62
VEGASON 51K … 53K
Set-up
Continuation HART
®
-menu plan – VEGASON 51K…53K
from 1.3.4
1.3.4.8
Available initialisation words:
..SOL
Meas. condition solid
..LIQ
Meas. condition liquid
..FED
Delete false echo memory
..FEN04.58M
False echo e.g. at 4.58 m create new
..FEN48.67FT
False echo e.g. at 48.67 ft create new
..FEU03.68M
Extend false echo memory:
add a new false echo to the false echo memory at 3.68 m
..FEU36.05FT
add a new false echo to the false echo memory at 36.05 ft
Initialisation word
(enter at last)
newly entered and initialisa-
tion word to enquire with
ENTER and SEND
D
Note:
After the adjustment of the initialisation word, press
"ENTER“ and then "SEND“.
Confirm the message to change over to manual
operation with "OK“ and the message to switch over
to automatic operation again with "OK“.
Only then is the adjustment written in the sensor and
effective.
1.4.3.1
1.4.3.1.2
Low:
In case of failure current output
goes to 22 mA
High:
In case of failure current output
goes to < 3,6 mA
1.4.3.1.3
1.4.3.1.3.1
from
1.4.3.
Warning:
Switch off
control!
Generic: SENSOR
Message
..SOL
..FEN04.58M
HELP DEL ESC ENTER
Generic: SENSOR
Analogue output
1 A01
13,467mA
2 A0 Alrm typ
3 Loop test
4 D/A trim
5 Scaled D/A trim
HELP SAVE HOME
Generic: SENSOR
Choose analogue output
level
1 4 mA
2 20 mA
3 Other
4 End
Abort Enter
Generic: SENSOR
Fld dev output is
fixed at 4.000 mA
ABORTOK
Generic: SENSOR
A0 Alrm typ
Hold last out valu
Exit