9 Diagnosis, asset management and service
VEGABAR 82 • Profibus PA
45031-EN-220624
The data are read out via a PC with PACTware/DTM or the control
system with EDD.
9.4 Asset Management function
The instrument features self-monitoring and diagnostics according
to NE 107 and VDI/VDE 2650. In addition to the status messages in
the following tables there are more detailed error messages available
under the menu item "
Diagnostics
" via the respective adjustment
module.
The status messages are divided into the following categories:
•
Failure
•
Function check
•
Out of specification
•
Maintenance required
and explained by pictographs:
4
1
2
3
Fig. 40: Pictographs of the status messages
1 Failure - red
2 Out of specification - yellow
3 Function check - orange
4 Maintenance required - blue
Malfunction (Failure):
Due to a malfunction in the instrument, a fault signal is output.
This status message is always active. It cannot be deactivated by the
user.
Function check:
The instrument is being worked on, the measured value is temporarily
invalid (for example during simulation).
This status message is inactive by default.
Out of specification:
The measured value is unreliable because an instrument specification
was exceeded (e.g. electronics temperature).
This status message is inactive by default.
Maintenance required:
Due to external influences, the instrument function is limited. The
measurement is affected, but the measured value is still valid. Plan in
maintenance for the instrument because a failure is expected in the
near future (e.g. due to buildup).
This status message is inactive by default.