OPA2-MOD(-H) 

Configuration

 

 

Doc: 70-00-0290, V1.0 R0, Date: 20160208 

© Vector Controls GmbH, Switzerland 

Page 6 

Subject to alteration 

Register definitions 

Terminal Setup 

Address 

Type 

R/W 

Contents 

1000 

8bit 

Hardware version / type 

1001 

8bit 

Software version  

1002 

8bit 

Software revision 

1003 

8bit 

R/W 

Communication address (must be unique in network)(factory default is “

1

”) 

1004 

Selection 

0-4 

R/W 

Baud rate:  
0 = 

19200

 

1 = 4800 

2 = 9600 

3 = 19200 

4 = 38400 

1005 

Bit 

R/W 

Parity mode: 0 = No Parity, 

1 =Even Parity, 

2 = Odd Parity 

1006 

Bit 

R/W 

Mode of communication : 0 = 

RTU, 

1 = ASCII 

1007 

Bit 

R/W 

Allow changing of communication address through broad cast command. (will 

reset automatically after 30 seconds) 

0 = Not allowed, 

1 = Allowed 

1008 

Selection 

0-5 

R/W 

Total number of groups 

0 = one group with fan speed selection on right key 

1 = one group

 

2 = two groups 

3 = three groups 

4 = four groups

 

5 = five groups

 

1009 

Bit 

R/W 

Setpoint change enable 
0 = disabled, 

1 = enabled

 

1010 

Bit 

R/W 

Operation mode change ON/OFF enabled 

0 = disabled, 

1 = enabled

 

1011 

Bit 

R/W 

Operation mode change occupied / unoccupied enabled 

0 = disabled, 

1 = enabled 

1012 

BCD 

R/W 

Clock with hours and minutes in BCD format 

1013 

Bit 

R/W 

24h / 12h Clock mode: 

0 = 24h, 

1 = 12h (AM/PM) 

1014 

Bit 

R/W 

AM/PM flag: 

0 = AM, 

1 = PM 

1015 

Bit 

R/W 

Celsius/Fahrenheit: 

0 = Celsius, 

1 = Fahrenheit 

1016 

Byte 

R/W 

Timeout in seconds to idle mode. (0…255 seconds) 

1017 

Bit 

R/W 

Idle mode, 

0 = disabled

, 1 = enabled

 

If enabled shows a specific screen if no key is pressed for the time defined in 1016

 

1018 

Byte 

R/W 

Maximum number of FAN speeds (1…

3

This setting applies if number of groups is set to “one group with fan speed”.  

(1008 = 0).  

1019 

Byte signed 

-12.7...12.7 

R/W 

Humidity sensor calibration 

1020 

Byte signed 

-12.7...12.7 

R/W 

Internal NTC sensor calibration 

1021 

Byte signed 

-12.7...12.7 

R/W 

External NTC sensor calibration 

1022 

16bit 

R/W 

Modbus communication timeout: If there is no communication within the amount 

of seconds specified here, “Err1” is shown on the small digits. Setting the value to 

“0” disables this feature. 

1023 

Byte 

R/W 

Delay for remote disable function. The delay defines how long the contact needs to 

be open before the device switches into OFF mode. This is used for key card 

switches or window contacts connected to digital inputs. This function is controlled 

with registers 10300/10400.  

1024 

16bit 

R/W 

Delay for standby/comfort switchover function. The delay defines how long the 

contact needs to be open before the device switches into standby mode. This is 

used for key card switches or motion detectors connected to digital inputs. This 

function is controlled with registers 10300/10400.  

 

 

 

Содержание OPA2-MOD

Страница 1: ...led based on these inputs An external temperature may be measured through the additional temperature input This may be useful for underfloor heating sensor averaging for large rooms outdoor temperatur...

Страница 2: ...ll be connected between the terminals and of the furthermost node of the network Network topology Daisy chain according EIA TIA 485 specifications Recommended maximum length per chain 1200 m 4000 ft E...

Страница 3: ...above air discharge grills and diffusers Location of mounting is less critical if external temperature sensors are used Installation 1 Connect the wires to the terminals of the power case according to...

Страница 4: ...uccessfully for the time period defined with CP18 1022 Verify wiring or operation of Modbus master device To disable this error set CP18 1022 to 0 Err2 The selected sensor is damaged or missing NA The...

Страница 5: ...selection on right key 1 one zone 5 five zones 0 5 1 CP 06 Setpoint change enable 0 disabled 1 enabled 0 1 1 CP 07 Operation mode change ON OFF enabled 0 disabled 1 enabled 0 1 1 CP 08 Operation mode...

Страница 6: ...M 1014 Bit R W AM PM flag 0 AM 1 PM 1015 Bit R W Celsius Fahrenheit 0 Celsius 1 Fahrenheit 1016 Byte R W Timeout in seconds to idle mode 0 255 seconds 1017 Bit R W Idle mode 0 disabled 1 enabled If en...

Страница 7: ...umber of fan speeds 1 3 2003 8bit R W Actual fan speed 2004 bit R W Show fan symbol 0 2005 bit R W Show alarm symbol 0 2006 bit R W Show alarm string 0 2007 bit R W Show heating symbol 0 2008 bit R W...

Страница 8: ...value zone 1 5001 3 setpoint zone 1 5004 or 5005 depending on operation mode 4 value zone 2 6001 5 setpoint zone 2 6004 or 6005 depending on operation mode 6 value zone 3 7001 7 setpoint zone 3 7004 o...

Страница 9: ...2 Clock 13 Alarm text 14 Internal temperature 15 External temperature 16 Relative humidity 17 Digital input 1 18 Digital input 2 4001 Selection R W Contents of small digits 0 empty 1 text string OFF 2...

Страница 10: ...xt string group 1 2 value 3 setpoint Comfort standby depending on operation mode 4 Alarm text 5 internal NTC 6 external NTC 7 humidity value 8 digital input 1 9 digital input 2 5004 16 bit signed R W...

Страница 11: ...byte R W Digital input 1 open character 02 O 10304 byte R W Digital input 1 open character 03 F 10305 byte R W Digital input 1 open character 04 F 10306 byte R W Digital input 1 closed character 01 1...

Страница 12: ...yte R W FAN string 2 character 4 1 11008 byte R W FAN string 3 character 1 F 11009 byte R W FAN string 3 character 2 A 11010 byte R W FAN string 3 character 3 N 11011 byte R W FAN string 3 character 4...

Отзывы: