TLC3-ECO Economizer 

O

PERATION

 

 

Doc: 70-00-0660, V1.1, Date: 20170322 

© Vector Controls GmbH, Switzerland 

Page 3 

Subject to alteration 

Connection  

 

Terminal description  

 

1  

Power supply:  

0V AC Neutral 

2  

Power supply:  

230VAC 

3  

Y1 

Binary output 230VAC:  

Outdoor damper for spring return actuator 

Open for 3-point actuators 

4  

Y2 

Binary output 230VAC:  

Fan or mechanical heating or cooling 

Close for 3-point actuators 

5  

Signal ground 

Signal ground for external inputs.  

6  

X1

 

NTC 10kΩ @ 25°C (77°F) 

Outdoor sensor 

7  

X2

 

NTC 10kΩ @ 25°C (77°F)  

External temperature sensor   

 

 

Open contact to SGND 

Enable input 

 

Mounting location 

 

Install the controller on an easy accessible interior wall, approx. 1.5 m above the floor in an area of average 

temperature. 

 

Avoid direct sunlight or other heat sources, e.g. the area above radiators and heat emitting equipment.  

 

Avoid locations behind doors, outside walls and below or above air discharge grills and diffusers.  

 

Location of mounting is less critical if external temperature sensors are used. 

 

Ensure adequate air circulation to dissipate heat generated during operation. 

 

Observe local regulations. 

 

Do not mount in wet or condensation prone environments. 

Installation 

1.

 

Connect the wires to be connected to the terminals of the power case according to wiring diagram 

2.

 

Install the mounting plate to the flush mounting box. Make sure that the nipple with the front holding screw is 
facing to the ground. Make sure the mounting screw heads do not stand out more than 5 mm (0.2”) off the 

surface of the mounting plate.  

3.

 

Ensure that the jumpers are set correctly.  

4.

 

Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate.  

5.

 

Carefully lower the front part until the interconnector reaches the mounting-plate. Continue pressing in a gentle 

way until the front part is fully connected. While inserting the connectors, a slight resistance can be felt. This is 

normal. Do not use excessive force!  

6.

 

With a Philips-type screw driver of size #2, carefully tighten the front holding screw to secure the front part to the 

mounting plate. This screw is located on the front lower side of the unit. There is no need to tighten the screw too 

much. 

Warning:  
Live Electrical Components! 

During installation, testing, servicing and 
troubleshooting of Vector Controls 
products, it may be necessary to work with 

live electrical components. Have a qualified 
licensed electrician or other individual who 
has been properly trained in handling live 
electrical components perform these tasks. 
Failure to follow all electrical safety 
precautions when exposed to live electrical 
components could result in death or 
serious injury.

 

X

T INT 

TLC3-ECO 

X1 

X2 

 

 

 

 

Y1 

Y2 

Actua

tor 

 

Содержание 40-10 0214

Страница 1: ...e input heat cool changeover or high low limit The economizer controls an outdoor damper and optional fan It activates the outdoor damper if there is heating or cooling demand and if outdoor condition...

Страница 2: ...tic conditions Temperature Humidity Mechanical conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing class 2M2 Standards conformity RoHS directive...

Страница 3: ...diagram 2 Install the mounting plate to the flush mounting box Make sure that the nipple with the front holding screw is facing to the ground Make sure the mounting screw heads do not stand out more...

Страница 4: ...ue Small digits show set point Vertical bars show analog output value Arrows in position 1 2 and or 3 show active binary digital output stages Power failure All parameters and set points are memorized...

Страница 5: ...4 PRO 1 is shown 1 is blinking UP DOWN to change OPTION to select SEL PRO Pro 1 to Pro 4 OFF ON Step 2 Enable disable time schedule group Pro x is fixed now ON OFF blinks Press UP DOWN to set ON or O...

Страница 6: ...inputs and type of outputs 241 How to change parameters 1 Press UP DOWN buttons simultaneously for three seconds The display will show firmware version and revision number Press the OPTION button to s...

Страница 7: ...ture sensor X1 10 to 10 in 0 1 steps 10 10 0 UP 10 Calibrate external temperature sensor X2 10 to 10 in 0 1 steps 10 10 0 UP 11 Select contents of Large LCD display in standard mode 0 6 2 Indoor Tempe...

Страница 8: ...F CP 08 Min temperature difference required to start free cooling 0 10 0 C 1 0 C 2 0 F CP 09 Switching hysteresis is the difference between switching on and switching off A small hysteresis will incre...

Страница 9: ...tion Function of mechanical heating or cooling activation If there is heating or cooling demand The controller verifies if free heating or cooling is possible based on control logic mentioned on the l...

Отзывы: