Command
Service Code
Class ID
Instance ID
Attribute ID
Service
data length
(number of bytes)
Service
data field
Description
ADAPTIVE
CONTROL
SENSOR DELAY
Set
16
51
1
107
1
X
Get
14
X:
0 = 0, 1 = 0.02, 2 = 0.04, 3 = 0.06, 4 = 0.08, 5 = 0.10, 6 = 0.15
7 = 0.20, 8 = 0.25, 9 = 0.30, 10 = 0.35, 11 = 0.4, 12 = 0.5, 13 = 0.6
14 = 0.8, 15 = 1.0
Note: Refer to «Sensor delay adjustment» for details.
PRESSURE
CONTROL
SETPOINT RAMP
Set
16
51
1
108
1
X
Get
14
X:
0 = 0, 1 = 0.5, 2 = 1.0, 3 = 1.5, 4 = 2.0, 5 = 2.5, 6 = 3.0
7 = 3.5, 8 = 4.0, 9 = 4.5, 10 = 5.0, 11 = 5.5, 12 = 6.0, 13 = 6.5
14 = 7.0, 15 = 7.5, 16 = 8.0, 17 = 8.5, 18 = 9.0, 19 = 9.5, 20 = 10.0
Note: Refer to «Setpoint ramp adjustment» for details.
LEARN
(calibration service)
99
51
1
0
-
-
This command starts LEARN.
With CONTROL MODE commands open valve or close valve the routine may be
interrupted.
Note: Without LEARN the PID controller is not able to perform pressure control.
Refer to «Learn (adaptive control algorithm)» for correct learn gas flow and procedure.
LEARN
PRESSURE LIMIT
(calibration scale)
Set
16
51
1
100
2 integer
4 float
X
Get
14
X:
learn pressure limit according to selected DATA TYPE,
nominal pressure range is 0 … 10’000 (sensor full scale) but it may be scaled,
refer also to command GAIN for details.
This command transfers/reads the pressure limit for LEARN.
Note: Refer to «Learn (adaptive control algorithm)» for correct learn pressure limit setting.
LEARN STATUS
(calibration state)
Get
14
51
1
106
2
X
This command returns the status of the LEARN procedure. The status is binary coded.
X:
Bit
Explanation:
(LSB) 0
LEARN running
1
LEARN data set not present
2
LEARN terminated by user
3
Pressure in position OPEN
> 50% sensor full scale
(of high range sensor in case of a 2 sensor system)
or
> LEARN PRESSURE LIMIT
4
pressure in position 0
< 10% sensor full scale
(of low range sensor in case of a 2 sensor system)
5
Pressure falling during LEARN
6
Sensor not stable during LEARN
7..9 reserved
10
LEARN terminated by controller
11
Pressure in position OPEN negative
(MSB) 12..15 reserved
Содержание 653 AQ Series
Страница 21: ...Series 65 INSTALLATION 982156EB Edition 2019 06 05 21 110 Controller...
Страница 56: ...INSTALLATION Series 65 56 110 Edition 2019 06 05 982156EB Example...
Страница 109: ...Series 65 APPENDIX 982156EB Edition 2019 06 05 109 110 13 Appendix No information entered on time...
Страница 110: ...Series 65 110 110 Edition 2019 06 05 982156EB This page left blank intentionally...