11 Supplement

VEGAFLEX 81 • Profibus PA

44214-EN-171002

Fig. 38: VEGAFLEX 81: Block diagram with AI FB 1 … AI FB 3 OUT values
TB  Transducer Block

FB 1 … FB 3 

Function Block

Module of the PA sensors

For the cyclic data traffic, VEGAFLEX 81 provides the following modules:

• 

AI FB1 (OUT)

 

Out value of the AI FB1 after scaling

• 

AI FB2 (OUT)

 

Out value of the AI FB2 after scaling

• 

AI FB3 (OUT)

 

Out value of the AI FB3 after scaling

• 

Free Place

 

This module must be used if a value in the data telegram of the cyclical data traffic should not 

be used (e.g. replacement of temperature and Additional Cyclic Value)

A maximum of three modules can be active. By means of the configuration software of the Profibus 

master you can determine the configuration of the cyclical data telegram with these modules. The 

procedure depends on the respective configuration software.

Note:

The modules are available in two versions:

• 

Short for Profibus master supporting only one "Identifier Format" byte, e.g. Allen 

Bradley

Содержание VEGAFLEX 81

Страница 1: ...Operating Instructions TDR sensor for continuous level and interface measurement of liquids VEGAFLEX 81 Profibus PA Coax probe Document ID 44214 ...

Страница 2: ... Connecting to power supply 17 5 1 Preparing the connection 17 5 2 Connecting 18 5 3 Wiring plan single chamber housing 20 5 4 Wiring plan double chamber housing 20 5 5 Double chamber housing with VEGADIS Adapter 21 5 6 Wiring plan version IP 66 IP 68 1 bar 22 5 7 Set instrument address 22 5 8 Switch on phase 23 6 Set up with the display and adjustment module 24 6 1 Insert display and adjustment m...

Страница 3: ...10 1 Dismounting steps 62 10 2 Disposal 62 11 Supplement 63 11 1 Technical data 63 11 2 Communication Profibus PA 73 11 3 Dimensions 77 11 4 Industrial property rights 81 11 5 Trademark 81 Safety instructions for Ex areas Take note of the Ex specific safety instructions for Ex applications These instructions are attached as documents to each instrument with Ex approval and are part of the operatin...

Страница 4: ...ID This symbol on the front page of this instruction refers to the Docu ment ID By entering the Document ID on www vega com you will reach the document download Information tip note This symbol indicates helpful additional information Caution If this warning is ignored faults or malfunctions can result Warning If this warning is ignored injury to persons and or serious damage to the instrument can...

Страница 5: ... all prevailing regulations and directives The instrument must only be operated in a technically flawless and reliable condition The operator is responsi ble for the trouble free operation of the instrument When measuring aggressive or corrosive media that can cause a dangerous situation if the instrument malfunctions the operator has to implement suitable measures to make sure the instrument is f...

Страница 6: ...n field instrumentation The device fulfils the requirements of the following NAMUR recom mendations NE 21 Electromagnetic compatibility of equipment NE 53 Compatibility of field devices and display adjustment components NE 107 Self monitoring and diagnosis of field devices For further information see www namur de 2 7 Installation and operation in the USA and Canada This information is only valid f...

Страница 7: ...instrument 12 Symbol of the device protection class 13 ID numbers instrument documentation 14 Reminder to observe the instrument documentation 15 Notified authority for CE marking 16 Approval directives The type label contains the serial number of the instrument With it you can find the following instrument data on our homepage Product code HTML Delivery date HTML Order specific instrument feature...

Страница 8: ...Instructions for optional instrument features Ex specific Safety instructions with Ex versions If necessary further certificates DVD DTM Collection included therein PACTware DTM Collection Instrument master files GSD for Profibus PA FDT certificates Information In this operating instructions manual the optional instrument features are described The respective scope of delivery results from the ord...

Страница 9: ...owave im pulses is reflected The other part passes through the upper product and is reflected by the interface The running times to the two product layers are processed by the instrument TS d1 h1 h2 d2 1 L2 L1 L3 Fig 3 Interface measurement 1 Sensor reference plane seal surface of the process fitting d1 Distance to the interface d2 Distance to the level TS Thickness of the upper medium d1 d2 h1 He...

Страница 10: ...phase does not always exist d2 0 The instrument is always preset to the application Level measure ment For the interface measurement you can select the requested output signal with the setup 3 3 Packaging transport and storage Your instrument was protected by packaging during transport Its capacity to handle normal loads during transport is assured by a test based on ISO 4180 The packaging of stan...

Страница 11: ...ing system You can find further information in the operating instructions Display and adjustment module PLICSCOM Document ID 36433 The interface adapter VEGACONNECT enables the connection of communication capable instruments to the USB interface of a PC For parameter adjustment of these instruments the adjustment software PACTware with VEGA DTM is required You can find further information in the o...

Страница 12: ...her information in the operating instructions manual Electronics module VEGAFLEX series 80 The display and adjustment module can be optionally replaced by a display and adjustment module with heating function You can use this display and adjustment module in an ambient tem perature range of 40 70 C You can find further information in the operating instructions Display and adjustment module with he...

Страница 13: ...Make sure that the degree of contamination specified in chapter Technical data meets the existing ambient conditions Metric threads In the case of instrument housings with metric thread the cable glands are screwed in at the factory They are sealed with plastic plugs as transport protection You have to remove these plugs before electrical connection NPT thread In the case of instrument housings wi...

Страница 14: ...the center of the vessel as measurement is then possible nearly down to the lowest point of the bottom Keep in mind that measurement all the way down to the tip of the probe may not be pos sible The exact value of the min distance lower dead band is stated in chapter Technical data Fig 4 Vessel with conical bottom Before beginning the welding work remove the electronics module from the sensor By d...

Страница 15: ...essure in the vessel Before use check if the seal material is resistant against the measured product and the process temperature The max permissible pressure is specified in chapter Technical data or on the type label of the sensor If there is a risk of the coaxial probe touching the vessel wall during operation due to product movements or agitators etc the measuring probe should be securely fixed...

Страница 16: ...16 4 Mounting VEGAFLEX 81 Profibus PA 44214 EN 171002 1 2 1 2 Fig 6 Fasten the probe 1 Coax probe 2 Retaining sleeve ...

Страница 17: ...t which cable outer diameter the cable gland is suitable for Use a cable gland fitting the cable diameter Please make sure that your installation is carried out according to the Profibus specification In particular make sure that the termination of the bus is done with appropriate terminating resistors You can find detailed information of the cable specification installa tion and topology in the P...

Страница 18: ...d signal output are connected via the spring loaded terminals in the housing Connection to the display and adjustment module or to the interface adapter is carried out via contact pins in the housing Information The terminal block is pluggable and can be removed from the electronics To do this lift the terminal block with a small screwdriver and pull it out When reinserting the terminal block you ...

Страница 19: ...rt ed directly into the terminal openings In case of flexible cores without end sleeves press the terminal from above with a small screwdriver the terminal opening is then free When the screwdriver is released the terminal closes again You can find further information on the max wire cross section under Technical data Electromechanical data 7 Check the hold of the wires in the terminals by lightly...

Страница 20: ...inal compartment single chamber housing 1 Voltage supply signal output 2 For display and adjustment module or interface adapter 3 Selection switch for instrument address 4 For external display and adjustment unit 5 Ground terminal for connection of the cable screen 5 4 Wiring plan double chamber housing The following illustrations apply to the non Ex as well as to the Ex ia version 1 1 5 0 0 5 1 6...

Страница 21: ...ment unit 4 Ground terminal for connection of the cable screen 5 5 Double chamber housing with VEGADIS Adapter 3 1 2 Fig 12 View to the electronics compartment with VEGADIS adapter for connec tion of the external display and adjustment unit 1 VEGADIS adapter 2 Internal plug connection 3 Plug connector M12 x 1 3 4 1 2 Fig 13 View to the plug connector M12 x 1 1 Pin 1 2 Pin 2 3 Pin 3 4 Pin 4 Termina...

