OPA2-MOD(-H) 

Technical data

 

 

Doc: 70-00-0290, V1.0 R0, Date: 20160208 

© Vector Controls GmbH, Switzerland 

Page 3 

Subject to alteration 

Security Advise 

This device is intended to be used for comfort applications. Where a device failure endangers human life and/or property, 

it is the responsibility of the owner, designer and installer to add additional safety devices to prevent or detect a system 

failure caused by such a device failure. The manufacturer of this device cannot be held liable for any damage caused by 

such a failure.  
Failure to follow specifications and local regulations may endanger life, cause equipment damage and void warranty. 

Connection diagram 

 

 

Terminal description: 

0V 

Power supply:  

0V; common for power supply 

24V 

Power supply:  

24V AC or 24V DC 

DI1 

Passive input:  

Binary input, keep open or switch to 0V 

DI2 

Passive input:

 

Binary input, keep open or switch to 0V

 

RT1

 

Passive input: 

NTC 10kΩ @ 25°C (77°F) or open contact 

D0(A)

 

RS485 A: 

Modbus A or - 

D1(B) 

RS485 B: 

Modbus B or + 

GND ISO

 

RS485 Com 

Modbus Reference  

Mounting location  

 

On an easy accessible interior wall, approx. 1.5 m (4.5’) above the floor in an area of average temperature.  

 

Avoid exposure to direct sunlight or other heat sources, e.g. the area above radiators and heat emitting electrical 

equipment.   

 

Avoid locations behind doors, outside walls and below or above air discharge grills and diffusers.   

 

Location of mounting is less critical if external temperature sensors are used 

 

Installation  

1.

 

Connect the wires to the terminals of the power case according to wiring diagram  

2.

 

Install the mounting plate to the flush mounting box. Make sure that the nipple with the front holding screw is 
facing to the ground. Verify that the mounting screw heads do not stand out more than 5 mm (0.2”) off the 

surface of the mounting plate.   

3.

 

Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate.   

4.

 

Carefully lower the front part until the interconnector reaches the mounting-plate. Continue pressing in a gentle 

way until the front part is fully connected. While inserting the connectors, a slight resistance can be felt. This is 

normal. Do not use excessive force!   

5.

 

With a Philips-type screw driver of size #2, carefully tighten the front holding screw to secure the front part to 

the mounting plate. This screw is located on the front lower side of the unit. There is no need to tighten the 

screw too much. 

 

Note:  

Power GND ≠ Modbus common! 

Line polarization: 

The device needs line polarization. This should be done 
at the master device only.  

Each a 680 ohm resistor should be connected between 

D0 and RS485 COM and D1 and RS485 5V. 

On last node on either end of bus only  

connect 120Ω termination resistor between A and B (D0 and D1) 

Modbus Common 
Modbus D0 (A or -) 
Modbus D1 (B or +) 

120Ω 

Balanced pair 

OPA2-MOD 

0V 

24V 

DI1 

DI2 

RT1 

D1 

(B) 

D0 

(A) 

GND 

ISO 

Содержание OPA2-MOD

Страница 1: ...led based on these inputs An external temperature may be measured through the additional temperature input This may be useful for underfloor heating sensor averaging for large rooms outdoor temperatur...

Страница 2: ...ll be connected between the terminals and of the furthermost node of the network Network topology Daisy chain according EIA TIA 485 specifications Recommended maximum length per chain 1200 m 4000 ft E...

Страница 3: ...above air discharge grills and diffusers Location of mounting is less critical if external temperature sensors are used Installation 1 Connect the wires to the terminals of the power case according to...

Страница 4: ...uccessfully for the time period defined with CP18 1022 Verify wiring or operation of Modbus master device To disable this error set CP18 1022 to 0 Err2 The selected sensor is damaged or missing NA The...

Страница 5: ...selection on right key 1 one zone 5 five zones 0 5 1 CP 06 Setpoint change enable 0 disabled 1 enabled 0 1 1 CP 07 Operation mode change ON OFF enabled 0 disabled 1 enabled 0 1 1 CP 08 Operation mode...

Страница 6: ...M 1014 Bit R W AM PM flag 0 AM 1 PM 1015 Bit R W Celsius Fahrenheit 0 Celsius 1 Fahrenheit 1016 Byte R W Timeout in seconds to idle mode 0 255 seconds 1017 Bit R W Idle mode 0 disabled 1 enabled If en...

Страница 7: ...umber of fan speeds 1 3 2003 8bit R W Actual fan speed 2004 bit R W Show fan symbol 0 2005 bit R W Show alarm symbol 0 2006 bit R W Show alarm string 0 2007 bit R W Show heating symbol 0 2008 bit R W...

Страница 8: ...value zone 1 5001 3 setpoint zone 1 5004 or 5005 depending on operation mode 4 value zone 2 6001 5 setpoint zone 2 6004 or 6005 depending on operation mode 6 value zone 3 7001 7 setpoint zone 3 7004 o...

Страница 9: ...2 Clock 13 Alarm text 14 Internal temperature 15 External temperature 16 Relative humidity 17 Digital input 1 18 Digital input 2 4001 Selection R W Contents of small digits 0 empty 1 text string OFF 2...

Страница 10: ...xt string group 1 2 value 3 setpoint Comfort standby depending on operation mode 4 Alarm text 5 internal NTC 6 external NTC 7 humidity value 8 digital input 1 9 digital input 2 5004 16 bit signed R W...

Страница 11: ...byte R W Digital input 1 open character 02 O 10304 byte R W Digital input 1 open character 03 F 10305 byte R W Digital input 1 open character 04 F 10306 byte R W Digital input 1 closed character 01 1...

Страница 12: ...yte R W FAN string 2 character 4 1 11008 byte R W FAN string 3 character 1 F 11009 byte R W FAN string 3 character 2 A 11010 byte R W FAN string 3 character 3 N 11011 byte R W FAN string 3 character 4...

Отзывы: