AC300 Series Vector Control Inverter Manual
Basic Operation and Trial Run
32
Stop/Reset
Stop/Reset
When the command given channel is keyboard control, press
this key to stop the inverter; the parameter [F04.08] can be used
to define whether other command channels are valid; the
inverter resets when pressing the key in fault status.
G
Digital potentiometer: clockwise to increase the operating value,
counterclockwise to decrease the operating value
Set key: After modifying the value, press this key to confirm the
modified value.
Left/Right Shift
Move left and right operation bits
H
Jog/Reverse
Select the function of the key by parameter [F04.07], 0: reverse
1: jog
●
Number word comparison table
Table 4-1: Digital Text Comparison Table
AC300 Series Vector Control Inverter Manual
Fault Diagnoses and Processing
33
Chapter 5 Fault Diagnoses and Processing
This chapter explains the display content and processing of the inverter fault, alarm and operation fault. It also simply
explains the bad situation caused by inverter or motor fault and how to solve it. For the adjustment guide in trial run,
please refer this chapter too.
5.1
Fault Types
Type
Inverter action while fault happens
External fault
In certain application occasions, external related equipments fault signals are considered in
the inverter control system as usage of monitoring, protection or switch control. At this time,
if one multi function terminal is defied as “external fault”, the inverter stops output alarm
signal.
5.2
Fault Information and Details
Chart 5-1: Fault information and details
Keyboard
display
Commu
nication
code
Fault type
Possible causes
Treatment
64
Too low
voltage while
stop
●
Power supply is too low
●
Voltage detection circuit is
abnormal
●
Check input power,clear
fault.
●
Seek support from factory.
10
Too low
voltage in run
●
Power supply is too low
●
Power capacitance is too
small, or there is big impact
current in the power grid.
●
Inner DC main contactor is
not connect well
●
Check input power,clear
fault.
●
Improve power supply.
●
Seek support from factory.
7
Accel.
over-voltage
●
Power voltage fluctuation
over limit.
●
Start when motor is running .
●
Detect power voltage and
clear fault.
●
Restart motor until it
completely stop.Set E-30 as
1or2.