Страница 22: ...nized by the control system if the address is set correctly When the instrument is shipped address 126 is set This address can be used to test the function of the instrument and to connect it to a Profibus PA network Then the address must be changed to integrate additional instruments The address setting is carried out either via The address selection switch in the electronics compartment of the i...

Страница 23: ...lection switches The addressing procedure is described in the operating instructions manual Display and adjustment module 5 8 Switch on phase After VEGAFLEX 81 is connected to the bus system the instrument carries out a self test for approx 30 seconds The following steps are carried out Internal check of the electronics Indication of a status message e g F 105 Determine measured value on the displ...

Страница 24: ...y 90 It is not necessary to interrupt the power supply Proceed as follows 1 Unscrew the housing lid 2 Place the display and adjustment module on the electronics in the desired position and turn it to the right until it snaps in 3 Screw housing lid with inspection window tightly back on Disassembly is carried out in reverse order The display and adjustment module is powered by the sensor an ad diti...

Страница 25: ...mber housing 1 In the electronics compartment 2 In the terminal compartment Note If you intend to retrofit the instrument with a display and adjustment module for continuous measured value indication a higher lid with an inspection glass is required 6 2 Adjustment system 1 2 Fig 18 Display and adjustment elements 1 LC display 2 Adjustment keys OK key Key functions ...

Страница 26: ...turns to the main menu The menu language is then switched over to English Approx 60 minutes after the last pressing of a key an automatic reset to measured value indication is triggered Any values not confirmed with OK will not be saved After switching on the VEGAFLEX 81 carries out a short self test where the device software is checked The output signal transmits a fault signal during the switch ...

Страница 27: ...tems in the follow ing chapter Parameter adjustment Extended adjustment 6 4 Parameter adjustment Extended adjustment For technically demanding measuring points you can carry out extended settings in Extended adjustment The main menu is divided into five sections with the following func tions Setup Settings e g measurement loop name medium application vessel adjustment AI FB 1 Channel Scaling Dampi...

Страница 28: ...onnect it to a Profibus PA network Then the address must be changed to integrate additional instruments The address setting is carried out either via The address selection switch in the electronics compartment of the instrument address setting via hardware The display and adjustment module address setting via software PACTware DTM address setting via software Hardware addressing Hardware addressin...

Страница 29: ...stem When choosing Yes then the probe length will be determined automatically When choosing No you can enter the probe length manually Coax probes can be only used in liquids In this menu item the fixed adjusted medium type Liquid is displayed In this menu item you can select the application You can choose between level measurement and interface measurement You can also choose between measurement ...

Страница 30: ... isocyanate chloroform 3 Hydrocarbons Solvents oils liquid gas This menu item is only available if you have chosen interface meas urement under the menu item Application In this menu item you can enter if there is a superimposed gas phase in your application Only set the function to Yes if the gas phase is permanently pre sent This menu item is only available if you have selected interface meas ur...

Страница 31: ...p in mind that the max level must lie below the dead band In this menu item you can enter the min adjustment for the level With interface measurement this is the minimum total level Adjust the requested percentage value with and store with OK Enter the suitable distance value in m for the empty vessel e g distance from the flange to the probe end corresponding to the per centage value The distance...

Страница 32: ...nter the respective distance value in m for the interface correspond ing to the percentage value of the interface The following circumstances cause interfering reflections and can influence the measurement High mounting sockets Vessel internals such as struts Note A false signal suppression detects marks and saves these false signals so that they are no longer taken into account for the level and ...

Страница 33: ... updated The menu item Delete is used to completely delete an already cre ated false signal suppression This is useful if the saved false signal suppression no longer matches the metrological conditions in the vessel A linearisation is necessary for all vessels in which the vessel volume does not increase linearly with the level e g a horizontal cylindri cal or spherical tank when the indication o...

