TLC3-ECO Economizer 

O

VERVIEW

 

 

Doc: 70-00-0660, V1.1, Date: 20170322 

© Vector Controls GmbH, Switzerland 

Page 1 

Subject to alteration 

TLC3-ECO Economizer 

 

Features 

 

Compares outdoor temperature with indoor or control 

temperature. Activates free heating or cooling.  

 

Low power energy consumption: < 1W per unit 

 

Relays switching for outputs each up to 300W 

 

Optional external temperature control input 

 

Choose between one 3-point actuator and 2 binary 

outputs. (1 outdoor damper, 1 mechanical enable or fan.)  

 

Password protected programmable user and control 

parameters 

TLC3-ECO-D also includes 

 

Power cap protected real-time clock with 48hr power 

backup 

 

Time schedule events, with many options 

 

Blue backlight 

 

Infrared remote control receiver 

Applications 

 

Economizer:  
Control of outdoor 

damper 

 

For 3-point or spring 
return actuators 

 

With enable for 
mechanical heating 

or cooling or fan 

 

General 

 

TLC3-ECO: 1 independent temperature control loop with 1 heating and 1 cooling sequence. 1 internal 

temperature sensor, 1 outside temperature input, 1 auxiliary input for external temperature input,  heat – 

cool changeover or high/low limit. 

 

The economizer controls an outdoor damper and optional fan. It activates the outdoor damper if there is 

heating or cooling demand and if outdoor conditions are favorable for free heating or cooling. An additional 

input may be used to close the damper based on an open contact input (for example high humidity or bad air 

quality). 

 

Flexible application configuration is made with a parameter-setting routine using the standard operation 

terminal.  

Name 

 

Ordering 

Model 

Item code 

Variation 

Option 

TLC3-ECO-230 

TLC3-ECO-230-W01 

40-10 0214 
40-10 0214-01 

Standard 

Cooling only 

Economizer with:  

1 internal and 1 external temperature sensor 

2 relay normally open outputs

 

TLC3-ECO-D-230 

TLC3-ECO-D-230-W01 

40-10 0215 
40-10 0215-01 

Deluxe 

Cooling only 

Temperature sensors

: Use Vector Controls NTC sensors to achieve maximum accuracy: SDB-Tn10-20 (duct),  

SRA-Tn10 (room), SDB-Tn10-20 and AMI-S10 as immersion sensor.  

Binary auxiliary device

s (e.g. pumps, fans, on/off valves, etc): Do not directly connect devices that exceed specified 

limits in technical specifications – observe startup current on inductive loads. 

Voltage:  

Blank = 230V, 0 = 24V, 1 = 120V 

Housing 

Blank = square housing, U = 2x4” housing 

Control: 

ECO: Economizer

 

Series: 

TLC3

 

T  L  C 

-  E 

 

Содержание 40-10 0214

Страница 1: ...e input heat cool changeover or high low limit The economizer controls an outdoor damper and optional fan It activates the outdoor damper if there is heating or cooling demand and if outdoor condition...

Страница 2: ...tic conditions Temperature Humidity Mechanical conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing class 2M2 Standards conformity RoHS directive...

Страница 3: ...diagram 2 Install the mounting plate to the flush mounting box Make sure that the nipple with the front holding screw is facing to the ground Make sure the mounting screw heads do not stand out more...

Страница 4: ...ue Small digits show set point Vertical bars show analog output value Arrows in position 1 2 and or 3 show active binary digital output stages Power failure All parameters and set points are memorized...

Страница 5: ...4 PRO 1 is shown 1 is blinking UP DOWN to change OPTION to select SEL PRO Pro 1 to Pro 4 OFF ON Step 2 Enable disable time schedule group Pro x is fixed now ON OFF blinks Press UP DOWN to set ON or O...

Страница 6: ...inputs and type of outputs 241 How to change parameters 1 Press UP DOWN buttons simultaneously for three seconds The display will show firmware version and revision number Press the OPTION button to s...

Страница 7: ...ture sensor X1 10 to 10 in 0 1 steps 10 10 0 UP 10 Calibrate external temperature sensor X2 10 to 10 in 0 1 steps 10 10 0 UP 11 Select contents of Large LCD display in standard mode 0 6 2 Indoor Tempe...

Страница 8: ...F CP 08 Min temperature difference required to start free cooling 0 10 0 C 1 0 C 2 0 F CP 09 Switching hysteresis is the difference between switching on and switching off A small hysteresis will incre...

Страница 9: ...tion Function of mechanical heating or cooling activation If there is heating or cooling demand The controller verifies if free heating or cooling is possible based on control logic mentioned on the l...

Отзывы: