INSTALLATION
Series 65
38/110
Edition 2019-06-05
982156EB
4.5
Valve configuration
Basic valve configuration must be adapted according to application needs.
Definition of valve plate position in case of:
•
After power up, default is ‘close‘.
•
Power failure, default is ‘not defined‘. Only for versions that have Power Fail Option equipped
[653 . . - . . C . - . . . . or 653 . . - . . H . - . . . . ].
•
Network failure, for default settings refer to individual product data sheet.
4.5.1
Homing Start Option
Homing start option defines when the valve performs the homing procedure.
Parameter
Description
Start Condition
Homing start option defines when the valve performs the homing procedure.
Standard
Do homing after restart if valve is not in sealed state
Open Command
Do homing on an open command
Move Command
Do homing on any move command
At Startup
Do homing after restart
Homing Command
Do homing on homing command
Move Command
(Standard)
Settings from move commands, without homing in
close position by close command
End Control Mode This control mode is set after a successful homing.
Position
Moves to position defined in End Position
Close
Closes the valve
Open
Opens the valve
End Position
In case the End Control Mode is set to Position, this parameter defines which
position is set after successful homing.
Parameter location:
CPA
DEVICENET
Valve.Homig
Only End Control Mode in Pressure Controller Object
(Class ID 100)
Содержание 653 AQ Series
Страница 21: ...Series 65 INSTALLATION 982156EB Edition 2019 06 05 21 110 Controller...
Страница 56: ...INSTALLATION Series 65 56 110 Edition 2019 06 05 982156EB Example...
Страница 109: ...Series 65 APPENDIX 982156EB Edition 2019 06 05 109 110 13 Appendix No information entered on time...
Страница 110: ...Series 65 110 110 Edition 2019 06 05 982156EB This page left blank intentionally...