Страница 34: ...socket correction For the vessel height you have to enter the total height of the vessel For the socket correction you have to enter the height of the socket above the upper edge of the vessel If the socket is lower than the up per edge of the vessel this value can also be negative h D h Fig 19 Vessel height and socket correction value D Vessel height h Positive socket correction value h Negative ...

Страница 35: ... the measured level values for 0 and 100 Level measured value min Measured level value max To damp process dependent measured value fluctuations you can set a time of 0 999 s in this menu item The damping applies to the level and interface measurement The default setting is a damping of 0 s In the menu item Lock unlock adjustment you can protect the sen sor parameters against unauthorized or inadv...

Страница 36: ...ect parameters to ensure optimum adjustment of the display options The procedure is described in the following The following submenu points are available The submenu points are described below This menu item enables the setting of the requested national lan guage In delivery status the sensor is set to English In this menu item you define the indication of the measured value on the display You can...

Страница 37: ... on the strength of the supply voltage see Technical data In delivery status the lighting is switched on In this menu item the device status is displayed When the instrument displays a failure message you can here get detailed information on the failure reason The respective min and max measured value is saved in the sen sor The two values are displayed in the menu item Peak values distance If you...

Страница 38: ... peak values of the level measurement In another window you can carry out a reset of the two peak values separately The respective min and max measured values are saved in the sensor The values are displayed in the menu item Peak values Ad ditional This menu item displays the peak values of the electronics tempera ture as well as the dielectric constant In another window you can carry out a reset ...

Страница 39: ...nd set the requested value Push the ESC key to deactivate the simulation Information The simulation is terminated automatically 60 minutes after the activa tion of the simulation With the menu item Setup the echo curve it is possible to save at the time of setup This is generally recommended for using the Asset Management functions it is necessary If possible the curve should be saved with a low l...

Страница 40: ...s is carried out No further safety inquiry follows The following reset functions are available Delivery status Restores the parameter settings at the time of ship ment from the factory incl order specific settings Any stored false signal suppression or user programmed linearisation curve as well as the measured value memory are deleted Basic settings Resetting of the parameter settings incl specia...

Страница 41: ...edium TS 1 5 Tube inner diameter 200 mm Setup Max adjustment Level 100 Max adjustment Level Distance 0 000 m d note block ing distances Min adjustment Level 0 Min adjustment Level Distance Probe length take dead band into account Accept adjustment of the level measurement No Max adjustment Interface 100 Max adjustment Interface Distance 0 000 m d note block ing distances Min adjustment Interface 0...

Страница 42: ...I FB1 Hi Limit 3 402823E 38 AI FB1 Lo Lo Limit 3 402823E 38 AI FB1 Lo Limit 3 402823E 38 AI FB1 Hysteresis 0 50 AI FB1 Fail Safe Mode behaviour in case of mal function Last Valid Out Value last valid measured value AI FB1 Fail Safe Value 0 00 AI FB1 Target Mode Auto Menu Display Menu Menu item Default value Display Language Selected language Displayed value 1 Filling height Level Displayed value 2...

Страница 43: ...re Device memory Measured value memory Re cording in time interval 3 min Device memory Measured value memory Re cording with measured value difference 15 Device memory Measured value memory Start with measured value Not active Device memory Measured value memory Stop with measured value Not active Device memory Measured value memory Stop recording when memory is full Not active Menu Additional adj...

Страница 44: ...s 0 50 AI FB2 Fail Safe Mode behaviour in case of mal function Last Valid Out Value last valid measured value AI FB2 Fail Safe Value 0 00 AI FB2 Target Mode Auto Additional settings AI FB3 Tag Descriptor AI FB3 Channel Primary Value lin percent level AI FB1 scaling PV Scale min 0 AI FB3 scaling PV Scale max 100 AI FB3 Lin Type Linear AI FB3 Out Scale Unit AI FB3 Out Scale Decimal Point AI FB3 Out ...

