QC-POWER-P96 (Page 1 of 6)

SPECIFICATIONS

DISPLAY

Liquid crystal display with backlight
4 line, 4 digits per line to show electrical Parameters
5

th

 line, 8 digits to show energy

Bar graph for current indication as a % of CT rating

LCD INDICATIONS

- Integration of energy
- Unit is in configuration menu -
Communication in progress
- Maximum & Minimum Demand of Power

WIRING INPUT

3.Ø - 4 wire, 3.Ø - 3 wire, 2.Ø - 3 wire, 1.Ø - 2 wire

RATED INPUT VOLTAGE

11 to 300Vac (L­N); 19 to 519Vac (L­L)

FREQUENCY RANGE

4 5 - 6 5 H z

CT PRIMARY

1A to 10000A (Programmable for any value)

CT SECONDARY

Nominal 5A (min 11mA, Max 6A)

PT PRIMARY

100 to 500KVac (Programmable for any value)

PT SECONDARY

100 to 500Vac (Programmable for any value)

DISPLAY UPDATE TIME

1 Second for parameters

DISPLAY SCROLLING

Automatic 

Manual

POWER CONSUMPTION

<8VA

TEMPERATURE

Operating 

: -10 to 55°C

Storage 

: -20 to 75°C

HUMIDITY

85% non-condensing

MOUNTING

Panel  mounting

WEIGHT

318gms

OUTPUT

Pulsed Output : Voltage range External 24VDC max

Current capacity : 100mA

INSTALATION CATEGORY

Category III

SERIAL COMMUNICATION

Interface Standard
and protocol

RS485 & Modbus RTU

Communication address

1 to 255

Transmission Mode

Half 

duplex

Data types

Float and Integer

Transmission distance

500 Meter maximum

±0.1% of Full Scale

For L-N Voltage >20V

For L-L Voltage >35V

Active Power

Reactive Power

Apparent Power

Active Energy 

Class 1

Reactive Energy 

Class 1

Apparent Energy 

Class 1

MAX / Min Active Power 

1%

MAX / MIN Reactive Power 

1%

MAX Apparent Power 

1%

RESOLUTION

PT Ratio x CT Ratio 

KWh / KVAh / KVArh 

Pulse

<15 

0.01K 

0.01K

<150 

0.1K 

0.1K

<1500 

1K 

1K

<15000 

0.01M 

0.01M

<150000 

0.1M 

0.1M

≥1500000

1M 

1M

NOTE:

1)  For  Voltage,  Current,  Power,  resolution

is automatically adjusted.

2) For Power Factor resolution is 0.001
3)  

Blink  every  5  seconds,  if  a  load  is

connected  to  at  least  1  of  the  3  phases

SAFETY PRECAUTIONS

All  safety  related  codifications,  symbols  and  instructions  that
appear  in  this  operation  manual  or  on  the  equipment  must  be
strictly  followed  to  ensure  the  safety  of  the  operating  personnel
as  well  as  the  instrument.
If  the  equipment  is  not  used  in  the  manner  specified  by  the
manufacturer it might impair the protection provided by the
equipment.

CAUTION

Read 

the 

instructions 

prior 

to 

installation

and operation of the unit

.

CAUTION

Risk of electrical shock

WIRING GUIDELINES

WARNING

1.

To prevent the risk of electric shock, power supply to the
equipment must be kept OFF while installing the wiring.

2.

Wiring shall be done strictly according to the terminal
layout. Confirm that all connections are correct.

3.

Use lugged terminals.

4.

To reduce electromagnetic interference use of wires with
adequate ratings and twists of the same in equal size shall
be made with shortest connections.

5. 

Layout of connecting cables shall be away from any
internal EMI source.

6. 

Cable used for connection to power source, must have a
cross section of 0.5mm2 to 2.5mm2. These wires shall
have current capacity of 6A.

7. 

Copper cable should be used (Stranded or single core
cable).

8. 

 Before attempting work on the device ensure absence of
voltages using appropriate voltage detection device.

INSTALLATION GUIDELINES

MECHANICAL INSTALLATION

For installing the meter
1.  Prepare the panel cut out with the dimensions as shown below.

2.  Push the meter into the panel cut-out. Secure the meter in its place by

fitting  the  clamp  from  the  rear  side.  Fit  clamps  on  both  sides  in
diagonally  opposite  location  for  optimum  fitting.

3.  For proper sealing, tighten the screws evenly with required torque.
4.  Recommended conductor cross section = 1.5mm

2

.

Screw clamps tightening torque = 0.1N-m

CAUTION

The equipment  in  its  installed state must not co  in close proximity to any
heating  sources,  caustic  vapour,  oil,  steam  or  other  unwanted  process
by-products.

EMC Guidelines

1. Use input power cable with shortest connections.
2. Layout  of  connecting  cables  shall  be  away  from  any  internal  EMI

source.

Panel Cut-out

Dimensions (In mm)

Meter Outline

Dimensions (In mm)

TERMINAL CONNECTIONS

CAUTION

1.

This  equipment,  being  of  a  built-in-type,  normally  becomes
a part of a main control panel and  in case the terminals do
not  remain  accessible  to  the  end  user  after  installation  and
internal wire.

2.

Conductors  must  not  come  into  contact  with  the  internal
circuitry of the equipment or  it may  lead to a safety hazard
that  may  in  turn  endanger  life  or  cause  electrical  shock  to
the  operator.

3.

Protection  &  disconnection  means  must  be  installed
between  power  source  and  supply  terminals  to  facilitate
power  ‘ON’  or  ‘OFF’  function  &  must  be  installed  in  a
convenient  position  normally  accessible  to  the  operator.

LEFT HAND CT MOUNTING PHASE CORRECTION

The  meter  phases  L1,  L2  &  L3  are  setup  as  default  for  the  CT  to  be
mounted  as  an  incomer  on  the  RH  (Right  Hand)  side  of  the  board.
Meter  display  shows  rH  when  “I”  is  pressed  for  3  seconds.
When  the  CT  is  mounted  on  the  LH  (Left  Hand)  side  of  the  board  the
phase sequence needs to be reversed.
1.

Press  “I”  for  3  seconds,  then  release  and  then  press  again  for
3  seconds.  Phase  will  be  reversed  and  the  display  will  show
LH.

2.

Wait 5 seconds for the meter to resume online reading. Meter
display shows LH when “I” is pressed for 3 seconds.

SERIAL NUMBER DESCRIPTION

Press PF 

key for 10 seconds to 8 digit serial number only for

10 seconds on the fifth line of the display

QC-POWER-P96

Operating Instructions

QUALITY ELECTRONIC DESIGN

Transmission speed

300, 600, 1200, 2400, 4800

9600, 19200 (bps)

Parity

None, Odd, Even

1 or 2

100mS

Stop bits

Response time

Measurement

Voltage V

L-N

Voltage V

L-L

Current

Frequency

Accuracy

±0.5% of Full Scale

±0.5% of Full Scale

±0.5% of Full Scale

Power factor

±0.1%

1%

1%

1%