Hazardous Location Heaters

Thermostat

INSTRUCTION MANUAL

Summary of Contents for HLTSTAT10C

Page 1: ... 2016 Pentair Equipment Protection 89115889 Rev E P N 89115890 2016 Pentair Equipment Protection 89115889 Rev E P N 89115890 Hazardous Location Heaters Thermostat INSTRUCTION MANUAL ...

Page 2: ...IECEX PTB 07 0054X see www pentairprotect com TABLE OF CONTENTS Application 3 Control Accuracy 3 Technical Data 3 Design Data 3 HLTSTAT Thermostat Nominal Setpoints 3 Explosion Protection 4 Installation Instructions 4 ROUTINE CHECK TESTS 5 Initial Operation 5 Wiring Diagram 7 Maintenance 7 CE Declaration of Conformity 8 WARRANTY 10 RETURN AND REPAIR POLICY 10 LIMITATION OF LIABILITY 11 ...

Page 3: ...uate by 18 F 10 C or more For exact temperature control of an instrument a proportional controller with temperature sensor should be used TECHNICAL DATA DESIGN DATA HLTSTAT10C HLTSTAT20C Rated voltage VAC or VDC 0 400V Maximum Rated Current Amps acc to DIN VDE 0298 10 Temperature Tolerance 5 F 3 C Temperature class T6 Ambient temperature 76 to 140 F 60 to 60 C Maximum permissible operating tempera...

Page 4: ...the connection cable during unpacking and transport Before entering the customer supplied Ex junction box the connection cable must be firmly installed and mechanically protected observing the permissible bending radius of 5 times the outside cable diameter If the connection is made in a hazardous area the connection cable must be connected in a housing that meets the requirements of one of the ty...

Page 5: ...rried out on the installed heating system ɒ Do a Visual inspection to determine if the conditions specified under Installation Instructions are met ɒ Conduct an insulation test INITIAL OPERATION When the routine tests are successfully completed the device can be switched on Spacer Mounting Surface Figure 1 ...

Page 6: ... 2016 Pentair Equipment Protection 6 89115889 Figure 2 Figure 3 ...

Page 7: ...tat Figure 4 MAINTENANCE The thermostat is completely encapsulated in silicone and requires no maintenance Performance and safety tests can be conducted at intervals as determined by the operator in compliance with current regulations Repairs must only be done by the manufacturer In dust hazardous areas applicable requirements of EN 60079 17 and EN 60079 19 must be observed ...

Page 8: ... provision of the following directives ɧɚ ɤɨɬɨɪɭɸ ɪɚɫɩɪɨɫɬɪɚɧɹɟɬɫɹ ɞɚɧɧɨɟ ɡɚɹɜɥɟɧɢɟ ɫɨɨɬɜɟɬɫɬɜɭɟɬ ɫɥɟɞɭɸɳɢɦ ɞɢɪɟɤɬɢɜɚɦ 2014 34 EU ATEX 2006 95 EG LVD 2014 30 EU EMC 2011 65 EU RoHS 2012 19 EU WEEE 2014 34 EU ATEX 2006 95 EC LVD 2014 30 EU EMC 2011 65 EU RoHS 2012 19 EU WEEE 2014 34 EU ATEX 2006 95 EC LVD 2014 30 EU EMC 2011 65 EU RoHS 2012 19 EU WEEE und mit folgenden Normen oder normativen Dokume...

Page 9: ... 2016 Pentair Equipment Protection 89115889 9 NOTES ...

Page 10: ...ir Equipment Protection label affixed to product without written Pentair Equipment Protection approval Pentair Equipment Protection must be notified of a claim in writing not later than fourteen 14 days from the date when Buyer has become aware of such occurrence or where the defect is such that it may cause damage immediately such notice containing a description of how the defect manifests itself...

Page 11: ...is fee If approval is not received within 30 days material will be scrapped and all shipping expenses and corresponding analysis fees will be billed to Buyer I At Buyer s request Failure Analysis can be provided by Pentair Equipment Protection for warrantable goods at no charge Failure analysis for non warranty repairs are subject to a 150 per hour Engineering charge plus any other incurred testin...

Page 12: ... 2016 Pentair Equipment Protection 89115889 Rev E P N 89115890 Pentair Equipment Protection 2100 Hoffman Way Minneapolis MN 55303 USA 1 763 422 2211 1 763 576 3200 PentairProtect com ...