Страница 45: ... data are stored in the sensor a check is carried out to determine if the data fit the sensor If the data do not fit a fault signal is triggered or the function is blocked When data are being written into the sensor the display shows which instrument type the data originate from and which TAG no this sensor had Tip We recommend to save the instrument adjustments In case of an electronics exchange ...

Страница 46: ...sation data We recommended writing down the adjustment data e g in this op erating instructions manual and archiving them afterwards They are thus available for multiple use or service purposes If the instrument is equipped with a display and adjustment module the data in the sensor can be saved in the display and adjustment module The procedure is described in menu item Copy device settings in th...

Страница 47: ...arisation curve The function can also be used to transfer settings from one instru ment to another instrument of the same type If it is necessary to exchange a sensor the display and adjustment module is inserted into the replacement instrument and the data are likewise written into the sensor via the menu item Copy device settings ...

Страница 48: ...ollec tion The DTMs can also be integrated into other frame applications according to FDT standard Note To ensure that all instrument functions are supported you should always use the latest DTM Collection Furthermore not all described functions are included in older firmware versions You can download the latest instrument software from our homepage A description of the update procedure is also av...

Страница 49: ...ion for complete project documentation as well as a save function for measured value and echo curves In addition there is a tank calculation program as well as a multiviewer for display and analysis of the saved measured value and echo curves The standard version is available as a download under www vega com downloads and Software The full version is avail able on CD from the agency serving you 7 ...

Страница 50: ...is connected Check the connection to the instrument Extended adjustment With the extended adjustment you carry out the parameter adjust ment for the instrument via the clear menu structure in the DTM Device Type Manager This enables additional and special settings over and above those offered by quick setup Maintenance Under the menu item Maintenance you get comprehensive and important support for...

Страница 51: ...are VEGAFLEX 81 Profibus PA 44214 EN 171002 7 4 Saving the parameterisation data We recommend documenting or saving the parameterisation data via PACTware That way the data are available for multiple use or service purposes ...

Страница 52: ... EN 171002 8 Set up with other systems 8 1 DD adjustment programs Device descriptions as Enhanced Device Description EDD are available for DD adjustment programs such as for example AMS and PDM The files can be downloaded at www vega com downloads under Software ...

Страница 53: ...espective measured values The requested values and recording conditions are set via a PC with PACTware DTM or the control system with EDD Data are thus read out and also reset Up to 500 events are automatically stored with a time stamp in the sensor non deletable Each entry contains date time event type event description and value Event types are for example Modification of a parameter Switch on a...

Страница 54: ...ictographs of the status messages 1 Failure red 2 Out of specification yellow 3 Function check orange 4 Maintenance blue Failure Due to a malfunction in the instrument a fault message is outputted This status message is always active It cannot be deactivated by the user Function check The instrument is being worked on the measured value is temporarily invalid for example during simulation This sta...

Страница 55: ...e electronics Send instrument for repair Bit 3 F040 Error in the elec tronics Hardware defect Exchanging the electronics Send instrument for repair Bit 4 F041 Probe loss Cable probe broken or rod probe defective Check probe and exchange if necessary Bit 13 F080 General software error General software error Briefly separate operating voltage Bit 5 F105 Measured value is determined The instrument is...

Страница 56: ...s message Function check and provides information on causes as well as corrective measures Code Text message Cause Rectification TB Diagnostics C700 Simulation active A simulation is active Finish simulation Wait for the automatic end after 60 mins Bit 27 The following table shows the error codes and text messages in the status message Out of specification and provides information on causes as wel...

Страница 57: ...ue available Sensor does not detect an echo during operation Check and correct mounting and or parameter adjustment Bit 20 Process component or probe contaminated or defective Clean or exchange process com ponent or probe Bit 20 M506 Installation Set up error Error during setup Check and correct mounting and or parameter adjustment Check probe length Bit 21 M507 Error in the in strument settings E...

Страница 58: ...djustment not correct Adapt min max adjustment Incorrect linearisation curve Adapt linearisation curve Running time error small meas urement error close to 100 serious error close to 0 Repeat setup 2 Measured value jumps towards 100 Level time 0 Due to the process the amplitude of the product echo decreases A false signal suppression was not carried out Carry out a false signal suppres sion Amplit...

Страница 59: ... range during emptying Level time 0 False signal larger than the level echo Level echo too small Eliminate false signals in the close range Remove contamination on the probe After having removed the source of the false signals the false signal suppression must be deleted Carry out a new false signal suppression 8 Measured value re mains reproducible in one position during emptying Level time 0 Sto...

Страница 60: ...s why you have to carry out a fresh setup after exchanging the electronics If you saved the parameter settings during the first setup of the sen sor you can transfer them to the replacement electronics module A fresh setup is then not necessary 9 6 Software update The following components are required to update the instrument software Instrument Voltage supply Interface adapter VEGACONNECT PC with...

Страница 61: ...lows Print and fill out one form per instrument Clean the instrument and pack it damage proof Attach the completed form and if need be also a safety data sheet outside on the packaging Please contact the agency serving you to get the address for the return shipment You can find the agency on our home page www vega com ...

Страница 62: ...es We use recyclable materials and have designed the electronics to be easily separable Correct disposal avoids negative effects on humans and the environ ment and ensures recycling of useful raw materials Materials see chapter Technical data If you have no way to dispose of the old instrument properly please contact us concerning return and disposal WEEE directive 2012 19 EU This instrument is no...

Страница 63: ...nclosed Ʋ Ʋ Inner conductor up to the separation rod 316L Ʋ Ʋ Spacers PFA Ʋ Ʋ Tube ø 21 3 mm 0 839 in 316L Alloy C22 2 4602 304L Ʋ Ʋ Tube ø 42 2 mm 1 661 in 316L Alloy C22 2 4602 304L Materials non wetted parts Ʋ Ʋ Plastic housing plastic PBT Polyester Ʋ Ʋ Aluminium die cast housing Aluminium die casting AlSi10Mg powder coated basis Polyester Ʋ Ʋ Stainless steel housing precision casting 316L Ʋ Ʋ ...

Страница 64: ...cess fittings tube ø 42 2 mm 1 661 in Ʋ Ʋ Pipe thread cylindrical ISO 228 T1 G1 according to DIN 3852 A Ʋ Ʋ Pipe thread conical ASME B1 20 1 1 NPT Ʋ Ʋ Flanges DIN from DN 50 ASME from 2 Weight Ʋ Ʋ Instrument weight depending on process fitting approx 0 8 8 kg 0 176 17 64 lbs Ʋ Ʋ Tube ø 21 3 mm 0 839 in approx 1110 g m 11 9 oz ft Ʋ Ʋ Tube ø 42 2 mm 1 661 in approx 3100 g m 33 3 oz ft Probe length L...

Страница 65: ...ruments 16 mA 0 5 mA Resolution digital 1 mm 0 039 in Accuracy according to DIN EN 60770 1 Process reference conditions according to DIN EN 61298 1 Ʋ Ʋ Temperature 18 30 C 64 86 F Ʋ Ʋ Relative humidity 45 75 Ʋ Ʋ Air pressure 860 1060 mbar 86 106 kPa 12 5 15 4 psig Mounting reference conditions Ʋ Ʋ Min distance to internal installations 500 mm 19 69 in Ʋ Ʋ Vessel metallic ø 1 m 3 281 ft centric mou...

Страница 66: ...n 5 Lower dead band see following diagrams grey section Typical deviation Interface measure ment 5 mm 0 197 in Typical deviation Total level interface measurement 5 mm 0 197 in Typical deviation Level measurement4 5 See following diagrams 4 Depending on the mounting conditions deviations can occur which can be rectified by adapting the adjustment or changing the measured value offset in the DTM se...

