INSTALLATION
Series 642
38/107
Edition 2017-11-24
813316EB
4.6.2
CC-Link configuration
The station type for VAT valves are: Version 2 Remote Device Station.
1. Station Number
The «station number» is used to distinguish between stations on the CC-Link network. Unique station
numbers in consecutive order without duplication must be used, when assigning stations to the CC-Link
network.
The «station number» can be configured by ‘Control View’, ‘Control Performance Analyzer’ or ‘Universal
Hyper Terminal’.
The «set-command» is: «s:25xxx00000». The xxx value is the «station number». Valid range is 001 to
064.
The «get-command» is: «i:25». The answer returns the node address
«i:25xxx00000». The xxx value
is the current «station number».
Consider that the controller must be in local mode to accept the commands! After a «s:25» command is
sent the module is reseted and starts up again.
«c:0100»
change into local mode
«c:0101»
change into remote mode
Example «get-command» with Terminal: