OPA2-MOD(-H) 

Configuration

 

 

Doc: 70-00-0290, V1.0 R0, Date: 20160208 

© Vector Controls GmbH, Switzerland 

Page 11 

Subject to alteration 

Input configuration 

Address 

Type 

R/W 

Contents 

10000 

bit 

R/W 

Enable internal temperature sensor 

0 = Sensor disabled 

1 = Sensor enabled

 

10001 

bit 

Error state of internal temperature sensor 

0 = OK 
1 = Error 

10002 

16 bit signed  R 

Measured value of internal temperature sensor 

10003 

16 bit signed  R/W 

Internal temperature sensor calibration (-12,7…

0

…12,7 °C/°F) 

10100 

bit 

R/W 

Enable internal humidity sensor(for –H type only) 

0 = Sensor disabled 

1 = Sensor enabled 

10101 

bit 

Error state of internal humidity sensor (for –H type only) 

0 = OK 

1 = Error 

10102 

16 bit signed  R 

Measured value of internal humidity sensor (for –H type only) 

10103 

16 bit signed  R/W 

Internal humidity sensor calibration (-12,7…

0

…12,7 %) 

10200 

selection 

R/W 

Enable external temperature input 

0 = Input disabled 

1 = Input enabled 

10201 

bit 

R/W 

Error state of external temperature input 

0 = ok 

1 = error 

10202 

16 bit signed  R 

Measured value of external temperature input 

10203 

16 bit signed  R/W 

External temperature input calibration (-12,7…

0

…12,7 °C/°F) 

10300 

bit 

R/W 

Digital input “1” function assignment: 

0: No function assigned 

1: Remote disable: Key card or Window contact 

2: Comfort/Standby changeover: Key card or motion detector 

10301 

bit 

Digital input 1 value 

 

 

 

 

10302 

byte 

R/W 

Digital input 1 open character 01 

 

10303 

byte 

R/W 

Digital input 1 open character 02 

10304 

byte 

R/W 

Digital input 1 open character 03 

10305 

byte 

R/W 

Digital input 1 open character 04 

 

 

 

 

10306 

byte 

R/W 

Digital input 1 closed character 01 

 

10307 

byte 

R/W 

Digital input 1 closed character 02 

10308 

byte 

R/W 

Digital input 1 closed character 03 

10309 

byte 

R/W 

Digital input 1 closed character 04 

 

 

 

 

10400 

bit 

R/W 

Digital input “2” function assignment: 

0: No function assigned 

1: Remote disable: Key card or Window contact 

2: Comfort/Standby changeover: Key card or motion detector 

10401 

bit 

Digital input 2 value 

 

 

 

 

10402 

byte 

R/W 

Digital input 2 open character 01 

10403 

byte 

R/W 

Digital input 2 open character 02 

10404 

byte 

R/W 

Digital input 2 open character 03 

10405 

byte 

R/W 

Digital input 2 open character 04 

 

 

 

 

10406 

byte 

R/W 

Digital input 2 closed character 01 

 

10407 

byte 

R/W 

Digital input 2 closed character 02 

10408 

byte 

R/W 

Digital input 2 closed character 03 

10409 

byte 

R/W 

Digital input 2 closed character 04 

 

 

Use Remote disable for key cards or window contacts. If the digital input is opened the device will switch to OFF mode 

after the delay defined with address 1023 (CP19) has expired. Closing the contact will switch the device back on 

immediately. The delay is defined in seconds.  

 

 

Use comfort/standby changeover with key card switches and occupancy sensors. The device will be in occupied mode 

as long as the digital input is connected to signal ground. Once the input is opened it will switch to unoccupied mode 

after the delay defined with address 1024 (CP20) has expired. The delay is defined in minutes.  

 

 

Содержание OPA2-MOD

Страница 1: ...led based on these inputs An external temperature may be measured through the additional temperature input This may be useful for underfloor heating sensor averaging for large rooms outdoor temperatur...

Страница 2: ...ll be connected between the terminals and of the furthermost node of the network Network topology Daisy chain according EIA TIA 485 specifications Recommended maximum length per chain 1200 m 4000 ft E...

Страница 3: ...above air discharge grills and diffusers Location of mounting is less critical if external temperature sensors are used Installation 1 Connect the wires to the terminals of the power case according to...

Страница 4: ...uccessfully for the time period defined with CP18 1022 Verify wiring or operation of Modbus master device To disable this error set CP18 1022 to 0 Err2 The selected sensor is damaged or missing NA The...

Страница 5: ...selection on right key 1 one zone 5 five zones 0 5 1 CP 06 Setpoint change enable 0 disabled 1 enabled 0 1 1 CP 07 Operation mode change ON OFF enabled 0 disabled 1 enabled 0 1 1 CP 08 Operation mode...

Страница 6: ...M 1014 Bit R W AM PM flag 0 AM 1 PM 1015 Bit R W Celsius Fahrenheit 0 Celsius 1 Fahrenheit 1016 Byte R W Timeout in seconds to idle mode 0 255 seconds 1017 Bit R W Idle mode 0 disabled 1 enabled If en...

Страница 7: ...umber of fan speeds 1 3 2003 8bit R W Actual fan speed 2004 bit R W Show fan symbol 0 2005 bit R W Show alarm symbol 0 2006 bit R W Show alarm string 0 2007 bit R W Show heating symbol 0 2008 bit R W...

Страница 8: ...value zone 1 5001 3 setpoint zone 1 5004 or 5005 depending on operation mode 4 value zone 2 6001 5 setpoint zone 2 6004 or 6005 depending on operation mode 6 value zone 3 7001 7 setpoint zone 3 7004 o...

Страница 9: ...2 Clock 13 Alarm text 14 Internal temperature 15 External temperature 16 Relative humidity 17 Digital input 1 18 Digital input 2 4001 Selection R W Contents of small digits 0 empty 1 text string OFF 2...

Страница 10: ...xt string group 1 2 value 3 setpoint Comfort standby depending on operation mode 4 Alarm text 5 internal NTC 6 external NTC 7 humidity value 8 digital input 1 9 digital input 2 5004 16 bit signed R W...

Страница 11: ...byte R W Digital input 1 open character 02 O 10304 byte R W Digital input 1 open character 03 F 10305 byte R W Digital input 1 open character 04 F 10306 byte R W Digital input 1 closed character 01 1...

Страница 12: ...yte R W FAN string 2 character 4 1 11008 byte R W FAN string 3 character 1 F 11009 byte R W FAN string 3 character 2 A 11010 byte R W FAN string 3 character 3 N 11011 byte R W FAN string 3 character 4...

Отзывы: