AC300 Series Vector Control Inverter Manual
Function Parameter Table
154
channel switch to terminal
F02.25
Counter input
0: Common X terminal
1: High speed input terminal PUL
2: PG card counting
0
●
0x219
F02.26
Count input frequency
0
~
6000
0
●
0x21A
F02.27
PUL signal source
0: X5(max
~
5 KHz)
1: Extend interface X10
0
〇
0x21B
F02.28
PUL input min frequency
0.00
~
50.00 KHz
0.00kH
●
0x21C
F02.29
PUL min frequency
corresponding setting
0.00
~
100.00%
0.00%
●
0x21D
F02.30
PUL input max frequency
0.00
~
50.00 KHz
50.00k
●
0x21E
F02.31
PUL max frequency
corresponding setting
0.00
~
100.00%
100.00
%
●
0x21F
F02.32
PUL filter time
0.000
~
9.000s
0.100s
●
0x220
F02.33
PUL cut-off frequency
0.000
~
1.000 KHz
0.010k
●
0x221
F02.34
UP/DW terminal control
mode
0: Off electricity storage
1: Off electricity does not storage
2: Valid in running, clear zero at
t
0
〇
0x222
F02.35
ACC/DEC speed of
UP/DW terminal
frequency control
0.01
~
50.00Hz/s
0.50Hz
/s
●
0x223
F02.36
Reserved
0x224
F02.37
Timer time unit
0:Second 1:Minute 2:Hour
0
●
0x225
F02.38
Timer setting value
0
~
65000
0
●
0x226
F02.39
Counter max value
0
~
65000
1000
●
0x227
F02.40
Counter setting value
0
~
65000
500
●
0x228
F02.41
Reserved
0x229
F02.42
Output terminal polarity
selection
0: Positive 1: Negative
LED “0” digit: Terminal Y
LED “00” digit: Relay output 1
LED “000” digit: Extended Y1
terminal
LED “0000” digit: Extended
Relay output 2
0000
●
0x22A
F02.43
Output terminal Y1
Refer to function table 4.2
1
●
0x22B
F02.44
Relay output
Refer to function table 4.2
4
●
0x22C
F02.45
Extend terminal Y1
Refer to function table 4.2
0x22D
F02.46
Extend relay output 2
Refer to function table 4.2
0x22E
F02.47
Y output delay time
0.000
~
6.000s
0.010s
●
0x22F
F02.48
Extend Y output delay
0.000
~
6.000s
0.010s
●
0x230
F02.49
Relay 1 output delay time
0.000
~
6.000s
0.010s
●
0x231
F02.50
Extend relay 2 output
0.000
~
6.000s
0.010s
●
0x232
F02.51
Output frequency level
0.00
~
Max. frequency
30.00H
●
0x233
F02.52
FDT1 lag
0.00
~
Max. frequency
1.00Hz
●
0x234
F02.53
Output frequency level
0.00
~
Max. frequency
50.00H
●
0x235
AC300 Series Vector Control Inverter Manual
Function Parameter Table
155
F02.54
FDT2 lag
0.00
~
Max. frequency
1.00Hz
●
0x236
F02.55
Given frequency arriving
checkout range
0.00
~
50.00Hz
2.00Hz
●
0x237
F02.60
Virtual vX1 terminal
function selection
Refer to function table 4.2
0
●
0x238
F02.61
Virtual vX2 terminal
function selection
Refer to function table 4.2
0
●
0x239
F02.62
Virtual vX3 terminal
function selection
Refer to function table 4.2
0
●
0x23A
F02.63
Virtual vX4 terminal
function selection
Refer to function table 4.2
0
●
0x23B
F02.64
vX terminal valid state
source
0: internal connection with virtual
vYn
1: Connect with physical terminal
Xn
2: function code setting valid or not
LED “0” digit: virtual vX1
LED “00” digit: virtual vX2
0
●
0x23C
F02.65
Virtual vX terminal
function code setting valid
state
0: invalid 1: valid
LED “0” digit: virtual vX1
LED “00” digit: virtual vX2
LED “000” digit: virtual vX3
LED “0000” digit: virtual vX4
0
●
0x23D
F02.66
Virtual vY1 terminal
function selection
Refer to function table 4.2
0
●
0x23E
F02.67
Virtual vY2 terminal
function selection
Refer to function table 4.2
0
●
0x23F
F02.68
Virtual vY3 terminal
function selection
Refer to function table 4.2
0
●
0x240
F02.69
Virtual vY4 terminal
function selection
Refer to function table 4.2
0
●
0x241
F02.70
vY1 output delay
0.000
~
6.000s
0.010
●
0x242
F02.71
vY2 output delay
0.000
~
6.000s
0.010
●
0x243
F02.72
vY3 output delay
0.000
~
6.000s
0.010
●
0x244
F02.73
Virtual vY2 output
0.000
~
6.000s
0.010
●
0x245
Analog Terminal Parameters
NO.
Function description
Range of settings and definition
Factory
setting
Feature
Address
F03.00
AI1 Lower limit
0.00
~
10.00V
0.00V
●
0x300
F03.01
AI1 Lower limit
corresponding setting
-100.00
~
100.00%
0.00%
●
0x301
F03.02
AI1 upper limit
0.00
~
10.00V
10.00V
●
0x302