OPA2-MOD(-H) 

Configuration

 

 

Doc: 70-00-0290, V1.0 R0, Date: 20160208 

© Vector Controls GmbH, Switzerland 

Page 9 

Subject to alteration 

Display in idle mode 

If enabled with address 1017(CP13), this screen is shown if no key is pressed for the time defined in 1016(CP12). 

Pressing the RIGHT or UP/DOWN key while in this screen will move to the Group 1 display.  

Address 

Type 

R/W 

Contents 

4000 

Selection 

R/W 

Contents of large digits:  

0 = empty

 

1 = text string OFF 

2 = value zone 1 (5001) 

3 = setpoint zone 1(5004 or 5005 depending on operation mode) 

4 = value zone 2 (6001) 

5 = setpoint zone 2(6004 or 6005 depending on operation mode) 

6 = value zone 3 (7001) 

7 = setpoint zone 3(7004 or 7005 depending on operation mode) 

8 = value zone 4 (8001) 

9 = setpoint zone 4(8004 or 8005 depending on operation mode) 

10 = value zone 5 (9001) 

11 = setpoint zone 5(9004 or 9005 depending on operation mode) 
12 = Clock 

13 = Alarm text 

14 = Internal temperature 

15 = External temperature 

16 = Relative humidity 

17 = Digital input 1 

18 = Digital input 2 

4001 

Selection 

R/W 

Contents of small digits:  

0 = empty 

1 = text string OFF 

2 = value zone 1 (5001) 

3 = setpoint zone 1(5004 or 5005 depending on operation mode) 

4 = value zone 2 (6001) 

5 = setpoint zone 2(6004 or 6005 depending on operation mode) 

6 = value zone 3 (7001) 

7 = setpoint zone 3(7004 or 7005 depending on operation mode) 

8 = value zone 4 (8001) 

9 = setpoint zone 4(8004 or 8005 depending on operation mode) 

10 = value zone 5 (9001) 

11 = setpoint zone 5(9004 or 9005 depending on operation mode) 
12 = Clock 

13 = Alarm text 

14 = Internal temperature 

15 = External temperature 

16 = Relative humidity 

17 = Digital input 1 

18 = Digital input 2 

4002 

Selection 

R/W 

Contents of vertical bar:  

0 = empty 

1 = bar of zone 1 

2 = bar of zone 2 

3 = bar of zone 3 
4 = bar of zone 4 

5 = bar of zone 5 

4003 

8bit (ASCII) 

R/W 

text string ON letter 1:  

 

4004 

8bit (ASCII) 

R/W 

text string ON letter 2:  

4005 

8bit (ASCII) 

R/W 

text string ON letter 3:  

4006 

8bit (ASCII) 

R/W 

text string ON letter 4:  

 

 

 

Содержание OPA2-MOD

Страница 1: ...led based on these inputs An external temperature may be measured through the additional temperature input This may be useful for underfloor heating sensor averaging for large rooms outdoor temperatur...

Страница 2: ...ll be connected between the terminals and of the furthermost node of the network Network topology Daisy chain according EIA TIA 485 specifications Recommended maximum length per chain 1200 m 4000 ft E...

Страница 3: ...above air discharge grills and diffusers Location of mounting is less critical if external temperature sensors are used Installation 1 Connect the wires to the terminals of the power case according to...

Страница 4: ...uccessfully for the time period defined with CP18 1022 Verify wiring or operation of Modbus master device To disable this error set CP18 1022 to 0 Err2 The selected sensor is damaged or missing NA The...

Страница 5: ...selection on right key 1 one zone 5 five zones 0 5 1 CP 06 Setpoint change enable 0 disabled 1 enabled 0 1 1 CP 07 Operation mode change ON OFF enabled 0 disabled 1 enabled 0 1 1 CP 08 Operation mode...

Страница 6: ...M 1014 Bit R W AM PM flag 0 AM 1 PM 1015 Bit R W Celsius Fahrenheit 0 Celsius 1 Fahrenheit 1016 Byte R W Timeout in seconds to idle mode 0 255 seconds 1017 Bit R W Idle mode 0 disabled 1 enabled If en...

Страница 7: ...umber of fan speeds 1 3 2003 8bit R W Actual fan speed 2004 bit R W Show fan symbol 0 2005 bit R W Show alarm symbol 0 2006 bit R W Show alarm string 0 2007 bit R W Show heating symbol 0 2008 bit R W...

Страница 8: ...value zone 1 5001 3 setpoint zone 1 5004 or 5005 depending on operation mode 4 value zone 2 6001 5 setpoint zone 2 6004 or 6005 depending on operation mode 6 value zone 3 7001 7 setpoint zone 3 7004 o...

Страница 9: ...2 Clock 13 Alarm text 14 Internal temperature 15 External temperature 16 Relative humidity 17 Digital input 1 18 Digital input 2 4001 Selection R W Contents of small digits 0 empty 1 text string OFF 2...

Страница 10: ...xt string group 1 2 value 3 setpoint Comfort standby depending on operation mode 4 Alarm text 5 internal NTC 6 external NTC 7 humidity value 8 digital input 1 9 digital input 2 5004 16 bit signed R W...

Страница 11: ...byte R W Digital input 1 open character 02 O 10304 byte R W Digital input 1 open character 03 F 10305 byte R W Digital input 1 open character 04 F 10306 byte R W Digital input 1 closed character 01 1...

Страница 12: ...yte R W FAN string 2 character 4 1 11008 byte R W FAN string 3 character 1 F 11009 byte R W FAN string 3 character 2 A 11010 byte R W FAN string 3 character 3 N 11011 byte R W FAN string 3 character 4...

Отзывы: