9 Diagnostics and servicing
VEGAFLEX 81 • Profibus PA
44214-EN-171002
Code
Text message
Cause
Rectification
TB
Diagnostics
S603
Impermissible
operating voltage
•
Operating voltage below specified
range
•
Check electrical connection
•
If necessary, increase operating
voltage
Bit 26
The following table shows the error codes and text messages in the
status message "
Maintenance
" and provides information on causes
as well as corrective measures.
Code
Text message
Cause
Rectification
TB
Diagnostics
M500
Error in the deliv
-
ery status
•
The data could not be restored
during the reset to delivery status
•
Repeat reset
•
Load XML file with sensor data
into the sensor
Bit 15
M501
Error in the
non-active line
-
arisation table
•
Index markers are not continu
-
ously rising, for example illogical
value pairs
•
Check linearisation table
•
Delete table/Create new
Bit 16
M504
Error at a device
interface
•
Hardware defect
•
Exchanging the electronics
•
Send instrument for repair
Bit 19
M505
no measured val
-
ue available
•
Sensor does not detect an echo
during operation
•
Check and correct mounting and/
or parameter adjustment
Bit 20
•
Process component or probe
contaminated or defective
•
Clean or exchange process com
-
ponent or probe
Bit 20
M506
Installation/Set
-
up error
•
Error during setup
•
Check and correct mounting and/
or parameter adjustment
•
Check probe length
Bit 21
M507
Error in the in-
strument settings
•
Error during setup
•
Error when carrying out a reset
•
False signal suppression faulty
•
Carry out reset and repeat setup
Bit 22
9.4 Rectify faults
The operator of the system is responsible for taking suitable meas
-
ures to rectify faults.
The first measures are:
•
Evaluation of fault messages via the adjustment device
•
Checking the output signal
•
Treatment of measurement errors
Further comprehensive diagnostics options are available with a PC
with PACTware and the suitable DTM. In many cases, the reasons can
be determined in this way and faults rectified.
The below tables show typical examples for application-relevant
measurement errors. There are two measurement errors:
Maintenance
Reaction when malfunc-
tion occurs
Procedure for fault recti-
fication
Treatment of measure-
ment errors