EMR3 Terminal - Fueling Depot Installation
Installing the Interconnection Box
46
Figure 36. Optional pulse encoder and keypad installations
Installing the Interconnection Box
NATIONAL ELECTRICAL CODE COMPLIANCE
The following information is for general reference and is not intended to replace recommended National Electric
Code (NEC) procedures. It is important for the installer to understand that electrical equipment and wiring located
in Class I, Division 1 and 2 installations shall comply with the latest appropriate articles found in the National
Electric Code (NFPA 70) and the Automotive and Marine Service Station Code (NFPA 30A).
WIRE TYPE FOR NON-BONDED METALLIC OR PVC CONDUIT
Veeder-Root requires the use of shielded cable when using non-bonded metallic or PVC conduit in any portion of
the wiring between the Display Head and the IB. In these installations, shielded cable must be rated less than 100
picofarad per foot and be manufactured with a material suitable for the environment.
emr\emopwir3.eps
Terminal
11
12
13
14
Wire Color
Red
Black
White
Green
Signal
+5V
GND
CHB
CHA
Terminal
02 KP2
03 KP3
04 KP4
05 KP5
06 KP6
07 KP7
08 KP8
Wire Color
Red
Black
White
Green
Yellow
Blue
Orange
Pulse Encoder Cable Connections
Keypad Cable Connections
Display assembly
terminal block
Flexible encoder
spring
Pulse encoder
retaining washer
and nut
Pulse
encoder
Chassis Ground - attached to saddle
clamp and Display Head terminal 1
CGND as shown
Pulse encoder
mounting base
Route cables as
shown to avoid
interference with
flexible shaft.
Use tie wraps to
attach cables firmly
to mounting base
#6 Self tapping
screws (3)
Optional
keypad
Rubber gasket (1)
01 CGND
02 KP2
03 KP3
04 KP4
05 KP5
06 KP6
07 KP7
08 KP8
09 AS-
10 AS+
11 +5V
12 GND
13 C
HB
14 C
HA
15 PTR
16 GND
17 CCS
18 GND
19 ESS
20 TP
21 TP
22 MF-A
23 MF-B
24 PWR
25 GND
26 IB-B
27 IB-A
9/64" (3.58 mm)
max
Note Maximum screwdriver
size for attaching wires to
Display Head terminal block