133
English
Characteristic technical data
Model
ENY–P1
ENY–P2
ENY–P3
ENY–P4
Unit weight
Protection rating
with machine installed
Unit power supply
(3)
Maximum total
absorbed current
(3)
Rated absorbed
electrical power
(3)
Total number of fans
Total thermal output recovered
(2)
Maximum recovery efficiency
(2)
Total thermal output recovered
(1)
Thermal efficiency
EU regulation 1253/14
(1)
Minimum supply and return
air flow rate
Supply and return
rated available static pressure
Maximum supply and return
air flow rate
kg
–
V-Ph
A
W
–
kW
%
kW
%
m
3
/h
Pa
m
3
/s
m
3
/h
230-1 + N / 50Hz
180
IP20
4,7
1060
2
15,4
90
9,1
80
600
250
0,47
1700
230-1 + N / 50Hz
154
IP20
3,4
770
2
10,5
90
6,2
80
300
220
0,32
1150
230-1 + N / 50Hz
110
IP20
2,8
330
2
6,5
90
3,9
80
270
170
0,20
720
230-1 + N / 50Hz
290
IP20
6,5
1460
2
24,5
94
14,8
85
690
250
0,72
2600
Overall dimensions
of the packaged unit
Model
ENY–P1
ENY–P2
ENY–P3
ENY–P4
Weight
Dimensions
kg
F
mm
E
mm
D
mm
300
1880
2345
735
190
1430
2245
595
164
1030
1845
510
120
1030
1845
469
1)
Air conditions: TAE = 5°C and t
i
= 25°C, no condensate
2)
Air conditions: TAE = -10°C and t
i
= 20°C, RH
i
50% RH
3)
Basic version without optional electric heaters
Sound power level emitted by
structure
LWA
62
63
56
61
man_Energy Plus IT-UK-FR-DE-ES-NL-FM_Ultima_Rev_0721.indd 133
man_Energy Plus IT-UK-FR-DE-ES-NL-FM_Ultima_Rev_0721.indd 133
24/01/2022 16:06:18
24/01/2022 16:06:18