147
English
−
FC contact to use as ON/OFF
potential free contact for Crystall Filter
If 4 ON post-heating/cooling
NA
FC contact usable
as remote general alarm status
If 4 ON post heating only
7
6
5
With post treatment
No post treatment
4
Valve actuator/E.R. ON/OFF
PWM electric resistance
3
Preheating
Without preheating
2
Installation of F2 intake to right
Installation of F1 intake to left
1
ON
OFF
DIP
DEFAULT
Configuration DIP switches
The electronic board is equipped with a set of 10 Dip switches for configuring the unit, i.e. the
direction of use of the fans, and any accessories to be connected, such as pre- or post-air
treatment coils.
The dip switches configuration must be executed once the unit has been disconnected from
the power supply.
Electronic control board – Connections
man_Energy Plus IT-UK-FR-DE-ES-NL-FM_Ultima_Rev_0721.indd 147
man_Energy Plus IT-UK-FR-DE-ES-NL-FM_Ultima_Rev_0721.indd 147
24/01/2022 16:06:50
24/01/2022 16:06:50