
6.000s
Default : 0.010s