Страница 67: ...1 mm Variables influencing measurement accuracy Temperature drift Digital output 3 mm 10 K relating to the max measuring range or max 10 mm 0 394 in Additional deviation through electromag netic interference acc to EN 61326 10 mm 0 394 in Influence of the superimposed gas and pressure on measurement accuracy The propagation speed of the radar impulses in gas or vapour above the medium is reduced b...

Страница 68: ...fications on the type label The lowest value always applies The measurement error through the process conditions in the specified pressure and temperature range is 1 Process pressure Ʋ Ʋ Standard version 1 40 bar 100 4000 kPa 14 5 580 psig depending on the process fitting Ʋ Ʋ with borosilicate glass leadthrough 1 100 bar 100 10000 kPa 14 5 1450 psig depending on the process fitting Vessel pressure...

Страница 69: ...g on the seal material 1 Aluminium housing 2 Plastic housing 3 Stainless steel housing precision casting 4 Stainless steel housing electropolished 0 C 32 F 40 C 40 F 80 C 176 F 35 C 95 F 40 C 104 F 30 C 86 F 60 C 140 F 200 C 392 F 150 C 302 F 100 C 212 F 50 C 122 F 80 C 176 F 20 C 4 F 1 2 3 4 A B Fig 37 Ambient temperature process temperature version with temperature adapter A Ambient temperature ...

Страница 70: ...land Material seal insert Cable diameter 4 5 8 5 mm 5 9 mm 6 12 mm 7 12 mm 10 14 mm PA NBR Brass nickel plated NBR Stainless steel NBR Wire cross section spring loaded terminals Ʋ Ʋ Massive wire stranded wire 0 2 2 5 mm AWG 24 14 Ʋ Ʋ Stranded wire with end sleeve 0 2 1 5 mm AWG 24 16 Electromechanical data version IP 66 IP 68 1 bar Options of the cable entry Ʋ Ʋ Cable gland with integrated connec ...

Страница 71: ...Housing ABS Ʋ Ʋ Inspection window Polyester foil Functional safety SIL non reactive Integrated clock Date format Day Month Year Time format 12 h 24 h Time zone factory setting CET Max rate deviation 10 5 min year Additional output parameter Electronics temperature Output of the values Ʋ Ʋ Indication Via the display and adjustment module Ʋ Ʋ Analogue Via the current output Ʋ Ʋ Digital Via the digit...

Страница 72: ... floating Ground terminal Galvanically connected with the metal process fitting Galvanic separation between electronics and metal housing parts Ʋ Ʋ Reference voltage 500 V AC Electrical protective measures Protection rating Housing material Version Protection acc to IEC 60529 Protection acc to NEMA Plastic Single chamber IP 66 IP 67 Type 4X Double chamber IP 66 IP 67 Type 4X Aluminium Single chamb...

Страница 73: ...tmap file is used for symbolic indication of the PA instru ment in the configuration tool ID number Each Profibus instrument gets an unambiguous ident number ID number from the Profibus user organisation PNO This ID number is also included in the name of the GSD file Optionally in ad dition to this manufacturer specific GSD file PNO also provides a general so called profile specific GSD file If th...

Страница 74: ... the AI FB3 after scaling Free Place This module must be used if a value in the data telegram of the cyclical data traffic should not be used e g replacement of temperature and Additional Cyclic Value A maximum of three modules can be active By means of the configuration software of the Profibus master you can determine the configuration of the cyclical data telegram with these modules The procedu...

Страница 75: ...are not used in this example Data format of the output signal Byte4 Byte3 Byte2 Byte1 Byte0 Status Value IEEE 754 Fig 39 Data format of the output signal The status byte corresponds to profile 3 02 Profibus PA Profile for Process Control Devices coded The status Measured value OK is coded as 80 hex Bit7 1 Bit6 0 0 The measured value is transferred as a 32 bit floating point number in the IEEE 754 ...

