AC300 Series Vector Control Inverter Manual
Function Parameter Table
170
F11.07
PID control selection
LED”0” digit: Feedback feature
selection
0: Positive feature 1:Negative
feature
LED”00”/”000” digit: Reserved
LED”0000” digit: Differential
adjustment properties
0: Differential bias
1: Differential of feedback
0100
●
0xB07
F11.08
PID preset output
0.0
~
100.0%
100.0%
●
0xB08
F11.09
PID preset output
running time
0.0
~
6500.0s
0.0s
●
0xB09
F11.10
PID control deviation
0.0
~
100.0%
0.0%
●
0xB0A
F11.11
Proportional gain P1
0.000
~
8.000
0.100
●
0xB0B
F11.12
Integral time I1
0.0
~
600.0s
1.0s
●
0xB0C
F11.13
Differential time D1
0.000
~
6.000s
0.000s
●
0xB0D
F11.14
Proportional gain P2
0.000
~
8.000
0.100
●
0xB0E
F11.15
Integral time I2
0.0
~
600.0s
1.0s
●
0xB0F
F11.16
Differential gain D2
0.000
~
6.000s
0.000s
●
0xB10
F11.17
PID Parameter
switching condition
0: No switch
1: Use DI terminal to switch
2: Switch according to deviation
0
●
0xB11
F11.18
Low value of
switching deviation
0.0
~
100.0%
20.0%
●
0xB12
F11.19
High value of
switching deviation
0.0
~
100.0%
80.0%
●
0xB13
F11.20
Reserved
0xB14
F11.21
Differential limit
0.0
~
100.0%
5.0%
●
0xB15
F11.22
PID output upper limit
0.0
~
100.0%
100.0%
●
0xB16
F11.23
PID output lower limit
-100.0
~
F11.19
0.0%
●
0xB17
F11.24
PID output filter time
0.000
~
6.000s
0.000s
●
0xB18
F11.25
Feedback wire break
detection time
0.0
~
120.0s
1.0s
●
0xB19
F11.26
Feedback wire break
action selection
0: Go on PID operation without alarm
1: Stop and alarm malfunction
2: continue to PID operation and
output alarm signal
3: Run at the current frequency and
output alarm signal
0
●
0xB1A
F11.27
Wire break alarm
0.0
~
100.0%
100.0%
●
0xB1B
F11.28
Wire break alarm
0.0
~
100.0%
0.0%
●
0xB1C
F11.29
Close-loop suspend
detection threshold
0.0
~
100.0%
0.0%
●
0xB1D
F11.30
Close-loop suspend
detection time
0.0
~
600.0s
1.0s
●
0xB1E
AC300 Series Vector Control Inverter Manual
Function Parameter Table
171
Multi-Speed and PLC Function Parameter Group
NO.
Function description
Range of setting and definition
Factory
default
Feature
Address
F12.00
PLC Speed 1
0.00
~
Max frequency
10.00Hz
●
0xC00
F12.01
PLC Speed 2
0.00
~
Max frequency
20.00Hz
●
0xC01
F12.02
PLC Speed 3
0.00
~
Max frequency
30.00Hz
●
0xC02
F12.03
PLC Speed 4
0.00
~
Max frequency
40.00Hz
●
0xC03
F12.04
PLC Speed 5
0.00
~
Max frequency
50.00Hz
●
0xC04
F12.05
PLC Speed 6
0.00
~
Max frequency
40.00Hz
●
0xC05
F12.06
PLC Speed 7
0.00
~
Max frequency
30.00Hz
●
0xC06
F12.23
PLC Speed 8
0.00
~
Max frequency
20.00Hz
●
0xC07
F12.08
PLC Speed 9
0.00
~
Max frequency
10.00Hz
●
0xC08
F12.09
PLC Speed 10
0.00
~
Max frequency
20.00Hz
●
0xC09
F12.10
PLC Speed 11
0.00
~
Max frequency
30.00Hz
●
0xC0A
F12.11
PLC Speed 12
0.00
~
Max frequency
40.00Hz
●
0xC0B
F12.12
PLC Speed 13
0.00
~
Max frequency
50.00Hz
●
0xC0C
F12.13
PLC Speed 14
0.00
~
Max frequency
40.00Hz
●
0xC0D
F12.14
PLC Speed 15
0.00
~
Max frequency
30.00Hz
●
0xC0E
F12.15
PLC Running mode
selection
LED”0” digit: cycle mode
0: Stop after single cycle
1: Continuous cycles
2: Keep final value after single cycle
LED”00” digit: Time unit
0: second 1: minute
2:hour
LED”000” digit: Power down
memory
0: Not save 1: save
LED”0000” digit: Start mode
0: Restart from the 1st stage
1: Restart from the stop stage
2: Continue running from the time
when stop
0000
●
0xC0F
F12.16
PLC 1st step running
0.0
~
6500.0(s/m/h)
10.0
●
0xC10
F12.17
PLC 2nd step running
0.0
~
6500.0(s/m/h)
10.0
●
0xC11
F12.18
PLC 3rd step running
0.0
~
6500.0(s/m/h)
10.0
●
0xC12
F12.19
PLC 4thstep running time
0.0
~
6500.0(s/m/h)
10.0
●
0xC13
F12.20
PLC 5th step running
0.0
~
6500.0(s/m/h)
10.0
●
0xC14
F12.21
PLC 6th step running
0.0
~
6500.0(s/m/h)
10.0
●
0xC15
F12.22
PLC 7th step running
0.0
~
6500.0(s/m/h)
10.0
●
0xC16
F12.23
PLC 8th step running
0.0
~
6500.0(s/m/h)
10.0
●
0xC17
F12.24
PLC 9th step running
0.0
~
6500.0(s/m/h)
10.0
●
0xC18
F12.25
PLC 10th step running
0.0
~
6500.0(s/m/h)
10.0
●
0xC19
F12.26
PLC 11th step running
0.0
~
6500.0(s/m/h)
10.0
●
0xC1A