resistance
Identification
For
heat recovery unit
ENY–P4
ENY–P3
ENY–P2
ENY–P1
BER 40/6/T
BER 35/5/T
BER 25/3/M
BER 25/2/M
Minimum air flow rate
Circular Flange Diameter
D
Amperes absorbed by the resistance
Power supply voltage
Rated power
m
3
/h
mm
A
V/Hz/Ph
kW
690
600
300
270
400
355
250
250
8,7
7,2
13,0
9,1
6,0
4,5
400V 50Hz 3Ph + Pe
3,0
230V 50Hz 1Ph + Pe
2,1
9022414
9022314
9022214
9022114
Code
Pressure drop
BER
Pressure drop (Pa)
Air flow rate (m
3
/h)
ELECTRIC POST-HEATING
COIL BER
(to be placed on the "Intake air"
duct)
Electric heating coil consisting of armored
elements inserted inside a galvanised sheet
metal duct section with circular flanges and
rubber gasket. The electric coil can be used in
premises with air temperature between -20°
C and +40° C and is equipped with double
safety thermostat: one with automatic reset
and one with manual reset. Operation is
controlled by the ON/OFF logic in order to
reach the setpoint of the indoor air heating
controlled by the temperature probe on the
return air flux. The resistance supply circuit is
fitted with an adjustable thermostat, which
has a limiting function. Protection class IP 43.
Supply air
Duct fitted
by the installer
AIR