Страница 76: ...alue Failsafe replacement value Failsafe Mode Last val ue and already valid measured value since switching on 0 x 48 uncertain substitute set Switch on simulation Failsafe replacement value Failsafe Mode Fsafe value 0 x 4c uncertain initial value Failsafe replacement value Failsafe Mode Last valid value and no valid measured value since switching on 0 x 51 uncertain sensor con version not accurate...

Страница 77: ... 5 NPT 1 2 ø 79 mm 3 11 Fig 41 Housing versions with protection rating IP 66 IP 67 with integrated display and adjustment module the housing is 9 mm 0 35 in higher 1 Plastic single chamber 2 Plastic double chamber Aluminium housing 2 1 ø 86 mm 3 39 116 mm 4 57 116 mm 4 57 M20x1 5 M20x1 5 NPT 87 mm 3 43 M16x1 5 ø 86 mm 3 39 120 mm 4 72 M20x1 5 NPT Fig 42 Housing versions with protection rating IP 6...

Страница 78: ...m 0 35 in higher 1 Aluminium single chamber 2 Aluminium double chamber Stainless steel housing 69 mm 2 72 ø 79 mm 3 11 117 mm 4 61 M20x1 5 NPT 59 mm 2 32 ø 80 mm 3 15 112 mm 4 41 M20x1 5 NPT 87 mm 3 43 ø 86 mm 3 39 120 mm 4 72 M20x1 5 NPT M16x1 5 3 2 1 Fig 44 Housing versions with protection rating IP 66 IP 68 0 2 bar with integrated display and adjustment module the housing is 9 mm 0 35 in higher...

Страница 79: ... 3 39 M20x1 5 M20x1 5 NPT M16x1 5 93 mm 3 66 ø 80 mm 3 15 112 mm 4 41 M20x1 5 NPT 3 2 1 Fig 45 Housing version with protection rating IP 66 IP 68 1 bar with integrated display and adjustment module the housing is 9 mm 0 35 in higher 1 Stainless steel single chamber electropolished 2 Stainless steel single chamber precision casting 3 Stainless steel double chamber housing precision casting ...

Страница 80: ...W 41 1 61 G1 1 NPT SW 46 1 81 G1 1 NPT G NPT G1 1 NPT G1 1 NPT 46 mm 1 81 ø 21 3 mm 0 84 L 22 mm 0 86 ø 42 2 mm 1 66 SW 55 2 17 51 mm 2 01 G1 1 NPT 1 2 Fig 46 VEGAFLEX 81 threaded version L Sensor length see chapter Technical data 1 Coaxial version ø 21 3 mm 0 839 in 2 Coaxial version ø 42 2 mm 1 661 in ...

Страница 81: ...es droits de propriété intellec tuelle Pour plus d informations on pourra se référer au site www vega com VEGA lineas de productos están protegidas por los derechos en el campo de la propiedad indus trial Para mayor información revise la pagina web www vega com Линии продукции фирмы ВЕГА защищаются по всему миру правами на интеллектуальную собственность Дальнейшую информацию смотрите на сайте www ...

Страница 82: ...tion date 46 False signal suppression 32 Fault rectification 57 Functional principle 8 G Gas phase 30 GSD file 73 H Hardware addressing 22 28 I Inflowing medium 14 Installation position 14 Instrument address 22 28 Instrument master file 73 K Key function 25 L Language 36 Linearisation 33 Lock adjustment 35 M Main menu 27 Meas certainty 38 Measured value indication 36 Measured value memory 53 Measu...

Страница 83: ...ofibus PA 44214 EN 171002 Sensor status 37 Service hotline 59 Simulation 39 Software addressing 23 28 Special parameters 45 Status bytes PA output value 76 T Telegram configuration 75 Type label 7 Type of medium 29 U Units 29 ...

Страница 84: ...e of delivery application practical use and operat ing conditions of the sensors and processing systems correspond to the information available at the time of printing Subject to change without prior notice VEGA Grieshaber KG Schiltach Germany 2017 Phone 49 7836 50 0 Fax 49 7836 50 201 E mail info de vega com www vega com ...

Отзывы: