Värmebaronen EK 15E
Menu item - Service level
Quick increase
- Service mode, setting.
0: Off
1: On, speeds up step in / step out rate for 15 minutes.
0
Temporary disconnection of connection delay
after power on, service mode, adjustment.
See also "Advanced Service" level row 14.
0: Normal
1: Temporary disconnection
0
Load guard, the size of the main fuse
in amps. Adjustment 0-50
25
Load guard, stage size current value
expressed as one tenth ampere.
DO NOT CHANGE!
31
Stage limitation
, number of output stages, installed output, that the electric flow heater can work with -
settings 1-7
Step 1
2
3
4
5
6
7
Power output
2.1
4.2 6.3 8.4 10.5 12.6 14.7
kW
Current
3
6.05 9.1 12.1 15.1 18.1 21.2
A
7
UTK function switched off, see Advanced Service Level row 15.
UTK min-Limitation
of the supply line temperature. Adjustment 10-50°C.
10
UTK function switched off, see Advanced Service Level row 15.
UTK Max-Limiting
the supply line temperature. Adjustment 20-80°C.
70
UTK function switched off, see Advanced Service Level row 15.
Room unit,
activate / deactivate adjustment
0: No room unit or switched off
1: Room unit connected
0
UTK function switched off, see Advanced Service Level row 15.
UTK room unit P-factor, 1 / 10th°C / °C. Adjustment 0-100
30
UTK function switched off.
UTK room unit I-factor, 1 / 10th°C / °C / h. Adjustment 0-100
10
Program Version power board, display
Enter 21, for access to "Advanced service level".
0
Delivery setting