TLC3-ECO Economizer 

C

ONTROL 

C

ONFIGURATION

 

 

Doc: 70-00-0660, V1.1, Date: 20170322 

© Vector Controls GmbH, Switzerland 

Page 9 

Subject to alteration 

Output configuration 

Parameter  Description 

Range 

Default 

CP 13 

Y1: Output setting, spring return or 3-point: 
0 = Spring return open/close 

1 = 3-point binary output (Y1 open, Y2 close) 

0…1 

Spring return 

CP 14 

Running time in 3-point mode or delay for fan in seconds 
Delay for mechanical heating or cooling in minutes 

0…255 

90 

CP 15 

Y2: only valid if Y1 = Spring return 

0 = Not used 

1 = mechanical cooling 

2 = mechanical heating 

3 = mechanical heating and cooling 

4 = fan 

0...4 

 

On-Off control 

Two devices may be controlled in case the output setting is 0 (CP13). Y1 controls the outdoor damper. Y2 may 
enable mechanical heating or cooling or a fan. 

 

 

3-point output 

A 3 point actuator has an open and a close input. Applying power to the open input will drive the valve or damper 

open, applying power to the close input will drive the valve or damper to the closed position. 

 

The running time of the actuator may be preset. We recommend to enter the maximum running time under 

maximum load in order to make sure that the damper can fully close and fully open in any circumstance.  

In order to open the damper Y1 will be activated for the preset amount of time. After the expiration of the running 

time Y1 and Y2 will both be OFF. The damper is closed by activating Y2 for the preset amount of time.  

If 0 is entered as running time, the binary output will remain constantly active in open or closed position.  

 

Function of mechanical heating or cooling activation 

If there is heating or cooling demand. The controller verifies if free heating or cooling is possible based on control 

logic mentioned on the last page. If it is not possible, mechanical heating or cooling will be enabled by closing 

contact of Y2.  

If free heating or cooling is active, the timer specified in CP14 will start to run. The timer counts the number of 

minutes. If the set point cannot be reached after defined number for minutes, mechanical heating or cooling is 

enabled. (outdoor damper will remain open until free heating / cooling conditions are not met anymore.  

Setting delay to 0, will not activate mechanical heating or cooling while free heating or cooling is active 

independent of time.  

 

Function of Y2 in fan mode 

In fan mode, the fan activates with a delay defined under CP14 after the outdoor damper starts to open. This will 

give the damper time enough to fully open before the fan starts blowing.  

The fan switches offwhenthe outdoor damper starts to close.  

 

Input configuration 

Parameter  Description 

Range 

Default 

CP 16 

Input X1: Minimum outdoor temperature. If outdoor temperature is 

lower than this temperature, the outdoor damper will close, 

independent of demand. There is a 5 °C hysteresis before reset.  

-40-60°C 

5°C (9°F) 

CP 17 

Input X1: Maximum outdoor temperature. If outdoor temperature is 

higher than this temperature, the outdoor damper will close, 

independent of demand. There is a 5 °C hysteresis before reset.  

-40-60°C 

45°C (113°F) 

CP 18 

Input X2, configuration:  

0 = No external input 
1 = Alternative control input instead of internal sensor 

2 = Close damper if contact is open (high humidity, low air quality) 

0…2 

 

Fan 

Outdoor damper 

Demand 

CP14 

Time [s] 

Содержание 40-10 0214

Страница 1: ...e input heat cool changeover or high low limit The economizer controls an outdoor damper and optional fan It activates the outdoor damper if there is heating or cooling demand and if outdoor condition...

Страница 2: ...tic conditions Temperature Humidity Mechanical conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing class 2M2 Standards conformity RoHS directive...

Страница 3: ...diagram 2 Install the mounting plate to the flush mounting box Make sure that the nipple with the front holding screw is facing to the ground Make sure the mounting screw heads do not stand out more...

Страница 4: ...ue Small digits show set point Vertical bars show analog output value Arrows in position 1 2 and or 3 show active binary digital output stages Power failure All parameters and set points are memorized...

Страница 5: ...4 PRO 1 is shown 1 is blinking UP DOWN to change OPTION to select SEL PRO Pro 1 to Pro 4 OFF ON Step 2 Enable disable time schedule group Pro x is fixed now ON OFF blinks Press UP DOWN to set ON or O...

Страница 6: ...inputs and type of outputs 241 How to change parameters 1 Press UP DOWN buttons simultaneously for three seconds The display will show firmware version and revision number Press the OPTION button to s...

Страница 7: ...ture sensor X1 10 to 10 in 0 1 steps 10 10 0 UP 10 Calibrate external temperature sensor X2 10 to 10 in 0 1 steps 10 10 0 UP 11 Select contents of Large LCD display in standard mode 0 6 2 Indoor Tempe...

Страница 8: ...F CP 08 Min temperature difference required to start free cooling 0 10 0 C 1 0 C 2 0 F CP 09 Switching hysteresis is the difference between switching on and switching off A small hysteresis will incre...

Страница 9: ...tion Function of mechanical heating or cooling activation If there is heating or cooling demand The controller verifies if free heating or cooling is possible based on control logic mentioned on the l...

Отзывы: