OPA2-MOD(-H)
Configuration
Doc: 70-00-0290, V1.0 R0, Date: 20160208
© Vector Controls GmbH, Switzerland
Page 10
Subject to alteration
Display zone 1
Address
Type
R/W
Contents
5000
Selection
R/W
Contents of large digits:
0 = empty
1 = text string group 1
2 = value
3 = setpoint (Comfort/Standby depending on operation mode)
4 = Alarm text
5 = internal NTC
6 = external NTC
7 = humidity value
8 = digital input 1.
9 = digital input 2.
5001
16 bit signed R/W
Value of large digits
5002
Selection
R/W
Unit of digits
0 = no unit
1 = %
2 = °C
3 = Pa
5003
Selection
R/W
Contents of small digits:
0 = empty
1 = text string group 1
2 = value
3 = setpoint (Comfort/standby depending on operation mode)
4 = Alarm text
5 = internal NTC
6 = external NTC
7 = humidity value
8 = digital input 1.
9 = digital input 2.
5004
16 bit signed R/W
Comfort setpoint
20.0
5005
16 bit signed R/W
Standby setpoint
20.0
5006
16 bit signed R/W
Setpoint step
0.1;
0.5;
1.0; 2.0; 5.0
5007
16 bit signed R/W
Low setpoint limit
16.0
5008
16 bit signed R/W
High setpoint limit
30.0
5009
8 bit
R/W
Vertical bar 0-10
0
5010
8bit (ASCII)
R/W
Text string letter 1
5011
8bit (ASCII)
R/W
Text string letter 2
L
5012
8bit (ASCII)
R/W
Text string letter 3
P
5013
8bit (ASCII)
R/W
Text string letter 4
1
Display zone 2 – 5
As above with following register addresses:
Group 2 = 6000 – 6013
Group 3 = 7000 – 7013
Group 4 = 8000 – 8013
Group 5 = 9000 – 9013